Carrier 48/50PD05 manual Appendix A - Local Display And Ccn Tables Cont, Mode - Configuration

Models: 48/50PD05

1 106
Download 106 pages 12.23 Kb
Page 73
Image 73
Table 34 — MODE - CONFIGURATION

APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)

Table 34 — MODE - CONFIGURATION

ITEM

EXPANSION

RANGE

UNITS

DEFAULT

CCN

CCN POINT

PAGE

TABLE/SUB---TABLE

NO.

 

 

 

 

 

 

CONFIGURATION

 

 

 

 

SERVICE

 

 

 

 

 

 

 

CONFIGURATION

 

 

DISP

Display Configuration

 

 

 

DISPLAY

 

 

METR

Metric Display

On/Off

 

Off

 

DISPUNIT

11

LANG

Language Selection

0=English

 

0

 

LANGUAGE

11

 

 

1=Spanish

 

 

 

 

 

 

 

2=French

 

 

 

 

 

 

 

3=Portuguese

 

 

 

 

 

PROT

Password Enable

Enable/Disable

 

Disable

 

PASS_EBL

12

PSWD

Service Password

0000 to 9999

 

1111

 

PASSWORD

12

TEST

Test Display LEDs

On/Off

 

Off

(display only, not in

DISPTEST

12

 

 

 

 

 

table)

 

 

UNIT

Unit Configuration

 

 

 

UNIT

 

 

S.DLY

Startup Delay

0 to 600

sec

30

 

STARTDLY

12

OC.FN

Fan On When Occupied

Yes/No

 

Yes

 

OCC_FAN

12

IDF.F

Shut Down on IDF Failure

Yes/No

 

Yes

 

FATALFAN

12

FS.MX

Supply Fan Maximum

80 to 100

%

100

 

SPEEDMAX

12

 

Speed

 

 

 

 

 

 

FS.MN

Supply Fan Minimum

10 to 40

%

20

 

SPEEDMIN

12

 

Speed

 

 

 

 

 

 

FS.VM

Vent Mode Fan Speed

40 to 100

^F

50

 

SPEEDVNT

12

FN.SW

Fan Status Switch

0=No Switch

 

0: no FIOP

 

FANSTCFG

12

 

 

1=Normal Open

 

1: FIOP

 

 

 

 

 

2=Normal Closed

 

 

 

 

 

FL.SW

Filter Status Switch

0=No Switch

 

0: no FIOP

 

FILSTCFG

12

 

 

1=Normal Open

 

1: FIOP

 

 

 

 

 

2=Normal Closed

 

 

 

 

 

FS.SW

Fire Shutdown Switch

0=No Switch

 

0: no FIOP

 

SHTDNCFG

12

 

 

1=Normal Open

 

1: FIOP

 

 

 

 

 

2=Normal Closed

 

 

 

 

 

RM.SW

Remote Occupancy

0=No Switch

 

0

 

REMOCCFG

12

 

Switch

1=Normal Open

 

 

 

 

 

 

 

2=Normal Closed

 

 

 

 

 

RH.S

RH Sensor on OAQ Input

Yes/No

 

No

 

RH_OAQ

13

RH.SW

Space Humidity Switch

0=No Switch

 

0

 

HUMSTCFG

13

 

 

1=Normal Open

 

 

 

 

 

 

 

2=Normal Closed

 

 

 

 

 

TCS.C

Temp Cmp Strt Cool Factr

0 to 60

mins

0

 

TCSTCOOL

13

TCS.H

Temp Cmp Strt Heat Factr

0 to 60

mins

0

 

TCSTHEAT

13

COOL

Cooling Configuration

 

 

 

COOL_CFG

 

 

MIN.C

Min Compressor Capacity

15 to 80

%

70

 

MIN_CAPC

14

FS.CD

Fan Speed Control

1 to 9.9

^F

3

 

SPEEDDMD

17

 

Demand

 

 

 

 

 

 

MRT.C

Compressor Min On Time

120 to 999

sec

180

 

MIN_ON

 

MOT.C

Compressor Min Off Time

300 to 999

sec

300

 

MIN_OFF

 

RST.C

Runtime to Reset Strikes

120 to 999

sec

300

 

MIN_ON_S

24

FOD.C

Fan-off Delay, Mech Cool

0 to 600

sec

60

 

COOL_FOD

 

CS.A1

Current Sensing A1

Enable/Disable

 

Disable: reserved for

 

A1_SENSE

25

 

 

 

 

future use

 

 

 

 

 

 

 

DO NOT ENABLE

 

 

 

C.LO

Compressor Lockout

0 to 100F

dF

0

 

OATLCOMP

 

 

Temp

 

 

 

 

 

 

ALM.N

Alert Each Strike

Yes//No

 

Yes

 

ALM_NOW

24

SAT

Supply Air Temperature

 

 

 

 

 

 

SASP

Cool Supply Air Setpoint

45 to 75

dF

65

 

SASP

17

SA.MU

SASP Maximum Reset Up

0 to 20

^F

10

 

SASPMAXU

18

SA.MD

SASP Maximum Reset

---20 to 0

^F

---10

 

SASPMAXD

18

 

Down

 

 

 

 

 

 

SAT.U

Minimum SAT Upper Level

35.0 to 65.0

dF

60

 

SATMIN_H

 

SAT.L

Minimum SAT Lower Level

35.0 to 65.0

dF

45

 

SATMIN_L

 

SST

Low Suction Control

 

 

 

 

 

 

SST.O

Suction OK Temperature

10 to 50

dF

18

 

SSTOK

26

SST.1

Low Suction --- Level 1

10 to 50

dF

20

 

SSTLEV1

26

SST.2

Low Suction --- Level 2

5 to 50

dF

15

 

SSTLEV2

26

SST.3

Low Suction --- Level 3

0 to 50

dF

10

 

SSTLEV3

26

PSI.D

Ckt A Minimum Pressure

0 to 500

psig

20

 

DELTAP_A

26

OFC

Outdoor Fan Control

 

 

 

 

 

 

1.MXP

Fan Lev1 Max Pressure

100 to 500

psig

450

 

LEV1MAXP

15

2.MNP

Fan Lev2 Min Pressure

100 to 500

psig

200

 

LEV2MINP

15

2.ON

Fan Lev2 On Temperature

0 to 100

F

55

 

LEV2ON

15

2.OFF

Fan Lev2 Off Temperature

0 to 100

F

45

 

LEV2OFF

15

48/50PD

73

Page 73
Image 73