(8)When the operating control is satisfied, terminals #6 in the panel and relay are de- energized. Terminal #5, “Main Gas Valve” lamp, Main Gas Valves, and Pilot Line Solenoid Valve are all de-energized and main burner and pilot burner flames are extinguished.

(9)“Main Power” lamp remains lighted. c. SAFETY SHUTDOWN

(1)SAFETY SWITCH CIRCUIT

If limit control, Low Water Cut-Off or any other electrical safety switch opens, power to terminal #6 in Panel is interrupted thus de-energizing terminal #5 in Panel. Consequently Main Gas Valves are de-energized and main burners are immediately extinguished. Normal operation can be resumed when the cause of safety switch malfunction is corrected. Make sure all manual resets are activated where involved.

(2)PILOT FAILURE:

(a)Pilot failure can only occur during the operating cycle of the boiler. Any pilot failure on the Q179C Electronic Pilot, after ignition of pilot flame, will close the main gas valves in 0.8 second.

(b)For 15 seconds, after failure of the Q179 pilot, the relay through terminals #3 and #4 will try to re-establish pilot flame. If no pilot flame can be sensed by the flame rod circuit, terminals #3 and #4 are de- energized, the relay will lock out of safety. “Pilot Failure Alarm Lamp” will be activated.

(c)Pilot failure is caused by the following:

(1)Complete loss of gas supply.

(2)Poor ignition spark caused by low voltage, poor ground connection, faulty wiring, and possibly a defective ignition transformer.

(3)Low gas pressure will prevent flame rod circuit from sensing pilot flame properly.

(4)Unusually strong secondary air drafts can blow the pilot flame away from the rod momentarily causing nuisance shut- down.

(5)A pilot line solenoid valve will not open because of faulty wiring, low voltage, or possibly the valve is defective.

(6)A defective RA890 may be the cause but items (1) thru (5) should be followed first. See also RA890 relay literature furnished with the panel system.

(7)By referring to the Sequence of Operations, step by step operation of the system can be controlled with

 

diligent use of the switches in the

 

Panel(s). In this manner the cause of

66

pilot failure can be readily found. After

 

the cause of pilot failure has been corrected, resume normal operation by following the Lighting Instructions on the Panel.

d.SHUTDOWN INSTRUCTIONS

(1)Turn off switches on panel.

(2)Close manual shut-off valve and pilot valve.

12.EEP CONTROL SYSTEM – 5015B thru 5026B

The 5015B thru 5026B boilers utilize two EEP Control Systems that are interconnected electrically thru all operating and safety controls. Should any of the aforementioned controls break the power supply circuit, both EEP Control Systems would be de-energized.

The succeeding paragraphs describe the function and operation of each EEP Control System. Should a pilot failure on one EE Control System occur, the other EEP Control System would not be affected. Thus main burners on the unaffected side would ignite on a “call for heat” and would continue to operate until the operating control was satisfied.

The EEP Control System functionally is the same as the EE Control System. The RA890F Protectorelay however, is installed in a prewired control cabinet along with a terminal strip, “main power” switch, “main gas valves” switch, “main power” lamp, “main gas valves” lamp, and “pilot failure” lamp.

The EEP Control System utilizes an RA890F Protectorelay and a Q179C Rectification Pilot, which in addition to a pilot burner and rectifying flame rod flame detector to prove pilot, includes an ignition electrode for spark ignition of the pilot. A Webster

612-6A7 Transformer supplies the high voltage spark potential. Once pilot flame is proven, ignition stops but pilot flame continues as long as there is a “call for heat” (intermittent electrically ignited pilot).

The RA890F Protectorelay Primary Control is a non- programming amplifying relay which when used with the Q179C Pilot provides solid state electronic Flame Safeguard Protection that will not allow the main gas valves to open on “call for heat” or that will shut down main burners and turn off “Main Gas Valves” lamp within 0.8 second if pilot flame is not “proved”. Protectorelay will lockout on safety shutdown within 15 seconds if there is a pilot flame failure on start or, if during the “run” cycle, pilot flame is not re-established, “Pilot Failure Alarm Lamp” will come on. Since #3 terminal in the Protectorelay is de-energized at end of safety switch timing, a solenoid valve in the pilot line will close and thus 100% shut-off is achieved.

a.OPERATING INSTRUCTIONS

(1)Turn off all switches on both panels.

(2)Turn off all manual main and pilot gas valves. Wait at least five (5) minutes before proceeding.

(3)Push safety reset button on both panels.

(4)Set Operating Control to desired temperature or pressure.

Page 66
Image 66
Burnham K50 manual Safety Switch Circuit