Fan Status

Fan Status

If a Fan Status accessory was field installed, the unit must be configured for it by setting ConfigurationUNITFN.SW to normally open (1) or normally closed (2). Normally open (1) is the preferred configuration.

IMPORTANT: Fan Status input is not on the terminals marked Fan Status.

Filter Status

If a Filter Status accessory was field installed, the unit must be configured for it by setting ConfigurationUNITFL.SW to normally open (1) or normally closed (2). Normally open (1) is the preferred configuration.

Table 4 — Setting an Occupied Time Schedule - Weekdays Only for 7:30 to 22:30

DISPLAY

SUB￿ ￿SUB

KEYPAD

ITEM

DISPLAY

ITEM EXPANSION

COMMENT

MENU

MODE

ENTRY

 

 

 

 

TIMECLOCK

 

ENTER

 

 

Local Occupancy Schedule

 

SCH.L

PER.1

ENTER

OCC.1

 

Period Occupied Time

 

 

 

 

 

 

ENTER

 

00.00

 

Scrolling stops

 

 

ENTER

 

00.00

 

Hours Flash

 

 

Y

 

07.00

 

Select 7

 

 

ENTER

 

07.00

 

Change accepted, minutes flash

 

 

Y

 

07.30

 

Select 30

 

 

ENTER

 

07.30

 

Change accepted

 

 

ESCAPE

OCC.1

07.30

Period Occupied Time

Item/Value/Units scrolls again

 

 

B

UNC.1

00.00

Period Unoccupied Time

 

 

 

ENTER

 

00.00

 

Scrolling stops

 

 

ENTER

 

00.00

 

Hours Flash

 

 

Y

 

22.00

 

Select 22

 

 

ENTER

 

22.00

 

Change accepted, minutes flash

 

 

Y

 

22.30

 

Select 30

 

 

ENTER

 

22.30

 

Change accepted

 

 

ESCAPE

UNC.1

22.30

Period Unoccupied Time

Item/Value/Units scrolls again

 

 

B

MON.1

NO

Monday In Period

 

 

 

ENTER

 

NO

 

Scrolling stops

 

 

Y

 

YES

 

Select YES

 

 

ENTER

 

YES

 

Change accepted

 

 

ESCAPE

MON.1

YES

Monday In Period

Item/Value/Units scrolls again

 

 

B

TUE.1

NO

Tuesday In Period

 

 

 

ENTER

 

NO

 

Scrolling stops

 

 

Y

 

YES

 

Select YES

 

 

ENTER

 

YES

 

Change accepted

 

 

ESCAPE

TUE.1

YES

Tuesday In Period

Item/Value/Units scrolls again

 

 

B

WED.1

NO

Wednesday In Period

 

 

 

ENTER

 

NO

 

Scrolling stops

 

 

Y

 

YES

 

Select YES

 

 

ENTER

 

YES

 

Change accepted

 

 

ESCAPE

WED.1

YES

Wednesday In Period

Item/Value/Units scrolls again

 

 

B

THU.1

NO

Thursday In Period

 

 

 

ENTER

 

NO

 

Scrolling stops

 

 

Y

 

YES

 

Select YES

 

 

ENTER

 

YES

 

Change accepted

 

 

ESCAPE

THU.1

YES

Thursday In Period

Item/Value/Units scrolls again

 

 

B

FRI.1

NO

Friday In Period

 

 

 

ENTER

 

NO

 

Scrolling stops

 

 

Y

 

YES

 

Select YES

 

 

ENTER

 

YES

 

Change accepted

 

 

ESCAPE

FRI.1

YES

Friday In Period

Item/Value/Units scrolls again

 

 

ESCAPE

 

 

 

 

 

 

ESCAPE

 

 

 

 

48/50PD

9

Page 9
Image 9