Burnham K50 Minimum Input Adjustments, V8944B Combination Valve, Motorized Modulating Actuator

Models: K50

1 116
Download 116 pages 32.31 Kb
Page 72
Image 72

CAUTION

The following procedures should only be performed by a qualified service technician.

15.MINIMUM INPUT ADJUSTMENTS

This section covers Minimum Input Adjustments on Honeywell V8944B Diaphragm Type “Lo-Hi-Lo” Gas

Valves, Honeywell V5055B Fluid Power Gas Valves equipped with either a V4062A “Lo-Hi-Lo” Actuator or a V9055A “Modulating” Actuator.

a.Minimum Input Adjustments – “Lo-Hi-Lo” Combination Valve, V8944B (Natural Gas Only)

On boilers equipped with the V8944B combination diaphragm valve/regulator, Low Fire Adjustment should not be less than Minimum Input shown on Rating Plate (1/3 of full rated input). Fig. 57 shows the outlet pressure adjustment screws for low and high fire. The V8944B low and high fire pressure settings are factory set at 0.8” and 3.5” W.C. respectively. If further adjustments are necessary, remove pressure regulator adjustment caps and insert a screwdriver to raise or lower the regulator pressure.

Fig. 57

V8944B COMBINATION VALVE

b. MINIMUM INPUT ADJUSTMENTS – “LO-HI-LO” MOTORIZED ACTUATOR, V4062A

(1)

With power to actuator “off”, remove the

 

wiring compartment cover.

(2)

Check to be sure the low fire adjustment is set

 

at MAX to insure a safe light-off. (Low fire

 

adjustment is preset at factory in the MAX

 

position.)

(3)

Disconnect the controller lead from terminal #4

 

on the actuator to keep the valve in the low fire

 

position.

(4)

Start the system and establish the main burner

 

flame.

(5)

Loosen the setscrew in the cam (Fig. 58A) with

 

the special wrench taped to inside of actuator

 

cover. Keep the wrench seated in the setscrew.

 

Rotate the cam slightly downward (by moving

 

the wrench toward the base of actuator) to open

 

bleed valve. Actuator will start to close.

(6)

When valve reaches desired low fire position,

 

quickly tighten setscrew and remove wrench. If

 

the desire low fire setting is “missed”, merely

 

loosen the setscrew and rotate cam in the

 

opposite direction to the desired set point.

(7)

Shut down burner, and then restart. Repeat

 

several times to be sure the low fire setting

 

is that desired and suitable for correct burner

 

lightoff. Readjust if necessary.

(8)

Disconnect power and reconnect controller lead

 

removed in step (3) above.

(9)

Replace the wiring compartment cover.

c. MINIMUM INPUT ADJUSTMENTS –

MOTORIZED “MODULATING” ACTUATOR,

V9055A

On boilers equipped with Fluid Power Valves that

have “Modulating” Actuators, Low Fire Adjustment

should not be less than Minimum Input shown on

Rating Plate (1/3 of full rated input).

Fig. 58B shows the Low Fire Adjusting Screw

for increasing or decreasing low fire input on the

Honeywell V9055A “Modulating” Actuator. To

adjust the low fire setting after the burners are “on”,

the following procedure should be used.

(1)

With power to actuator “off”, remove the wiring

 

compartment cover.

(2)

Check to make sure the low fire adjustment is

 

set at MAX (full clockwise) to insure a safe

 

light-off. (Low fire adjustment is preset at the

72

On boilers equipped with Fluid Power Valves that have “Lo-Hi-Lo” Actuator, Low Fire Adjustment should not be less than Minimum Input shown on Rating Plate (1/3 of full rated input).

Fig. 58A shows the Limit Switch Cam and Scales to indicate direction to rotate cam for increasing or decreasing low fire input on the Honeywell V4062A “Lo-Hi-Lo” Actuator. To adjust the low fire setting after the burners are “on”, the following procedure should be used.

 

factory in the MAX position.)

(3)

Remove the lead to V9055A terminal R.

 

Jumper terminal R to W. This will prevent the

 

actuator from going to the high fire position.

(4)

Energize the system and light the main burner.

(5)

Use a Phillips screwdriver, or standard type with

 

a blade no more than 3/16 inch wide, to turn

 

the low fire adjusting screw for the desired low

 

fire position. DO NOT PUSH INWARD ON

 

SCREW.

Page 72
Image 72
Burnham K50 manual Minimum Input Adjustments, V8944B Combination Valve, Motorized Modulating Actuator, Screw