48/50PD
Table 18 — Pressure (psig) vs. Voltage Drop Values for Suction Pressure Transducers
PRESSURE | VOLTAGE |
| PRESSURE | VOLTAGE |
| PRESSURE | VOLTAGE |
| PRESSURE | VOLTAGE |
(psig) | DROP (V) |
| (psig) | DROP (V) |
| (psig) | DROP (V) |
| (psig) | DROP (V) |
0 | 0.465 |
| 68 | 1.135 |
| 136 | 1.804 |
| 204 | 2.474 |
2 | 0.485 |
| 70 | 1.154 |
| 138 | 1.824 |
| 206 | 2.493 |
4 | 0.505 |
| 72 | 1.174 |
| 140 | 1.844 |
| 208 | 2.513 |
6 | 0.524 |
| 74 | 1.194 |
| 142 | 1.863 |
| 210 | 2.533 |
8 | 0.544 |
| 76 | 1.214 |
| 144 | 1.883 |
| 212 | 2.553 |
10 | 0.564 |
| 78 | 1.233 |
| 146 | 1.903 |
| 214 | 2.572 |
12 | 0.583 |
| 80 | 1.253 |
| 148 | 1.922 |
| 216 | 2.592 |
14 | 0.603 |
| 82 | 1.273 |
| 150 | 1.942 |
| 218 | 2.612 |
16 | 0.623 |
| 84 | 1.292 |
| 152 | 1.962 |
| 220 | 2.631 |
18 | 0.642 |
| 86 | 1.312 |
| 154 | 1.982 |
| 222 | 2.651 |
20 | 0.662 |
| 88 | 1.332 |
| 156 | 2.001 |
| 224 | 2.671 |
22 | 0.682 |
| 90 | 1.351 |
| 158 | 2.021 |
| 226 | 2.690 |
24 | 0.702 |
| 92 | 1.371 |
| 160 | 2.041 |
| 228 | 2.710 |
26 | 0.721 |
| 94 | 1.391 |
| 162 | 2.060 |
| 230 | 2.730 |
28 | 0.741 |
| 96 | 1.410 |
| 164 | 2.080 |
| 232 | 2.749 |
30 | 0.761 |
| 98 | 1.430 |
| 166 | 2.100 |
| 234 | 2.769 |
32 | 0.780 |
| 100 | 1.450 |
| 168 | 2.119 |
| 236 | 2.789 |
34 | 0.800 |
| 102 | 1.470 |
| 170 | 2.139 |
| 238 | 2.809 |
36 | 0.820 |
| 104 | 1.489 |
| 172 | 2.159 |
| 240 | 2.828 |
38 | 0.839 |
| 106 | 1.509 |
| 174 | 2.178 |
| 242 | 2.848 |
40 | 0.859 |
| 108 | 1.529 |
| 176 | 2.198 |
| 244 | 2.868 |
42 | 0.879 |
| 110 | 1.548 |
| 178 | 2.218 |
| 246 | 2.887 |
44 | 0.898 |
| 112 | 1.568 |
| 180 | 2.237 |
| 248 | 2.907 |
46 | 0.918 |
| 114 | 1.588 |
| 182 | 2.257 |
| 250 | 2.927 |
48 | 0.938 |
| 116 | 1.607 |
| 184 | 2.277 |
| 252 | 2.946 |
50 | 0.958 |
| 118 | 1.627 |
| 186 | 2.297 |
| 254 | 2.966 |
52 | 0.977 |
| 120 | 1.647 |
| 188 | 2.316 |
| 256 | 2.986 |
54 | 0.997 |
| 122 | 1.666 |
| 190 | 2.336 |
| 258 | 3.005 |
56 | 1.017 |
| 124 | 1.686 |
| 192 | 2.356 |
| 260 | 3.025 |
58 | 1.036 |
| 126 | 1.706 |
| 194 | 2.375 |
| 262 | 3.045 |
60 | 1.056 |
| 128 | 1.726 |
| 196 | 2.395 |
| 264 | 3.065 |
62 | 1.076 |
| 130 | 1.745 |
| 198 | 2.415 |
| 266 | 3.084 |
64 | 1.095 |
| 132 | 1.765 |
| 200 | 2.434 |
| 268 | 3.104 |
66 | 1.115 |
| 134 | 1.785 |
| 202 | 2.454 |
| 270 | 3.124 |
MAJOR SYSTEM COMPONENTS
General
The 48/50PD single package rooftop units contain the ComfortLink™ electronic control system that monitors all operations of the rooftop. The control system is composed of several main control components and available
options or | sections below. |
See Fig. | schematics for |
48/50PD. Fig. 15 shows the layout of the control box, unit, and thermistor and transducer locations for the 48/50PD.