Table 65 — MODE - CONFIGURATION (cont)

48/50PD

Table 65 — MODE - CONFIGURATION (cont)

ITEM

EXPANSION

RANGE

UNITS

 

DEFAULT

CCN

CCN POINT

ENTRY

 

TABLE/SUB---TABLE

 

 

 

 

 

 

 

 

HEAT

Heating Configuration

 

 

 

 

HEAT_CFG

 

 

HT.TY

Type of Heat Installed

0=No Heat

 

0

(50 series with no

 

HEATTYPE

 

 

 

1=Gas

 

electric heat)

 

 

 

 

 

2=Electric

 

1

(48 series)

 

 

 

 

 

 

 

2

(50 series with

 

 

 

 

 

 

 

electric heat)

 

 

 

N.HTR

Number of Heat Stages

1 to 2

 

1

(50 series <15kW)

 

NUM_HEAT

 

 

 

 

 

2

(48 series, 50

 

 

 

 

 

 

 

series >=15kW)

 

 

 

MRT.H

Heat Minimum On Time

60 to 999

sec

120

 

HMIN_ON

 

MOT.H

Heat Minimum Off Time

60 to 999

sec

120

 

HMIN_OFF

 

H.DEC

Heat Stage Decrease

120 to 999

sec

300

 

HSTAGDEC

 

 

Time

 

 

 

 

 

 

 

H.INC

Heat Stage Increase Time

120 to 999

sec

450

 

HSTAGINC

 

FOD.E

Fan---off Delay, Elect Heat

10 to 600

sec

30

 

ELEC_FOD

 

FOD.G

Fan---off Delay, Gas Heat

45 to 600

sec

45

 

GAS_FOD

 

HT.LO

Heating Lockout Temp

40 to 125F

dF

75

 

OATLHEAT

 

SAT

SUPPLY AIR

 

 

 

 

 

 

 

 

TEMPERATURE

 

 

 

 

 

 

 

SAT.H

SAT Heat Mode Sensing

Enable/Disable

 

Disable

 

SAT_HEAT

 

SAM.L

Maximum SAT Lower

85 to 200

dF

140

 

SATMAX_L

 

 

Level

 

 

 

 

 

 

 

SAM.U

Maximum SAT Upper

85 to 200

dF

160

 

SATMAX_H

 

 

Level

 

 

 

 

 

 

 

SPT

SPACE TEMPERATURE

 

 

 

 

 

 

 

HT.PD

SPT Heat Demand (+)

0.5 to 5

^F

1

 

 

HDEM_POS

 

 

Level

 

 

 

 

 

 

 

HT.ND

SPT Heat Demand (---)

---5 to ---0.5

^F

---1

 

HDEM_NEG

 

 

Level

 

 

 

 

 

 

 

H.LAG

Heat Thermal Lag Factor

0 to 5

min

1

 

 

HEAT_LAG

 

ECON

Economizer Configuration

 

 

 

 

ECON_CFG

 

 

EC.EN

Economizer Installed

Yes/No

 

No: no FIOP

 

ECONO

 

 

 

 

 

Yes: FIOP

 

 

 

E.CTL

Economizer Control Type

1=Dig/Position

 

1

 

 

ECON_CTL

 

 

 

2=Dig/Command

 

 

 

 

 

 

 

 

3=Analog Ctrl

 

 

 

 

 

 

MP.25

Econ Min at 25%

0 to 100

%

0

 

 

MINP_25

 

 

Fanspeed

 

 

 

 

 

 

 

MP.50

Econ Min at 50%

0 to 100

%

0

 

 

MINP_50

 

 

Fanspeed

 

 

 

 

 

 

 

MP.75

Econ Min at 75%

0 to 100

%

0

 

 

MINP_75

 

 

Fanspeed

 

 

 

 

 

 

 

MP.MX

Econ Min at Max

0 to 100

%

30

 

MINP_MAX

 

 

Fanspeed

 

 

 

 

 

 

 

EC.MX

Econo Cool Max Position

0 to 100

%

100

 

ECONOMAX

 

M.ANG

Min Actuator Ctrl Angle

75 to 90

 

88

 

MINANGLE

 

EH.LO

Econo Cool Hi Temp Limit

40 to 100F

dF

65

 

OATLECLH

 

EL.LO

Econo Cool Lo Temp Limit

---30 to 50F

dF

0

 

 

OATLECLL

 

DF.DB

Diff Dry Bulb Control

Disable/Enable

 

Enable

 

DIFFBULB

 

UEFC

Unoccupied Free Cooling

0=Disabled

 

2

 

 

UEFC_CFG

 

 

 

1=Unoccupied

 

 

 

 

 

 

 

 

2=Preoccupancy

 

 

 

 

 

 

FC.TM

Free Cool PreOcc Time

1 to 9999

min

120

 

UEFCTIME

 

FC.LO

Free Cool Low Temp Limit

---30 to 70F

dF

50

 

OATLUEFC

 

PE.EN

Power Exhaust Installed

Yes/No

 

No: no FIOP

 

PE_ENABL

 

 

 

 

 

Yes: FIOP

 

 

 

PE1.C

Power Exhaust Stage1

100 to 15000

cfm

600

 

PE1_CFM

 

 

CFM

 

 

 

 

 

 

 

PE2.C

Power Exhaust Stage2

100 to 15000

cfm

0

 

 

PE2_CFM

 

 

CFM

 

 

 

 

 

 

 

IDF.C

Indoor Fan Max Speed

500 to 15000

cfm

1600 (05)

 

IDF_CFM

 

 

CFM

 

 

2000 (06)

 

 

 

EN.SW

Enthalpy Switch

0=No Switch

 

0: no FIOP

 

ENTHLCFG

 

 

 

1=Normal Open

 

1: FIOP

 

 

 

 

 

2=Normal Closed

 

 

 

 

 

 

102