Carrier 48/50PD05 manual Appendix A - Local Display And Ccn Tables Cont, Mode - Set Points

Models: 48/50PD05

1 106
Download 106 pages 12.23 Kb
Page 71
Image 71
Table 31 — MODE - SET POINTS

APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)

Table 31 — MODE - SET POINTS

ITEM

EXPANSION

RANGE

UNITS

DEFAULT

CCN TABLE/SUB---TABLE

CCN POINT

 

 

 

 

 

SETPOINT CONFIGURATION

 

SETPOINTS

 

 

 

 

SET_PNT

 

OCSP

Occupied Cool Setpoint

55 to 80F

dF

78

 

OCSP

UCSP

Unoccupied Cool Setpoint

75 to 95F

dF

85

 

UCSP

OHSP

Occupied Heat Setpoint

55 to 80F

dF

68

 

OHSP

UHSP

Unoccupied Heat Setpoint

40 to 80F

dF

60

 

UHSP

GAP

Heat---Cool Setpoint Gap

2 to 10F

^F

5

 

HCSP_GAP

STO.R

SPT Offset Range (+/---)

0 to 5F

^F

5

 

SPTO_RNG

SASP

Cool Supply Air Setpoint

45 to 75

dF

65

 

SASP

RH.SP

Space RH Setpoint

30 to 95

%

50

 

SPRH_SP

RH.DB

Space RH Deadband

2 to 20

%

5

 

SPRH_DB

C.LO

Compressor Lockout Temp

0 to 100F

dF

0

 

OATLCOMP

HT.LO

Heating Lockout Temp

40 to 125F

dF

75

 

OATLHEAT

EH.LO

Econo Cool Hi Temp Limit

40 to 100F

dF

65

 

OATLECLH

EL.LO

Econo Cool Lo Temp Limit

---30 to 50F

dF

0

 

OATLECLL

FC.LO

Free Cool Low Temp Limit

0 to 70F

dF

50

 

OATLUEFC

Table 32 — MODE - INPUTS

ITEM

EXPANSION

RANGE

UNITS

CCN TABLE/SUB---TABLE

CCN

CCN

DISPLAY

WRITE

WRITE

POINT

 

 

 

 

 

STATUS

STATUS

 

 

 

 

 

 

 

 

 

 

STATUS DISPLAY

 

 

 

INPUTS

 

 

 

UINPUTS

 

 

 

GEN.I

General Inputs

 

 

 

 

 

 

FIL.S

Filter Status Switch

Dirty/Clean

 

 

FILTSTAT

forcible

 

FAN.S

Fan Status Switch

On/Off

 

 

FAN_STAT

forcible

 

FDWN

Fire Shutdown Switch

On/Off

 

 

FIREDOWN

forcible

 

ENTH

Outdoor Enthalpy Switch

High/Low

 

 

ENTHALPY

forcible

 

RM.OC

Remote Occupancy Switch

On/Off

 

 

REM_OCC

forcible

 

HUM

Space Humidity Switch

High/Low

 

 

HUM_STAT

forcible

 

CMP.A

Compressor A Feedback

On/Off

 

 

COMP_A

 

 

C.ALM

Scroll Compressor Alarm

On/Off

 

 

COMP_ALM

 

 

CS.IN

Current Sensor Inputs

 

 

 

 

 

 

CS.A1

Compressor A1 Feedback

On/Off

 

 

CS_A1

 

 

AIR.Q

Air Quality Inputs

 

 

 

 

 

 

IAQ.S

IAQ Level (switch)

High/Low

 

 

IAQIN

forcible

forcible

IAQ

IAQ Level (sensor)

xxxx

ppm

 

IAQ

forcible

forcible

OAQ

OAQ Level (sensor)

xxxx

ppm

 

OAQ

forcible

forcible

SP.RH

Space Humidity Sensor

xxx.x

%

 

SPRH

forcible

forcible

48/50PD

71

Page 71
Image 71