48/50PD
measured a temperature above 268 F (131 C) or the thermistor has short circuited (jumpered out).
The DSC will
Flash Code 3 ⎯ Compressor Protector Trip
This occurs when the demand signal from the system controller is greater than 1.44VDC and there is no compressor current detected. This could be due to the compressor’s internal overload protector being open, fuse or breaker open, power disconnected to compressor contactor, compressor power wiring not run through DSC current transformer port or a compressor contactor failure. The DSC will
Flash Code 4 ⎯ Locked Rotor
A locked rotor condition in the compressor is sensed by the DSC on four consecutive start ups. The DSC will
Flash Code 5 ⎯ Demand Signal Loss
This occurs when the demand signal input has dropped below 0.5VDC. The demand input signal wire may be disconnected or
the system controller providing the signal may not be powered. The DSC will
Flash Code 6 ⎯ Discharge Thermistor Fault
This occurs when the DSC is not receiving a signal from the discharge temperature thermistor (DTT). The thermistor may be missing, disconnected or a wire broken. The alarm relay contacts will close and the DSC will not increase the capacity of the compressor beyond 50% loading. This ALERT code and alarm relay output are reset by reconnecting the DTT.
Flash Code 7 ⎯Reserved for future use
Flash Code 8 ⎯ Compressor Contactor Fault
This occurs when the compressor current is detected when the system controller demand signal is below 1.44VDC. The compressor contactor may have welded contacts or the contacts may be mechanically jammed. The compressor will continue to run in this condition since the DSC cannot open the compressor contactor. The DSC will energize the compressor contactor and the alarm relay contacts will close causing a T051 alert on the ComfortLink Control. The unloader solenoid will remain energized causing the compressor to run unloaded as long as the system controller demand signal is less than 1.44VDC. If the system controller demand is greater than 1.44VDC, the unloader solenoid will
Flash Code 9 ⎯ Low 24VAC Supply
This occurs when the supply voltage to the DSC has dropped below 18.5VDC. The DSC will
Table 10 — DSC Red LED Flash Codes
LED Flash | Description | Action Taken | Reset | Probable Cause |
Code |
| by Control | Method |
|
|
|
|
|
|
1 | Reserved for Future Use | N/A | N/A | N/A |
Flash |
|
|
|
|
|
|
|
|
|
2 | High Discharge Temperature | Compressor | Automatic | Compressor discharge temperature is greater then 268 |
Flash |
| shutdown |
| degrees F or the DTT is shorted. |
|
|
|
|
|
3 | Compressor Protector Trip | Compressor | Automatic | Compressor’s internal overload protector being open, |
Flash |
| shutdown |
| fuse or breaker open, power disconnected to compres- |
|
|
|
| sor contactor, compressor power wiring not run through |
|
|
|
| DSC current transformer port or a compressor contactor |
|
|
|
| failure. |
|
|
|
|
|
4 | Locked Rotor | Compressor | Manual | Four consecutive start ups with locked rotor. |
Flash |
| lockout |
|
|
|
|
|
|
|
5 | Demand Signal Loss | Compressor | Automatic | Signal wire may be disconnected or the system control- |
Flash |
| shutdown |
| ler providing the signal may not be powered |
|
|
|
|
|
6 | Discharge Thermistor Fault | Capacity Limited | Automatic | DTT may be missing, disconnected or a wire broken |
Flash |
|
|
|
|
|
|
|
|
|
7 | Reserved for Future Use | N/A | N/A | N/A |
Flash |
|
|
|
|
|
|
|
|
|
8 | Compressor Contactor Fault | Keep capacity | Automatic | Compressor contactor may have welded contacts or the |
Flash |
| at 15% |
| contacts may be mechanically jammed |
|
|
|
|
|
9 | Low 24VAC Supply | Compressor | Automatic | Bad connection or transformer. |
Flash |
| shutdown |
|
|
|
|
|
|
|
32