APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)
Table 34 — MODE - CONFIGURATION
ITEM | EXPANSION | RANGE | UNITS | DEFAULT | CCN | CCN POINT | PAGE | |
NO. | ||||||||
|
|
|
|
|
| |||
CONFIGURATION |
|
|
|
| SERVICE |
|
| |
|
|
|
|
| CONFIGURATION |
|
| |
DISP | Display Configuration |
|
|
| DISPLAY |
|
| |
METR | Metric Display | On/Off |
| Off |
| DISPUNIT | 11 | |
LANG | Language Selection | 0=English |
| 0 |
| LANGUAGE | 11 | |
|
| 1=Spanish |
|
|
|
|
| |
|
| 2=French |
|
|
|
|
| |
|
| 3=Portuguese |
|
|
|
|
| |
PROT | Password Enable | Enable/Disable |
| Disable |
| PASS_EBL | 12 | |
PSWD | Service Password | 0000 to 9999 |
| 1111 |
| PASSWORD | 12 | |
TEST | Test Display LEDs | On/Off |
| Off | (display only, not in | DISPTEST | 12 | |
|
|
|
|
| table) |
|
| |
UNIT | Unit Configuration |
|
|
| UNIT |
|
| |
S.DLY | Startup Delay | 0 to 600 | sec | 30 |
| STARTDLY | 12 | |
OC.FN | Fan On When Occupied | Yes/No |
| Yes |
| OCC_FAN | 12 | |
IDF.F | Shut Down on IDF Failure | Yes/No |
| Yes |
| FATALFAN | 12 | |
FS.MX | Supply Fan Maximum | 80 to 100 | % | 100 |
| SPEEDMAX | 12 | |
| Speed |
|
|
|
|
|
| |
FS.MN | Supply Fan Minimum | 10 to 40 | % | 20 |
| SPEEDMIN | 12 | |
| Speed |
|
|
|
|
|
| |
FS.VM | Vent Mode Fan Speed | 40 to 100 | ^F | 50 |
| SPEEDVNT | 12 | |
FN.SW | Fan Status Switch | 0=No Switch |
| 0: no FIOP |
| FANSTCFG | 12 | |
|
| 1=Normal Open |
| 1: FIOP |
|
|
| |
|
| 2=Normal Closed |
|
|
|
|
| |
FL.SW | Filter Status Switch | 0=No Switch |
| 0: no FIOP |
| FILSTCFG | 12 | |
|
| 1=Normal Open |
| 1: FIOP |
|
|
| |
|
| 2=Normal Closed |
|
|
|
|
| |
FS.SW | Fire Shutdown Switch | 0=No Switch |
| 0: no FIOP |
| SHTDNCFG | 12 | |
|
| 1=Normal Open |
| 1: FIOP |
|
|
| |
|
| 2=Normal Closed |
|
|
|
|
| |
RM.SW | Remote Occupancy | 0=No Switch |
| 0 |
| REMOCCFG | 12 | |
| Switch | 1=Normal Open |
|
|
|
|
| |
|
| 2=Normal Closed |
|
|
|
|
| |
RH.S | RH Sensor on OAQ Input | Yes/No |
| No |
| RH_OAQ | 13 | |
RH.SW | Space Humidity Switch | 0=No Switch |
| 0 |
| HUMSTCFG | 13 | |
|
| 1=Normal Open |
|
|
|
|
| |
|
| 2=Normal Closed |
|
|
|
|
| |
TCS.C | Temp Cmp Strt Cool Factr | 0 to 60 | mins | 0 |
| TCSTCOOL | 13 | |
TCS.H | Temp Cmp Strt Heat Factr | 0 to 60 | mins | 0 |
| TCSTHEAT | 13 | |
COOL | Cooling Configuration |
|
|
| COOL_CFG |
|
| |
MIN.C | Min Compressor Capacity | 15 to 80 | % | 70 |
| MIN_CAPC | 14 | |
FS.CD | Fan Speed Control | 1 to 9.9 | ^F | 3 |
| SPEEDDMD | 17 | |
| Demand |
|
|
|
|
|
| |
MRT.C | Compressor Min On Time | 120 to 999 | sec | 180 |
| MIN_ON |
| |
MOT.C | Compressor Min Off Time | 300 to 999 | sec | 300 |
| MIN_OFF |
| |
RST.C | Runtime to Reset Strikes | 120 to 999 | sec | 300 |
| MIN_ON_S | 24 | |
FOD.C | 0 to 600 | sec | 60 |
| COOL_FOD |
| ||
CS.A1 | Current Sensing A1 | Enable/Disable |
| Disable: reserved for |
| A1_SENSE | 25 | |
|
|
|
| future use |
|
|
| |
|
|
|
| DO NOT ENABLE |
|
|
| |
C.LO | Compressor Lockout | 0 to 100F | dF | 0 |
| OATLCOMP |
| |
| Temp |
|
|
|
|
|
| |
ALM.N | Alert Each Strike | Yes//No |
| Yes |
| ALM_NOW | 24 | |
SAT | Supply Air Temperature |
|
|
|
|
|
| |
SASP | Cool Supply Air Setpoint | 45 to 75 | dF | 65 |
| SASP | 17 | |
SA.MU | SASP Maximum Reset Up | 0 to 20 | ^F | 10 |
| SASPMAXU | 18 | |
SA.MD | SASP Maximum Reset | ^F |
| SASPMAXD | 18 | |||
| Down |
|
|
|
|
|
| |
SAT.U | Minimum SAT Upper Level | 35.0 to 65.0 | dF | 60 |
| SATMIN_H |
| |
SAT.L | Minimum SAT Lower Level | 35.0 to 65.0 | dF | 45 |
| SATMIN_L |
| |
SST | Low Suction Control |
|
|
|
|
|
| |
SST.O | Suction OK Temperature | 10 to 50 | dF | 18 |
| SSTOK | 26 | |
SST.1 | Low Suction | 10 to 50 | dF | 20 |
| SSTLEV1 | 26 | |
SST.2 | Low Suction | 5 to 50 | dF | 15 |
| SSTLEV2 | 26 | |
SST.3 | Low Suction | 0 to 50 | dF | 10 |
| SSTLEV3 | 26 | |
PSI.D | Ckt A Minimum Pressure | 0 to 500 | psig | 20 |
| DELTAP_A | 26 | |
OFC | Outdoor Fan Control |
|
|
|
|
|
| |
1.MXP | Fan Lev1 Max Pressure | 100 to 500 | psig | 450 |
| LEV1MAXP | 15 | |
2.MNP | Fan Lev2 Min Pressure | 100 to 500 | psig | 200 |
| LEV2MINP | 15 | |
2.ON | Fan Lev2 On Temperature | 0 to 100 | F | 55 |
| LEV2ON | 15 | |
2.OFF | Fan Lev2 Off Temperature | 0 to 100 | F | 45 |
| LEV2OFF | 15 |
48/50PD
73