48/50PD

Table 50 — Fan Performance - 48PDD05 Horizontal Units

AIRFLOW

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

(Cfm)

0.2

 

 

0.4

0.6

 

 

0.8

 

1.0

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1200

436

 

0.12

559

 

0.19

661

 

0.27

753

 

0.35

839

 

0.45

1300

456

 

0.14

574

 

0.22

673

 

0.30

762

 

0.39

845

 

0.49

1400

477

 

0.17

592

 

0.25

687

 

0.34

774

 

0.43

853

 

0.53

1500

500

 

0.20

611

 

0.29

703

 

0.38

787

 

0.48

864

 

0.58

1600

523

 

0.24

631

 

0.33

721

 

0.43

801

 

0.53

877

 

0.63

1700

548

 

0.28

652

 

0.38

739

 

0.48

818

 

0.58

891

 

0.69

1800

573

 

0.32

674

 

0.43

759

 

0.54

835

 

0.64

906

 

0.76

1900

600

 

0.37

697

 

0.48

779

 

0.60

854

 

0.71

923

 

0.83

2000

627

 

0.43

720

 

0.55

801

 

0.67

873

 

0.79

941

 

0.91

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

(Cfm)

1.2

 

 

1.4

1.6

 

 

1.8

 

2.0

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1200

918

 

0.54

993

 

0.64

1063

 

0.75

1130

 

0.86

1193

 

0.97

1300

922

 

0.58

995

 

0.69

1064

 

0.80

1130

 

0.91

1193

 

1.03

1400

929

 

0.63

1000

 

0.74

1067

 

0.85

1132

 

0.97

1194

 

1.09

1500

937

 

0.69

1006

 

0.80

1072

 

0.91

1136

 

1.03

1196

 

1.16

1600

947

 

0.74

1015

 

0.86

1079

 

0.98

1141

 

1.10

1201

 

1.23

1700

959

 

0.81

1025

 

0.93

1088

 

1.05

1148

 

1.18

1207

 

1.31

1800

973

 

0.88

1037

 

1.00

1098

 

1.13

1157

 

1.26

1214

 

1.39

1900

988

 

0.95

1050

 

1.08

1110

 

1.21

1168

 

1.35

1223

 

1.48

2000

1004

 

1.04

1065

 

1.17

1123

 

1.30

1179

 

1.44

1234

 

1.58

LEGEND

 

 

 

 

 

 

NOTES:

 

 

 

 

 

 

 

Bhp --Brake Horsepower

 

 

 

 

 

 

1. Maximum continuous BHP is 2.0.

 

 

 

 

 

__ High--Range Motor/Drive Required

 

 

 

 

2. See General Fan Performance Notes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 51 — Fan Performance - 48PDE05 Horizontal Units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

(Cfm)

0.2

 

 

0.4

0.6

 

 

0.8

 

1.0

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

 

 

 

 

 

 

1200

443

 

0.12

564

 

0.20

666

 

0.27

758

 

0.36

842

 

0.45

1300

463

 

0.15

580

 

0.22

678

 

0.31

767

 

0.40

849

 

0.49

1400

485

 

0.17

598

 

0.26

693

 

0.34

778

 

0.44

858

 

0.54

1500

508

 

0.21

617

 

0.30

709

 

0.39

792

 

0.48

869

 

0.59

1600

532

 

0.24

638

 

0.34

727

 

0.43

807

 

0.54

882

 

0.64

1700

558

 

0.28

660

 

0.39

746

 

0.49

824

 

0.59

896

 

0.70

1800

584

 

0.33

682

 

0.44

766

 

0.55

842

 

0.66

912

 

0.77

1900

611

 

0.38

706

 

0.50

788

 

0.61

861

 

0.72

930

 

0.84

2000

639

 

0.44

731

 

0.56

810

 

0.68

882

 

0.80

948

 

0.92

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

(Cfm)

1.2

 

 

1.4

1.6

 

 

1.8

 

2.0

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

 

 

 

 

 

 

1200

922

 

0.55

996

 

0.65

1066

 

0.75

1133

 

0.86

1196

 

0.97

1300

926

 

0.59

999

 

0.69

1068

 

0.80

1133

 

0.92

1196

 

1.03

1400

933

 

0.64

1004

 

0.75

1071

 

0.86

1136

 

0.98

1197

 

1.10

1500

942

 

0.69

1011

 

0.80

1077

 

0.92

1140

 

1.04

1200

 

1.17

1600

952

 

0.75

1020

 

0.87

1084

 

0.99

1146

 

1.11

1205

 

1.24

1700

965

 

0.82

1030

 

0.94

1093

 

1.06

1153

 

1.19

1211

 

1.32

1800

979

 

0.89

1043

 

1.01

1104

 

1.14

1163

 

1.27

1220

 

1.41

1900

995

 

0.97

1057

 

1.09

1116

 

1.22

1174

 

1.36

1229

 

1.50

2000

1012

 

1.05

1072

 

1.18

1130

 

1.32

1186

 

1.46

1240

 

1.60

LEGEND

 

 

 

 

 

 

NOTES:

 

 

 

 

 

 

 

Bhp --Brake Horsepower

 

 

 

 

 

 

1. Maximum continuous BHP is 2.0.

 

 

 

 

 

__ High--Range Motor/Drive Required

 

 

 

 

2. See General Fan Performance Notes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

94

Page 94
Image 94
Carrier 48/50PD05 manual Fan Performance 48PDD05 Horizontal Units, Fan Performance 48PDE05 Horizontal Units, Bhp Rpm

48/50PD05 specifications

The Carrier 48/50PD05 is a remarkable addition to Carrier's lineup of rooftop units, offering advanced cooling and heating solutions for commercial applications. Designed for medium-sized buildings, this unit is well-suited for both new installations and as a replacement for older systems, thanks to its versatile features and efficient performance.

One of the standout features of the 48/50PD05 is its energy efficiency. It incorporates state-of-the-art technology to achieve high Seasonal Energy Efficiency Ratios (SEER) and EER ratings, reducing operational costs while delivering superior comfort. The unit is also compliant with the latest energy regulations, making it an environmentally friendly choice for building owners concerned about sustainability.

The 48/50PD05 is equipped with a highly efficient scroll compressor, which not only enhances performance but also contributes to quiet operation. This is a significant advantage in commercial spaces where noise levels need to be kept in check for comfort and productivity. Additionally, the unit includes advanced airflow design, ensuring even distribution of conditioned air throughout the space.

Technologically, the Carrier 48/50PD05 features Carrier's Infinity Control system, which allows for precise control of indoor climate. This intelligent control mechanism can be integrated with smart building management systems, enabling users to monitor and manage energy use effectively. Wi-Fi connectivity is also available, providing remote access for real-time adjustments and diagnostics.

Durability is another characteristic of the 48/50PD05. Constructed with high-quality materials, the unit withstands various environmental conditions, ensuring longevity and reliability. Moreover, the modular design facilitates easy maintenance, making service procedures efficient and cost-effective.

In addition to cooling, the Carrier 48/50PD05 offers heating capabilities, often utilizing gas or electric heating options that can be tailored to the specific needs of a building. The unit can also be equipped with integrated economizers, allowing for free cooling during suitable outdoor conditions, further enhancing energy savings.

Overall, the Carrier 48/50PD05 stands out as a high-performance HVAC solution that combines efficiency, technology, and durability. It provides building owners with a versatile tool to ensure comfort while minimizing their environmental footprint. With a strong emphasis on energy savings and advanced control features, this rooftop unit is a smart investment for any commercial property.