Outdoor Fan Operation
The 48/50 PD units use a
When the outdoor fan contactor is energized the outdoor fan runs at low speed.
The outdoor fan speed is controlled by a system three of fan levels set up in the control software. Table 6 shows the three levels and fan speeds for each level. The fan levels are determined by Outdoor Air Temperature (Temperatures→AIR.T→OAT) but can be overridden by Condenser Pressure A (Pressures→SCP.A) inputs to the Main Base Board.
FAN | FAN | CONDITIONS TO TRANSITION TO NEXT | CONDITIONS TO TRANSITION TO NEXT |
LEVEL | SPEED | LOWER LEVEL | HIGHER LEVEL |
|
|
|
|
|
|
| 1. Compressor Contactor is ON |
|
|
| (on initial start up outdoor fan runs at Level 2 for |
0 | OFF | N/A | 10 seconds before moving to correct level based |
on outside air temperature or Condenser Pres- | |||
|
|
| sure A) |
|
|
|
|
|
|
| 1. Outside Air Temperature Control — Fan |
|
|
| Lev2 On Temperature 55 F or above (Configu- |
1 | LOW | 1. Compressor Contactor is OFF | ration→COOL→OFC→2.ON >=55F)* |
2. Condenser Pressure A Override — Fan | |||
|
|
| Lev1 Max Pressure 450 psig or above (Config- |
|
|
| uration→COOL→OFC→1.MXP>= 450 psig)* |
|
|
|
|
|
| 1. Outside Air Temperature Control |
|
|
| Lev2 Off Temperature 45 F or below (Confi- |
|
2 | HIGH | guration→COOL→OFC→2.OFF <=45F)* | N/A |
2. Condenser Pressure A Override | |||
|
| Lev2 Min Pressure 200 psig or below (Config- |
|
|
| uration→COOL→OFC→2.MNP<= 200 psig)* |
|
|
|
|
|
Table 6 — Fan Level Control of Outdoor Fan
*Configuration parameters 1.MXP, 2.MNP, 2.ON and 2.OFF factory default configuration should not be changed. The default configurations have been qualified over a wide range of conditions and are provided in case a field replacement of the control board occurs and the settings need to be checked or manually configured.\
48/50PD
Economizer Operation
If an economizer is installed, then Economizer Installed (Configuration→UNIT→EC.EN) should be set to YES. The economizer is controlled by the Econo Commanded Position (Outputs→ECON→EC.CP) on the Economizer Control Board (ECB). Feed back from the economizer actuator is output on
configuration parameter Econo Actual Position (Outputs→ECON→EC.AP).
Economizer Actuator Communication
The economizer actuator used with the 48/50PD units is a
The power to the unit must be cycled after the Economizer Control Type (Configuration →ECON→E.CTL) configuration parameter is changed.
E.CTL = 1 or 2 (Digital/Position or Digital/Command)
When Economizer Control Type (Configuration→ECON→E.CTL) is set to 1, the Economizer Control Board will communicate with the economizer actuator using the digital protocol, from Economizer Control Board plug
commanded position when E.CTL = 2. Because the wiring has a
E.CTL = 3 (Analog Control)
When E.CTL is set to 3, the Economizer Control Board will NOT communicate with the economizer actuator directly with the 4 to 20mA analog signal wired to
Free Cooling
The economizer will be allowed to help with cooling if the Outdoor Air Temperature (Temperatures→AIR.T→OAT) is less than the configured Econo Cool Hi Temp Limit (Configuration→ECON→EH.LO) and greater than the
configured Econo Cool Lo Temp Limit (Configuration→ECON→EL.LO). If an enthalpy sensor is installed, the outdoor temperature must be below the Econo Cool Hi Temp Limit (Configuration→ECON→EH.LO) and the Outdoor Enthalpy Switch (Inputs→GEN.I→ENTH) must be LOW.
Unoccupied Free Cooling
The unoccupied free cooling algorithm attempts to maintain the building space half way between the Occupied Cool Set Point (Setpoints→OCSP) and Occupied Heat Set Point (Setpoints→OHSP) using only the economizer when the conditions in the building and the outdoors are suitable., during UNoccupied periods if the air in the building and the outdoor air are suitable. Three different configurations define this algorithm:
1. Unoccupied | Free | Cooling |
(Configuration→ECON→UEFC) |
|
15