Carrier 48/50PD05 manual Appendix B - Vfd Information Cont, Vfd Configurations

Models: 48/50PD05

1 106
Download 106 pages 12.23 Kb
Page 82
Image 82
APPENDIX B - VFD INFORMATION (CONT)

48/50PD

APPENDIX B - VFD INFORMATION (CONT)

Table 40 — VFD CONFIGURATIONS

APPLICATION CRITICAL DRIVE PARAMETERS FOR ABB ACH550 DRIVES

Parameter Group

Parameter

Description

Value

 

UNITS

NOTE

 

Number

 

HK30WA001---208/230V

 

HK30WA008---460V

 

 

 

 

 

 

 

 

 

 

9901

Language

(0) English

---

ABB Drive default

 

 

 

 

 

 

 

 

 

9902

Application Macro

(1) HVAC Default

---

PD Product specific

 

setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9904

Motor Control Mode

(3) Scalar : Freq

---

ABB Drive default

 

 

 

 

 

 

 

 

 

9905

Motor Nominal Voltage

230

 

460

Volts

PD Product specific

 

 

setting

START---UP

 

 

 

 

 

 

 

 

 

 

 

 

 

DATA

9906

Motor Nominal Current

7.0

 

3.5

Amps

PD Product specific

 

 

 

 

 

 

 

setting

 

9907

Motor Nominal Frequency

60

 

 

Hz

ABB Drive default

 

 

 

 

 

 

 

 

 

9908

Motor Nominal Speed

1725

 

RPM

PD Product specific

 

 

setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9909

Motor Nominal Power

2.4

 

HP

PD Product specific

 

 

setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1001

EXT1 Commands

(1) DI --- 1 Start/Stop

---

ABB Drive default

 

 

 

 

 

 

START/STOP/DIR

1002

EXT2 Commands

(1) DI --- 1 Start/Stop

---

ABB Drive default

 

 

 

 

 

 

 

 

1003

Direction

(1) Forward

---

PD Product specific

 

setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ANALOG INPUTS

1301

Minimum Al --- 1

20

 

 

%

ABB Drive default

 

 

 

 

 

 

 

1302

Maximum Al --- 1

100

 

%

ABB Drive default

 

 

 

 

 

 

 

 

 

 

 

1401

Relay Output 1

(7) Started

---

Carrier default settings

 

from PPS

RELAY OUTPUTS

 

 

 

 

 

 

 

 

 

 

 

 

 

1402

Relay Output 2

(2) Run

 

---

ABB Drive default

 

 

 

 

 

 

 

 

 

1403

Relay Output 3

(3) Fault (---1)

---

ABB Drive default

 

 

 

 

 

 

SYSTEM

1601

Run Enable

(0) Not Set

---

ABB Drive default

CONTROL

1608

Start Enable 1

(4) DI --- 4

---

ABB Drive default

 

 

 

 

 

 

 

 

 

1701

Override Set

(3) DI --- 3

---

Carrier default settings

 

from PPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1702

Override Freq

60

 

 

Hz

Carrier default settings

 

 

 

from PPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OVER RIDE

1703

Override Speed

1750

 

RPM

Carrier default settings

 

from PPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1704

Over Pass Code

0

 

 

---

Carrier default settings

 

 

 

from PPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1705

Override

On

 

---

Carrier default settings

 

 

from PPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2003

Maximum Current

8.0

 

4.0

Amps

PD Product specific

 

 

setting

LIMITS

 

 

 

 

 

 

 

 

 

 

 

 

 

2007

Minimum Frequency

0

 

 

Hz

ABB Drive default

 

 

 

 

 

 

 

 

 

 

 

 

2008

Maximum Frequency

60

 

 

Hz

ABB Drive default

 

 

 

 

 

 

 

 

 

2101

Start Function

(8) Ramp

---

PD Product specific

 

setting

START/STOP

 

 

 

 

 

 

 

 

 

 

 

 

 

2102

Stop Function

(2) Ramp

---

PD Product specific

 

 

setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ACCEL/DECEL

2202

Accelerate Time

30

 

 

Seconds

ABB Drive default

 

 

 

 

 

 

 

2203

Decelerate Time

30

 

 

Seconds

ABB Drive default

 

 

 

 

 

 

 

 

 

 

 

 

2601

Flux Optimization

(1) On

 

---

PD Product specific

 

 

setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MOTOR

2605

Volt/Freq Ratio

(2) Squared

---

Carrier default settings

from PPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2606

Switching Frequency

8

 

 

kHz

Carrier default settings

 

 

 

from PPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAULT

3006

Motor Thermal Time

1050

 

Seconds

Carrier default settings

FUNCTIONS

 

from PPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

All Other Parameter Settings are ABB Drive Default Settings