Burnham K50 manual Recommended Piping to BUILT-IN Tankless Heaters, Open GAS Train Cartons

Models: K50

1 116
Download 116 pages 32.31 Kb
Page 31
Image 31

Fig. 27

RECOMMENDED PIPING TO

BUILT-IN TANKLESS HEATERS

36.OPEN GAS TRAIN CARTON(S)

CONNECT GAS TRAIN(S) TO ELBOW ON END OF MANIFOLD(S) according to the Gas Trains on pages

96, 97, 98, 99, 100, 101 or 102.

PRESSURE TESTING of gas service piping must be done before connecting to the boiler gas train. Test for leaks by introducing, from an isolated source, air or inert gas to the piping. Piping shall withstand 3 PSI gage pressure for a period of not less than 10 minutes without showing any drop in pressure.

37.A DRIP LEG SHOULD BE PROVIDED IN THE VERTICAL DROP TO EACH GAS TRAIN, see Fig.

1. An additional Manual Shut-off valve and ground joint union, as show in Fig. 1, should be installed in the piping to each gas train for ease of servicing.

CONNECT GAS SERVICE FROM METER TO GAS TRAIN in accordance with the requirements of the authority having jurisdiction or, in the absence of such

TABLE I - NATURAL GAS

Maximum Capacity of Piping in Cubic Feet of Gas Per Hour

(Based on a Pressure Drop of 0.3” Water

and 0.6 Specific Gravity)

Pipe

 

NOMINAL IRON PIPE SIZE IPS INCHES

 

Length

 

 

 

 

 

 

 

 

¾

1

2

3

4

in Feet

 

 

 

 

 

 

 

 

 

10

278

520

1050

1600

3050

4800

8500

17500

 

 

 

 

 

 

 

 

 

20

190

350

730

1100

2100

3300

5900

12000

 

 

 

 

 

 

 

 

 

30

152

285

590

890

1650

2700

4700

9700

 

 

 

 

 

 

 

 

 

40

130

245

500

760

1450

2300

4100

8300

 

 

 

 

 

 

 

 

 

50

115

215

440

670

1270

2000

3600

7400

 

 

 

 

 

 

 

 

 

60

105

195

400

610

1150

1850

3250

6800

70

96

180

370

560

1050

1700

3000

6200

 

 

 

 

 

 

 

 

 

80

90

170

350

530

990

1600

2800

5800

90

84

160

320

490

930

1500

2600

5400

 

 

 

 

 

 

 

 

 

100

79

150

305

460

870

1400

2500

5100

125

72

130

275

410

78

1250

2200

4500

 

 

 

 

 

 

 

 

 

150

64

12

250

380

710

1130

2000

4100

 

 

 

 

 

 

 

 

 

175

59

110

225

350

650

1050

1850

3800

 

 

 

 

 

 

 

 

 

200

55

100

210

320

610

980

1700

3500

 

 

 

 

 

 

 

 

 

TABLE II

Multipliers to be used with Table I when Pressure Drop is not 0.3”

Pressure Drop

Multiplier

0.1

.577

0.2

.815

 

 

0.5

1.29

1.0

1.83

 

 

0.3

1.00

TABLE III

Multipliers to be used with Tables I and II for

Specific Gravity Other than 0.60

 

 

 

Specific Gravity

Correction Factors

 

.50

1.10

 

 

 

 

.55

1.04

 

 

 

 

.60

1.00

 

.65

.96

 

 

 

 

.70

.93

 

requirements to the –

USA – “National Fuel Gas Code, ANSI Z223.1”.

CANADA – “Installation Codes for Natural and LP Gas Burning Appliances and Equipment, CAN/B149.1 &

.2”.

The size of the gas train(s) is no criteria as to the size of the service from the meter to the gas train(s). Sizing of the service is dependent on:

a.Required supply of gas in cu. ft./hr. input of boiler in BTUH

= heat value of gas, BTU/cu. ft.

b. Allowable loss of pressure in piping to obtain minimum input pressure indicated on rating label of boiler.

31

Page 31
Image 31
Burnham K50 manual Recommended Piping to BUILT-IN Tankless Heaters, Open GAS Train Cartons