Table 33 — MODE - OUTPUTS
ITEM | EXPANSION | RANGE | UNITS | CCN | CCN POINT | CCN | DISPLAY |
WRITE | WRITE | ||||||
|
|
|
|
|
| STATUS | STATUS |
|
|
|
| STATUS DISPLAY |
|
|
|
OUTPUTS |
|
|
| UOUTPUT |
|
|
|
FANS | Fan Outputs |
|
|
|
|
|
|
IDF | Indoor Fan VFD Pwr Relay | On/Off |
|
| IDF |
|
|
F.SPD | Commanded Fan Speed | xxx | % |
| FANSPEED |
|
|
OFC.1 | Outdoor Fan 1 Relay | On/Off |
|
| OFC_1 |
|
|
COOL | Cool Outputs |
|
|
|
|
|
|
CTLR | Digital Scroll Ctrl Pwr | On/Off |
|
| COMPCTLR |
|
|
CAPC | Compressor Capacity | xxx | % |
| CAPACITY |
|
|
CCH | Crankcase Heat Relay | On/Off |
|
| CCH |
|
|
HEAT | Heat Outputs |
|
|
|
|
|
|
HT.1 | Heat Stage 1 Relay | On/Off |
|
| HEAT_1 |
|
|
HT.2 | Heat Stage 2 Relay | On/Off |
|
| HEAT_2 |
|
|
ECON | Economizer Outputs |
|
|
|
|
|
|
EC.CP | Econo Commanded Position | 0 to 100 | % |
| ECONOCMD | forcible | forcible |
EC.AP | Econo Actual Position | 0 to 100 | % |
| ECONOPOS |
|
|
PE.1 | Power Exhaust 1 Relay | On/Off |
|
| PE_1 | forcible | forcible |
PE.2 | Power Exhaust 2 Relay | On/Off |
|
| PE_2 | forcible | forcible |
ALRM | Alarm Relay | On/Off |
|
| ALMOUT | forcible | forcible |