48/50PD
High Altitude
For high altitude applications greater than 2,000 ft the heat input rate should be reduced. The higher the altitude is above sea level, the less oxygen is in the air. See Table 8 for orifice sizing. A high altitude kit is available to convert unit for altitudes up to 7,000 ft.
Main Burners
For all applications, main burners are factory set and should require no adjustment.
Main Burner Removal
1.Shut off
2.Shut off power to unit.
3.Open gas section access door.
4.Disconnect gas piping from gas valve inlet.
5.Remove wires from gas valve.
6.Remove wires from rollout switch.
7.Remove sensor wire and ignitor cable from IGC board.
8.Remove 2 screws that hold the burner assembly to vestibule plate.
9.Rotate the burner/manifold assembly to the right, away from the flue extension and lift burner/manifold assembly out of unit.
Cleaning and Adjustment
1.Remove burner rack from unit as described in Main Burner Removal section above.
2.Inspect burners, and if dirty, remove burners from rack. The two outer burners have the flame crossover closed off in order to prevent gas flow from exiting the sides of the burner assembly. To prevent ignition problems, make sure the outer burners are returned to their original position when done servicing.
3.Using a soft brush, clean burners and crossover port as required.
4.Adjust spark gap. (See Fig. 38.)
5.Reinstall burners on rack.
6.Reinstall burner rack as described above.
A
| E |
| E |
A | B |
25.4 MAX. TYP.
B
SECTION
SCALE 2:1
SPARK GAP |
| D |
|
0.181” |
| SPARK GAP | |
[4.6] |
|
| |
C |
| 0.120 TO 0.140” | |
|
| ||
|
|
| [3.05 TO 3.56] |
| C | D |
|
SECTION | SECTION | SECTION | SECTION |
| SCALE 1:1 | SCALE 1:1 |
|
C06269
Fig. 38 - Spark Gap Adjustment
Filter Drier
Replace filter drier whenever refrigerant system is exposed to atmosphere. Only use factory specified
Protective Devices
Compressor Rotation
Overcurrent
Each compressor has internal line break motor protection.
Overtemperature
Each compressor has an internal protector to protect it against excessively high discharge gas temperatures.
If the
Current Sensor (CS)
The purpose of the CS is to detect losses in compressor power. After detecting a loss in compressor power, unit control locks out the compressor for 15 minutes. After 15 minutes, the alarm will automatically reset. If this alarm occurs 3 times consecutively, the compressor will remain locked out until an alarm reset is initiated via CCN or manually via the Scrolling Marquee display (see Alarms and Alerts section for more details).
IMPORTANT: The current sensor is not currently used in the 48/50PD, but reserved for future implementation.
66