Table 8 — ComfortLink™ Alarm Codes
|
|
|
|
| |
ALARM |
|
|
|
| |
OR | DESCRIPTION | ACTION TAKEN BY | RESET | PROBABLE CAUSE | |
ALERT | CONTROL | METHOD | |||
|
| ||||
NUMBER |
|
|
|
| |
| Digital Compressor Control Board Alarm | No action | Automatic | See the DSC’s LEDs for troubleshooting | |
| Compressor A1 Safety Trip | Add Strike for Circuit A | Automatic | Current Sensing turned on (CS.A1 = Enable) and | |
| should be off | ||||
|
|
|
| ||
| Service Test | Add Strike for Circuit A | Automatic | Current Sensing turned on (CS.A1 = Enable) and | |
T051 | should be off | ||||
|
|
| |||
| Compressor A1 Current Detected After | Turn off all | Automatic | Current Sensing turned on (CS.A1 = Enable) and | |
| Turnoff | compressors | should be off | ||
|
| ||||
| Service Test | Turn off all | Automatic | Current Sensing turned on (CS.A1 = Enable) and | |
| Detected After Turnoff | compressors | should be off | ||
|
| ||||
T064 | Circuit A Saturated Condensing Temp | Use OAT to control | Automatic | Faulty, shorted, or open thermistor caused by wiring | |
Thermistor Failure | Outdoor fans | error or loose connection. | |||
|
| ||||
T066 | Circuit A Saturated Suction Temperature | No Cooling | Automatic | Suction transducers internally forced inactive | |
Thermistor Failure | |||||
|
|
|
| ||
T073 | Outdoor Air Temperature Thermistor Failure | No cooling with | Automatic | Faulty, shorted, or open thermistor caused by wiring | |
economizer | error or loose connection. | ||||
|
|
| |||
T074 | Space Temperature Thermistor Failure | No heating or cooling | Automatic | Faulty, shorted, or open thermistor caused by wiring | |
error or loose connection. | |||||
|
|
|
| ||
T075 | Supply Air Temperature Thermistor Failure | No cooling mode | Automatic | Faulty, shorted, or open thermistor caused by wiring | |
error or loose connection. | |||||
|
|
|
| ||
T076 | Return Air Thermistor Failure | No differential DB | Automatic | Faulty, shorted, or open thermistor caused by wiring | |
crossover | error or loose connection. | ||||
|
|
| |||
T077 | Space Relative Humidity Sensor Failure | If RH.S = Yes, then no | Automatic | Faulty, shorted, or open sensor caused by wiring | |
indoor humidity control | error or loose connection. | ||||
|
|
| |||
T092 | Circuit A Suction Pressure Transducer | Shutdown Circuit A | Manual | Faulty transducer, faulty | |
Failure | connection | ||||
|
|
| |||
T102 |
| If CS.A1 = Enable, |
| Current Sensing turned on (CS.A1 = Enable) and | |
Compressor A1 Current Sensor Failure | then no T051 current | Automatic | |||
should be off | |||||
|
| alarm |
| ||
|
|
|
| ||
T110 | Circuit A Loss of Charge | Shutdown Circuit A | Manual | Low refrigerant or faulty suction pressure transducer | |
Service Test | Shutdown Circuit A | Manual | Low refrigerant or faulty suction pressure transducer | ||
| |||||
|
|
|
| An overcharged system, high outdoor ambient | |
| Circuit A High Discharge Pressure | Shutdown Circuit A | Automatic | temperature coupled with dirty outdoor coil, plugged | |
T126 |
|
|
| filter drier, or a faulty | |
Service Test |
|
| An overcharged system, high outdoor ambient | ||
|
|
| |||
| Shutdown Circuit A | Automatic | temperature coupled with dirty outdoor coil, plugged | ||
| Pressure | ||||
|
|
| filter drier, or a faulty | ||
|
|
|
| ||
|
|
|
| Low refrigerant charge, dirty filters, evaporator fan | |
|
|
|
| turning backwards, loose or broken fan belt, plugged | |
| Circuit A Low Refrigerant Pressure | Add Strike for Circuit A | Automatic | filter drier, faulty transducer, excessively cold return | |
|
|
|
| air, or stuck open economizer when the ambient | |
T133 |
|
|
| temperature is low. | |
|
|
| Low refrigerant charge, dirty filters, evaporator fan | ||
|
|
|
| ||
| Service Test |
|
| turning backwards, loose or broken fan belt, plugged | |
| Add Strike for Circuit A | Automatic | filter drier, faulty transducer, excessively cold return | ||
| Pressure | ||||
|
|
| air, or stuck open economizer when the ambient | ||
|
|
|
| ||
|
|
|
| temperature is low. | |
T143 | Circuit A Failure To Pressurize | Add Strike for Circuit A | Automatic | Wiring causing reverse rotation or faulty compressor | |
Service Test | Add Strike for Circuit A | Automatic | Wiring causing reverse rotation or faulty compressor | ||
| Pressurize | ||||
|
|
|
| ||
T153 | Real Timeclock Hardware Failure | No time and date | Automatic | No time/date configured, software failure, or MBB | |
schedule operation | failure | ||||
|
|
| |||
A154 | Serial EEPROM Hardware Failure | Unit Shutdown | Automatic | Software failure or MBB failure | |
T155 | Serial EEPROM Storage Failure Error | Unit operation errors | Automatic | Software failure or MBB failure | |
A156 | Critical Serial EEPROM Storage Fail Error | Unit Shutdown | Automatic | Software failure or MBB failure | |
A157 | A/D Hardware Failure | Unit Shutdown | Automatic | Software failure or MBB failure | |
| Circuit A Down Due to Failure | Shutdown Circuit A | Manual | Circuit has 3 strikes or has been locked out by | |
A163 | another alarm | ||||
|
|
| |||
Service Test | Shutdown Circuit A | Manual | Circuit has 1 strike or has been locked out by another | ||
| |||||
| Failure | alarm | |||
|
|
|
* See Legend on next page
48/50PD