48/50PD
Table 20 — ECB Connections
DISPLAY | POINT DESCRIPTION |
| SENSOR | TYPE OF I/O | CONNECTION |
NAME |
|
| LOCATION |
| PIN NUMBER |
|
|
| INPUTS |
|
|
| Input power from MBB |
| control box | 24 VAC | J1, |
RM.OC | Remote occupancy switch |
| field installed | switch input | J4, 2 |
ENTH or | Outdoor enthalpy switch, or |
| economizer, or | switch input | J4, 4 |
IAQ.S | Indoor air quality switch |
| return/space |
|
|
IAQ | Indoor air quality sensor |
| return/space | J5, 2 | |
OAQ or | Outdoor air quality sensor, or |
| field installed | J5, 5 | |
SP.RH | Relative humidity sensor |
|
|
|
|
| Sensor Common |
|
| Ground | J5, 3 |
| Actuator Common |
|
| Ground | J7, 3 |
|
| OUTPUTS |
|
| |
| Output power to enthalpy switch |
|
| 24 VAC | J4, 3 |
| Output power for loop power sensors |
|
| 24 VDC | J5, 1 |
| Output power to economizer actuator |
|
| 24 VAC | J7, 2 |
PE.1 | Power exhaust 1 relay |
|
| relay | J8, 3 |
PE.2 | Power exhaust 2 relay |
|
| relay | J8, 6 |
EC.CP | Commanded Economizer position |
|
| J9, 1 | |
|
| COMMUNICATION |
|
| |
| Local Equipment Network (LEN) |
|
| communication | J2, |
| Carrier Comfort Network (CCN) |
|
| communication | J3 |
EC.CP & | Economizer actuator position |
|
| MFT | J7, 1 |
EC.AP | (digital control) |
|
| communication |
|