Maintenance

Servicing the System

Before performing any generator maintenance, always perform the following steps:

1.Set generator’s circuit breaker to its OFF position.

2.Press and hold the control board OFF button.

3.Remove 15 Amp fuse from control board.

4.Utility voltage is present at generator control board. Disconnect power before servicing control board by removing the fuses from the transfer switch.

5.After all servicing has been completed, replace fuses in transfer switch, replace 15 Amp fuse in control board, set circuit breaker ON and press and hold control board AUTO button.

Service Code Detection System

The generator may have to run for long periods of time

Reset Service code Detection System

 

 

 

 

REPRODUCTION

with no operator present. For that reason, the system is

The operator must reset the service code detection system

equipped with sensors that automatically shut down the

each time it activates. To do so, press the control board OFF

generator in the event of potentially damaging conditions,

button for 5 seconds. nce the display turns off, leave it off

such as low oil pressure, high temperature, over speed, and

for at least 30 seconds. Remedy the service code condition,

other conditions.

 

 

 

then return the home generator to service by pressing and

The generator’s control board shows service code

holding the control board AUTO button and installing the 15

descriptions scrolling across the digital display. The service

Amp fuse (if removed).

code descriptions are listed below:

 

 

Low Battery Voltage

Low Battery Voltage

 

 

 

This service code is indicated by Low Battery Voltage scrolling

Low Oil Pressure

 

 

 

 

 

 

across the digital display and a single flash on the wireless

Under Voltage

 

for

 

monitor. This condition occurs if the battery voltage drops

Over Voltage

NOT

 

below the preset value. Causes for this problem may be a

 

 

 

service code battery or battery charge circuit. See Battery

• Engine Does Not Start

 

 

 

 

 

 

Charge Circuit,

 

 

 

 

 

Low Frequency

 

 

 

Remove the 15 Amp fuse and disconnect the battery from

 

 

 

 

 

Engine Overspeed

 

 

 

the generator. Test the battery voltage. If voltage meets

High Oil Temperature

 

 

 

specifications, take the battery to a local battery store for

 

 

 

analysis. Or contact your local service center for assistance.

• Transfer Switch Service code

 

 

 

 

Reinstall the battery (replace if necessary - see Battery in

No Wireless Communication

 

 

 

 

Final Installation Considerations in the installation manual).

Battery Charge Circuit

 

 

 

 

 

 

Then reset the service code detection system, as described

earlier.