the Q179C Pilot provides solid state electronic Flame |
| burners and pilot burners are immediately | |||
Safeguard Protection that will not allow the main gas |
| extinguished. Normal operation can be resumed | |||
valves to open on “call for heat” for that will shut |
| when the cause of safety switch malfunction | |||
down main burners within 0.8 second if pilot flame |
| is corrected. Make sure all manual resets are | |||
is not “proved”. Protectorelay will lockout on safety |
| activated where involved. | |||
shutdown within 15 seconds if there is a pilot flame | (2) | PILOT FAILURE | |||
failure on start or, if during the “run” cycle, pilot |
| (a) Pilot failure can occur during the start of | |||
flame is not |
| ||||
| operating cycle of the boiler. Any pilot | ||||
Protectorelay is |
| ||||
| failure, on the Q179C electronic pilot, after | ||||
timing, a solenoid valve in the pilot line will close and |
| ||||
| ignition of pilot flame will close the main | ||||
thus 100% |
| ||||
| gas valves in 0.8 second. | ||||
a. OPERATING INSTRUCTIONS |
| ||||
| (b) For 15 seconds after failure of the Q179 | ||||
(1) | Make sure Manual Main |
| pilot, the relay through terminals #3 and #4 | ||
| all Pilot Valve have been off for at least five |
| will try to | ||
| minutes. |
| pilot flame can be sensed by the flame rod | ||
(2) | Set Operating and Limit Controls to desired |
| circuit, terminal #3 and #4 are | ||
| and the relay will lock out on safety. | ||||
| settings. |
| |||
|
| (c) Pilot failure is caused by the following: | |||
(3) | Turn Manual Main |
| |||
| (1) | Complete loss of gas supply. | |||
| Valve to Open Position. |
| |||
(4) | Turn on Main Electric Switch and Service |
| (2) | Poor ignition spark caused by low | |
| Switch – Pilot will automatically light main |
|
| voltage, poor ground connection, faulty | |
| burners. |
|
| wiring, and possibly a defective ignition | |
SEQUENCE OF OPERATION EE - See Fig. 48 |
|
| transformer. | ||
| (3) | Low gas pressure will prevent flame rod | |||
b. NORMAL OPERATION - 5006B thru 5014B |
| ||||
|
| circuit from sensing pilot flame properly. | |||
(1) | When the operating control calls for heat, |
|
| ||
| (4) | Unusually strong secondary air drafts | |||
| terminal #6 of RA890 Relay is energized. |
|
| can blow the pilot flame away from the | |
(2) A component check circuit in the RA890 Relay |
|
| flame rod momentarily causing nuisance | ||
| is activated which checks the electronic network |
|
| shutdown. | |
| in the relay. |
| (5) A pilot line solenoid valve will not open | ||
(3) | Terminals #3 and #4 of the relay are energized. |
|
| because of faulty wiring, low voltage, or | |
| Terminal #3 opens pilot line solenoid valve |
|
| possibly the valve is defective. | |
| supplying gas to pilot. Terminal #4 energizes |
| (6) A defective RA890 may be the cause | ||
| ignition transformer creating electric spark |
|
| but items (1) thru (5) should be followed | |
| ignition at pilot. |
|
| first. Refer also to RA890 relay literature | |
(4) | Flame rod circuit between Q179C pilot |
|
| furnished with the control. | |
| and RA890 proves presence of pilot flame |
| (d) By referring to the Sequence of Operations | ||
| electronically. |
| |||
|
| step by step operation of the system can | |||
(5) | Terminal #4 to ignition transformer is de- |
| |||
| be controlled and the cause of pilot failure | ||||
| energized. |
| can be readily found. After the cause of | ||
(6) | Terminal #5 is energized and supplies power to |
| the pilot failure has been corrected, resume | ||
| the main gas valves. |
| normal operation by following the Lighting | ||
(7) | Main gas valves open and main burners are |
| Instructions. | ||
| lighted by pilot. | d. SHUTDOWN INSTRUCTIONS | |||
(8) | When operating control is satisfied, terminals | ||||
(1) | Close manual | ||||
| #6 and #5 are | ||||
| (2) | Turn off main electric switch. | |||
| and pilot line solenoid valve are all | ||||
| 8. EE CONTROL SYSTEM – 5015B thru 5026B | ||||
| and main burner and pilot burner flames are | ||||
| extinguished. | The 5015B thru 5026B boilers utilize two EE control | |||
c. SAFETY SHUTDOWN | systems that are interconnected electrically thru all | ||||
(1) SAFETY SWITCH CIRCUIT | operating and safety controls. Should any of the |
If limit control, low water | aforementioned controls break the power supply circuit, | |
both EE control systems would be | ||
electrical safety switch opens, power to terminal | ||
succeeding paragraphs describe the function and | ||
#6 in relay is interrupted thus | ||
operation of each EE Control System. Should a pilot | ||
terminal #5 and #3 in relay which | ||
failure on one EE Control System occur, the other EE | ||
main gas valves and pilot valves. Main gas | ||
Control System would not be affected. Thus main | ||
|