Carrier 48/50PD05 manual High Altitude, Main Burners, Filter Drier, Protective Devices

Models: 48/50PD05

1 106
Download 106 pages 12.23 Kb
Page 66
Image 66
High Altitude

48/50PD

High Altitude

For high altitude applications greater than 2,000 ft the heat input rate should be reduced. The higher the altitude is above sea level, the less oxygen is in the air. See Table 8 for orifice sizing. A high altitude kit is available to convert unit for altitudes up to 7,000 ft.

Main Burners

For all applications, main burners are factory set and should require no adjustment.

Main Burner Removal

1.Shut off (field-supplied) manual main gas valve.

2.Shut off power to unit.

3.Open gas section access door.

4.Disconnect gas piping from gas valve inlet.

5.Remove wires from gas valve.

6.Remove wires from rollout switch.

7.Remove sensor wire and ignitor cable from IGC board.

8.Remove 2 screws that hold the burner assembly to vestibule plate.

9.Rotate the burner/manifold assembly to the right, away from the flue extension and lift burner/manifold assembly out of unit.

Cleaning and Adjustment

1.Remove burner rack from unit as described in Main Burner Removal section above.

2.Inspect burners, and if dirty, remove burners from rack. The two outer burners have the flame crossover closed off in order to prevent gas flow from exiting the sides of the burner assembly. To prevent ignition problems, make sure the outer burners are returned to their original position when done servicing.

3.Using a soft brush, clean burners and crossover port as required.

4.Adjust spark gap. (See Fig. 38.)

5.Reinstall burners on rack.

6.Reinstall burner rack as described above.

A

 

E

 

E

A

B

25.4 Main Burners MAX. TYP.

B

SECTION E-E

SCALE 2:1

SPARK GAP

 

D

 

0.181”

 

SPARK GAP

[4.6]

 

 

C

 

0.120 TO 0.140”

 

 

 

 

 

[3.05 TO 3.56]

 

C

D

 

SECTION C-C

SECTION A-A

SECTION B-B

SECTION D-D

 

SCALE 1:1

SCALE 1:1

 

C06269

Fig. 38 - Spark Gap Adjustment

Filter Drier

Replace filter drier whenever refrigerant system is exposed to atmosphere. Only use factory specified liquid-line filter driers with working pressures no less than 650 psig. Do not install a suction-line filter drier in liquid line. A liquid-line filter drier designed for use with Puronrefrigerant is required on every unit.

Protective Devices

Compressor Rotation

Overcurrent

Each compressor has internal line break motor protection.

Overtemperature

Each compressor has an internal protector to protect it against excessively high discharge gas temperatures.

High-Pressure Switch

If the high-pressure switch trips, the compressor will shut down and the current sensor (3-phase units only) will not detect current. See the Current Sensor section below for more information.

Current Sensor (CS) (3-Phase Units Only)

The purpose of the CS is to detect losses in compressor power. After detecting a loss in compressor power, unit control locks out the compressor for 15 minutes. After 15 minutes, the alarm will automatically reset. If this alarm occurs 3 times consecutively, the compressor will remain locked out until an alarm reset is initiated via CCN or manually via the Scrolling Marquee display (see Alarms and Alerts section for more details).

IMPORTANT: The current sensor is not currently used in the 48/50PD, but reserved for future implementation.

66

Page 66
Image 66
Carrier 48/50PD05 High Altitude, Main Burners, Filter Drier, Protective Devices, Main Burner Removal, Compressor Rotation