Problem |
|
| Cause |
| Correction | |
|
|
|
|
|
| |
|
| 1. | Circuit breaker open or defective. | 1. | Reset or replace circuit breaker. | |
Engine is running, but no AC output | 2. | Fault in generator control panel. | 2. | Contact local service facility. | ||
is available. |
| 3. | Poor wiring connections or | 3. | Check and repair. | |
|
| |||||
|
|
| defective transfer switch. |
|
| |
|
|
|
|
|
| |
|
| 1. | Short circuit in a connected load. | 1. | Disconnect shorted | |
|
|
|
|
| electrical load. | |
|
| 2. | Generator is overloaded. | 2. | Turn off one or more loads. | |
Engine runs good at | 3. | Shorted generator circuit. | 3. | Contact local service facility. | ||
down” when loads are connected. | 4. | Fuel pressure or mixture | 4. | See Gaseous Fuel System in the | ||
|
| |||||
|
|
| is incorrect. |
| installation manual. | |
|
| REPRODUCTION |
| |||
|
| 5. | Kinked fuel line. | 5. | Remove kink. Replace | |
|
|
|
|
| if necessary. | |
|
| 1. | 15 Amp fuse missing or blown. | 1. | Install (new) 15 Amp fuse. | |
|
|
|
|
| See System Control Panel. | |
Engine will not start; or starts and | 2. | Fuel supply turned off or depleted. | 2. | Open fuel valve(s); check | ||
runs rough. | NOT |
|
|
| propane tank. | |
|
| 3. | Failed battery. | 3. | Replace battery. | |
|
| 4. | Fuel pressure is incorrect | 4. | See Gaseous Fuel System in the | |
|
|
|
|
| installation manual. | |
|
|
|
|
|
| |
| for | Fuel supply turned off or depleted. | 1. | Check fuel valves, fill | ||
|
| 1. | ||||
Engine shuts down during operation. |
|
|
| propane tank. | ||
2. | Fault indicator blinking. | 2. | Count blinks and refer to | |||
|
| |||||
|
|
|
|
| Fault Detection System. | |
|
|
|
|
|
| |
Loss of power on circuits. |
| 1. | Generator circuit breaker is open. | 1. | Reset circuit breaker. | |
| 2. | Transfer switch problems. | 2. | See transfer switch manual. | ||
|
| |||||
|
|
|
|
|
|
26