Carrier 48/50PD05 ECB Connections, Display, Point Description, Sensor, Type Of I/O, Name, Outputs

Models: 48/50PD05

1 106
Download 106 pages 12.23 Kb
Page 50
Image 50
Table 20 — ECB Connections

48/50PD

Table 20 — ECB Connections

DISPLAY

POINT DESCRIPTION

 

SENSOR

TYPE OF I/O

CONNECTION

NAME

 

 

LOCATION

 

PIN NUMBER

 

 

 

INPUTS

 

 

 

Input power from MBB

 

control box

24 VAC

J1, 1---2

RM.OC

Remote occupancy switch

 

field installed

switch input

J4, 2

ENTH or

Outdoor enthalpy switch, or

 

economizer, or

switch input

J4, 4

IAQ.S

Indoor air quality switch

 

return/space

 

 

IAQ

Indoor air quality sensor

 

return/space

0---20 mA

J5, 2

OAQ or

Outdoor air quality sensor, or

 

field installed

0---20 mA

J5, 5

SP.RH

Relative humidity sensor

 

 

 

 

 

Sensor Common

 

 

Ground

J5, 3

 

Actuator Common

 

 

Ground

J7, 3

 

 

OUTPUTS

 

 

 

Output power to enthalpy switch

 

 

24 VAC

J4, 3

 

Output power for loop power sensors

 

 

24 VDC

J5, 1

 

Output power to economizer actuator

 

 

24 VAC

J7, 2

PE.1

Power exhaust 1 relay

 

 

relay

J8, 3

PE.2

Power exhaust 2 relay

 

 

relay

J8, 6

EC.CP

Commanded Economizer position

 

 

0---20 mA

J9, 1

 

 

COMMUNICATION

 

 

 

Local Equipment Network (LEN)

 

 

communication

J2, 1---3

 

Carrier Comfort Network (CCN)

 

 

communication

J3

EC.CP &

Economizer actuator position

 

 

MFT

J7, 1

EC.AP

(digital control)

 

 

communication

 

50

Page 50
Image 50
Carrier 48/50PD05 manual ECB Connections, Display, Point Description, Sensor, Type Of I/O, Name, Pin Number, Outputs