APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)
Table 37 — MODE - OPERATING MODES (cont)
ITEM | EXPANSION | RANGE | UNITS | CCN | CCN POINT | CCN | DISPLAY | |
WRITE | WRITE | |||||||
|
|
|
|
| STATUS | STATUS | ||
|
|
|
|
|
| |||
HEAT | Heat Mode Diagnostic |
|
| HEATDIAG |
|
|
| |
HEAT | In Heating Mode? | Yes/No |
|
| IN_HEAT |
|
| |
OK.HT | OK to Select Heat Mode? | Yes/No |
|
| OKTOHEAT |
|
| |
MS.TG | Mode Select Timeguard | xxx | secs |
| HEATMSTG |
|
| |
H.LOC | Heat OAT Lockout | Yes/No |
|
| HEATLOCK |
|
| |
HT.LO | Heating Lockout Temp | xxx | dF |
| OATLHEAT |
|
| |
IDF | Indoor Fan State | On/Off |
|
| IDFSTATE |
|
| |
F.SPD | Commanded Fan Speed | xxx |
|
| FANSPEED |
|
| |
AVL.H | Available Heating Stages | x |
|
| AVLHSTGS |
|
| |
REQ.H | Requested Heating Stages | x |
|
| REQHSTGS |
|
| |
LMT.H | Max Heat Stage In Effect | x |
|
| HSTGLIMT |
|
| |
ACT.H | Actual Heating Stages | x |
|
| ACTHSTGS |
|
| |
HT.1 | Heat Stage 1 Relay | On/Off |
|
| HEAT_1 |
|
| |
HT.2 | Heat Stage 2 Relay | On/Off |
|
| HEAT_2 |
|
| |
SAT | Supply Air Temperature |
|
|
|
|
|
| |
SAT.H | SAT Heat Mode Sensing | Enable/Disable |
|
| SAT_HEAT |
|
| |
SAT | Supply Air Temperature | xxx.x | dF |
| SAT_DISP |
|
| |
SAM.L | Maximum SAT Lower Level | xxx | dF |
| SATMAX_L |
|
| |
SAM.U | Maximum SAT Upper Level | xxx | dF |
| SATMAX_H |
|
| |
SPT | Space Temperature |
|
|
|
|
|
| |
SPT | Space Temperature | xxx.x | dF |
| SPACE_T | forcible |
| |
DMD.H | Heating Demand | xxx.x | dF |
| HEAT_DMD |
|
| |
TRND | Spacetemp Trend (F/min) | xxx.x |
|
| SPTTREND |
|
| |
HT.PD | SPT Heat Demand (+) | xx.x | ^F |
| HDEM_POS |
|
| |
| Level |
|
|
|
|
|
| |
HT.ND | SPT Heat Demand | xx.x | ^F |
| HDEM_NEG |
|
| |
| Level |
|
|
|
|
|
| |
H.LAG | Heat Thermal Lag Factor | x.x | min |
| HEAT_LAG |
|
| |
ECON | Economizer Diagnostic |
|
| ECONDIAG |
|
|
| |
EC.EN | Economizer Installed | Yes/No |
|
| ECONO |
|
| |
OCC | Currently Occupied | Yes/No |
|
| OCCUPIED | forcible | forcible | |
IDF | Indoor Fan State | On/Off |
|
| IDFSTATE |
|
| |
F.SPD | Commanded Fan Speed | NNN |
|
| FANSPEED |
|
| |
COOL | In Cooling Mode? | Yes/No |
|
| IN_COOL |
|
| |
E.LOC | Econo Cool OAT Lockout | Yes/No |
|
| ECONLOCK |
|
| |
EH.LO | Econo Cool Hi Temp Limit | xxx | dF |
| OATLECLH |
|
| |
EL.LO | Econo Cool Lo Temp Limit | xx | dF |
| OATLECLL |
|
| |
FC.LO | Free Cool Low Temp Limit | xx | dF |
| OATLUEFC |
|
| |
EN.LO | Econo Cool Enth Lockout | Yes/No |
|
| ENTHLOCK |
|
| |
EC.MX | Econo Cool Max Position | xxx | % |
| ECONOMAX |
|
| |
AQ.DV | IAQ DCV Mode | Yes/No |
|
| IN_IAQDV |
|
| |
AQ.MN | Econo Min IAQ Position | xxx | % |
| IAQMINP |
|
| |
AQ.OV | IAQ Override Mode | Yes/No |
|
| IN_IAQOV |
|
| |
OVR.P | IAQ Override Position | xxx | % |
| IAQOVPOS |
|
| |
AQ.LO | OAQ Lockout Mode | Yes/No |
|
| IN_OAQLO |
|
| |
OAQ.L | OAQ Lockout Limit | xxxx |
|
| OAQLOCK |
|
| |
LP.OV | Lo Refrig Press Override | Yes/No |
|
| IN_LPOV |
|
| |
EC.CP | Econo Commanded | xxx | % |
| ECONOCMD | forcible |
| |
| Position |
|
|
|
|
|
| |
EC.AP | Econo Actual Position | xxx | % |
| ECONOPOS |
|
| |
EC.MP | Min Position in Effect | xxx | % |
| MIN_POS | forcible |
| |
C.ANG | Actuator Control Angle |
|
|
| CTLANGLE |
|
| |
E.CAL | Economizer Calibrating | Yes/No |
|
| ECOINCAL |
|
| |
DMD.L | Demand Limiting |
|
| DMDL |
|
|
| |
D.LMT | Demand Limit In Effect | Yes/No |
|
| MODEDMDL |
|
| |
LMT.C | Max Capacity In Effect | xxx |
|
| CAPLIMIT |
|
| |
LMT.H | Max Heat Stage In Effect | x |
|
| HSTGLIMT |
|
| |
REDL | Redline Activated | Yes/No |
|
| MODEREDL |
|
| |
SHED | Loadshed Activated | Yes/No |
|
| MODESHED |
|
| |
MAX.C | Max Compressor Capacity | x |
|
| MAX_CAPC |
| forcible | |
MAX.H | Max Allowed Heat Stages | x |
|
| MAXHSTGS |
| forcible | |
(Display TRIM | Sensor Calibration |
|
| TRIM |
|
|
| |
Configuration) |
|
|
|
|
|
|
| |
| Space Temp Calibration | dF |
| SPT_CAL | forcible |
| ||
| Space Temp Trim | ^F |
| SPT_OFF | forcible |
| ||
| Supply Air Temp Calib. | dF |
| SAT_CAL | forcible |
| ||
| Supply Air Temp Trim | ^F |
| SAT_OFF | forcible |
| ||
| Return Air Temp Calib. | dF |
| RAT_CAL | forcible |
| ||
| Return Air Temp Trim | ^F |
| RAT_OFF | forcible |
|
48/50PD