Heating Troubleshooting

Heating Troubleshooting

Use the unit Scrolling Marquee display or a CCN device to view the heating status display and the heating diagnostic display (see Appendix A) for information on the heating operation. Check the current alarms and alarm history for any heating alarm codes and correct any causes. (See Table 12.) Verify any unique control configurations per installed site requirements or accessories. If alarms conditions are corrected and cleared, operation of the heat stages and indoor fan may be verified by using the Service Test mode. (See Table 5.)

Phase Reversal Protection

If the control senses an incorrect phase relationship, the relay (K1) will be de-energized (opening its contact). If the phase relationship is correct, the relay will be energized. The control has a self-bypass function after a pre-set time. If the control determines that the three phases stay in a correct relationship for 10 consecutive minutes, the relay will stay energized regardless of the phase sequence of three inputs as long as 24-vac control voltage is applied. This self-bypass function will be reset if all three phases are restored in a phase loss event.

48/50PD

Gas Heat (48PD Units Only)

See Table 12 for general gas heating service analysis. See Fig. 9 for service analysis of the IGC board logic. Check the status LED on the IGC board for any flashing alarm codes and correct any causes. (See Table 13.)

Electric Heat (50PD Units Only)

See Table 14 for electric heating service analysis.

Variable Frequency Drive (VFD) Troubleshooting

The VFD must be in “Auto” mode and when commanding it to 100% the voltage signal should be 10vdc across AI1 and AIGND. Verify all parameters are correct to factory defaults. See Appendix B for parameters and additional troubleshooting.

Phase Loss Protection

The phase loss protection option will monitor the three-phase electrical system to provide phase reversal and phase loss protection.

Phase Loss Protection

If the reverse rotation board senses any one of the three phase inputs has no AC voltage, the relay will be de-energized (opening its contact). This protection is always active as long as 24-vac control voltage is applied, and is not affected by the self by-pass function of the phase sequence monitoring function. However, in the event of phase loss, the relay will be re-energized only if all three phases are restored and the three phases are in the correct sequence.

A red LED is provided to indicate the function of the board. See the table below.

LED STATUS

FUNCTION

On Continuously

Relay contact closed (normal operation).

Blinking

Relay contact open (phase loss or phase

reversal has occurred) --- No power will be

 

supplied to the control system.

Off

24 vac control power not present (off).

Table 12 — Gas Heating Service Analysis

 

 

 

 

 

PROBLEM

CAUSE

REMEDY

Burners Will Not Ignite.

Unit is not configured for heat.

Check heating configurations using ComfortLinkt Scrolling

 

 

 

 

Marquee.

 

 

 

Active alarm.

Check active alarms using ComfortLinkt Scrolling Marquee and

 

 

 

 

the IGC alert flash codes.

 

 

 

No power to unit.

Check power supply, fuses, wiring, and circuit breakers.

 

 

 

No power to IGC.

Check fuses and plugs.

 

 

 

Heaters off due to time guard to prevent short

Check active alarms using ComfortLinkt Scrolling Marquee and

 

 

 

cycling.

the IGC alert flash codes.

 

 

 

Occupancy schedule set point not calling for

Check using ComfortLinkt Scrolling Marquee.

 

 

 

Heating.

 

 

 

 

No gas at main burners.

Check gas line for air and purge as necessary. After purging gas

 

 

 

 

line of air, allow gas to dissipate for at least 5 minutes before

 

 

 

 

attempting to re---light unit.

 

 

 

Water in gas line.

Drain water and install drip.

Inadequate Heating.

Dirty air filters.

Replace air filters.

 

 

 

Gas input too low.

Check gas pressure at manifold. Refer to gas valve adjustment in

 

 

 

 

the Service section.

 

 

 

Occupancy schedule set point set too low.

Check setpoints and adjust if necessary.

 

 

 

Unit undersized for load.

Decrease load or increase of size of unit.

 

 

 

Restricted or low airflow.

Remove restriction, verify proper fan speed operation, and check

 

 

 

 

SAT compared to the SAT heating limits.

 

 

 

Too much outdoor air.

Check economizer position and configuration. Adjust minimum

 

 

 

 

position if needed using ComfortLink Scrolling Marquee. Verify

 

 

 

 

proper fan speed operation.

 

 

 

Limit switch cycles main burners.

Check rotation of blower and temperature rise of unit. Adjust as

 

 

 

 

needed.

Poor Flame

 

Incomplete combustion (lack of combustion air)

Check all screws around flue outlets and burner compartment.

Characteristics.

results in: Aldehyde odors, CO, sooting flame, or

Tighten as necessary.

 

 

 

floating flame.

 

 

 

 

Cracked heat exchanger, replace.

 

 

 

 

 

 

 

 

Unit is over---fired, reduce input. Adjust gas line or manifold

 

 

 

 

pressure.

 

 

 

 

Check vent for restriction. Clean as necessary.

 

 

 

 

Check orifice to burner alignment.

Burners Will Not Turn Off.

Unit is in Minimum on---time.

Check using ComfortLinkt Scrolling Marquee and the IGC alert

 

 

 

 

flash codes.

 

 

 

Unit running in Service Test mode.

Check using ComfortLinkt Scrolling Marquee.

 

 

 

Main gas valve stuck.

Turn off gas supply and unit power. Replace gas valve.

LEGEND

 

 

 

IGC

-

Integrated Gas Controller

 

SAT

-

Supply Air Temperature

 

34

Page 34
Image 34