48/50PD
APPENDIX B - VFD INFORMATION (CONT)
Table 40 — VFD CONFIGURATIONS
APPLICATION CRITICAL DRIVE PARAMETERS FOR ABB ACH550 DRIVES
Parameter Group | Parameter | Description | Value |
| UNITS | NOTE | ||
| Number |
|
|
|
| |||
|
|
|
|
|
|
| ||
| 9901 | Language | (0) English | ABB Drive default | ||||
|
|
|
|
|
|
|
| |
| 9902 | Application Macro | (1) HVAC Default | PD Product specific | ||||
| setting | |||||||
|
|
|
|
|
|
| ||
|
|
|
|
|
| |||
| 9904 | Motor Control Mode | (3) Scalar : Freq | ABB Drive default | ||||
|
|
|
|
|
|
|
| |
| 9905 | Motor Nominal Voltage | 230 |
| 460 | Volts | PD Product specific | |
|
| setting | ||||||
|
|
|
|
|
| |||
|
|
|
|
|
|
| ||
DATA | 9906 | Motor Nominal Current | 7.0 |
| 3.5 | Amps | PD Product specific | |
|
|
|
|
|
|
| setting | |
| 9907 | Motor Nominal Frequency | 60 |
|
| Hz | ABB Drive default | |
|
|
|
|
|
|
|
| |
| 9908 | Motor Nominal Speed | 1725 |
| RPM | PD Product specific | ||
|
| setting | ||||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
| 9909 | Motor Nominal Power | 2.4 |
| HP | PD Product specific | ||
|
| setting | ||||||
|
|
|
|
|
|
| ||
|
|
|
|
|
| |||
| 1001 | EXT1 Commands | (1) DI | ABB Drive default | ||||
|
|
|
|
|
| |||
START/STOP/DIR | 1002 | EXT2 Commands | (1) DI | ABB Drive default | ||||
|
|
|
|
|
|
| ||
| 1003 | Direction | (1) Forward | PD Product specific | ||||
| setting | |||||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
ANALOG INPUTS | 1301 | Minimum Al | 20 |
|
| % | ABB Drive default | |
|
|
|
|
|
|
| ||
1302 | Maximum Al | 100 |
| % | ABB Drive default | |||
|
| |||||||
|
|
|
|
|
|
|
| |
| 1401 | Relay Output 1 | (7) Started | Carrier default settings | ||||
| from PPS | |||||||
RELAY OUTPUTS |
|
|
|
|
|
| ||
|
|
|
|
|
|
| ||
1402 | Relay Output 2 | (2) Run |
| ABB Drive default | ||||
|
| |||||||
|
|
|
|
|
| |||
| 1403 | Relay Output 3 | (3) Fault | ABB Drive default | ||||
|
|
|
|
|
| |||
SYSTEM | 1601 | Run Enable | (0) Not Set | ABB Drive default | ||||
CONTROL | 1608 | Start Enable 1 | (4) DI | ABB Drive default | ||||
|
|
|
|
|
|
|
| |
| 1701 | Override Set | (3) DI | Carrier default settings | ||||
| from PPS | |||||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
| 1702 | Override Freq | 60 |
|
| Hz | Carrier default settings | |
|
|
| from PPS | |||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
OVER RIDE | 1703 | Override Speed | 1750 |
| RPM | Carrier default settings | ||
| from PPS | |||||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
| 1704 | Over Pass Code | 0 |
|
| Carrier default settings | ||
|
|
| from PPS | |||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
| 1705 | Override | On |
| Carrier default settings | |||
|
| from PPS | ||||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
| 2003 | Maximum Current | 8.0 |
| 4.0 | Amps | PD Product specific | |
|
| setting | ||||||
LIMITS |
|
|
|
|
|
| ||
|
|
|
|
|
|
| ||
2007 | Minimum Frequency | 0 |
|
| Hz | ABB Drive default | ||
|
|
| ||||||
|
|
|
|
|
|
|
| |
| 2008 | Maximum Frequency | 60 |
|
| Hz | ABB Drive default | |
|
|
|
|
|
|
|
| |
| 2101 | Start Function | (8) Ramp | PD Product specific | ||||
| setting | |||||||
START/STOP |
|
|
|
|
|
| ||
|
|
|
|
|
|
| ||
2102 | Stop Function | (2) Ramp | PD Product specific | |||||
| ||||||||
| setting | |||||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
ACCEL/DECEL | 2202 | Accelerate Time | 30 |
|
| Seconds | ABB Drive default | |
|
|
|
|
|
|
| ||
2203 | Decelerate Time | 30 |
|
| Seconds | ABB Drive default | ||
|
|
| ||||||
|
|
|
|
|
|
|
| |
| 2601 | Flux Optimization | (1) On |
| PD Product specific | |||
|
| setting | ||||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
MOTOR | 2605 | Volt/Freq Ratio | (2) Squared | Carrier default settings | ||||
from PPS | ||||||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
| 2606 | Switching Frequency | 8 |
|
| kHz | Carrier default settings | |
|
|
| from PPS | |||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
FAULT | 3006 | Motor Thermal Time | 1050 |
| Seconds | Carrier default settings | ||
FUNCTIONS |
| from PPS | ||||||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
All Other Parameter Settings are ABB Drive Default Settings
82