Carrier 48/50PD05 manual Appendix A - Local Display And Ccn Tables Cont, Mode - Time Clock

Models: 48/50PD05

1 106
Download 106 pages 12.23 Kb
Page 77
Image 77
Table 35 — MODE - TIME CLOCK

APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)

Table 35 — MODE - TIME CLOCK

ITEM

EXPANSION

RANGE

UNITS

DEFAULT

CCN

CCN POINT

TABLE/SUB---TABLE

 

 

 

 

 

 

TIME CLOCK

 

 

 

 

CONFIGURATION

 

TIME

Time of Day

 

 

 

TIME

 

TIME

Hour and Minute

xx.xx

hh.mm

 

 

TIME

DATE

Current Date

 

 

 

 

 

MNTH

Month of Year

January, February, ￿ &,

 

 

 

MOY

 

 

December

 

 

 

 

DOM

Day of Month

1 to 31

 

 

 

DOM

YEAR

Year

xxxx

 

 

 

YOCDISP

DAY

Day of Week

Monday, Tuesday, ￿ &,

 

 

 

DOWDISP

 

 

Sunday

 

 

 

 

DST

Daylight Savings Config.

 

 

 

BRODEFS

 

 

 

 

 

 

(continued)

 

STR.M

Start Month

January, February, ￿ &,

 

3

 

STARTM

 

 

December

 

 

 

 

STR.W

Start Week

1 to 5

 

2

 

STARTW

STR.D

Start Day

1 to 7

 

7

 

STARTD

M.ADD

Minutes to Add

0 to 90

 

60

 

MINADD

STP.M

Stop Month

January, February, ￿ &,

 

11

 

STOPM

 

 

December

 

 

 

 

STP.W

Stop Week

1 to 5

 

1

 

STOPW

STP.D

Stop Day

1 to 7

 

7

 

STOPD

M.SUB

Minutes to Subtract

0 to 90

 

60

 

MINSUB

SCH.L

Occupancy Schedule

 

 

 

(SCH.L = Display only)

 

PER.x

Occupancy Period x

 

 

 

 

 

OCC.x

Occupied From

00.00 to 23.59

hh.mm

00.00

 

PERxOCC

UNC.x

Occupied To

00.00 to 23.60

hh.mm

00.00

 

PERxUNC

MON.x

Monday in Period

Yes/No

 

No

 

PERxMON

TUE.x

Tuesday in Period

Yes/No

 

No

 

PERxTUE

WED.x

Wednesday in Period

Yes/No

 

No

 

PERxWED

THU.x

Thursday in Period

Yes/No

 

No

 

PERxTHU

FRI.x

Friday in Period

Yes/No

 

No

 

PERxFRI

SAT.x

Saturday in Period

Yes/No

 

No

 

PERxSAT

SUN.x

Sunday in Period

Yes/No

 

No

 

PERxSUN

HOL.x

Holiday in Period

Yes/No

 

No

 

PERxHOL

(repeat up to x=8

 

 

 

 

 

 

Periods)

 

 

 

 

 

 

(OCCFECS = CCN only)

 

 

 

 

OCCDEFCS

 

 

Timed Override Hours

x

hours

 

 

OVR---EXT

 

Period x DOW

xxxxxxxx

 

00000000

 

DOWx

 

(MTWTFSSH)

 

 

 

 

 

 

Occupied From

00.00 to 24.00

hh.mm

00.00

 

OCCTODx

 

Occupied To

00.00 to 24.00

hh.mm

00.00

 

UNOCTODx

 

 

 

 

 

 

(repeat up to

 

 

 

 

 

 

x=8 Periods)

HOL.L

Holiday Schedule

 

 

 

HOLIDAY

 

HOL.x

Holiday x

 

 

0

HOLDYxxS

 

MON.x

Holiday Start Month

1 to 12 = January to

 

0

 

HOLMONxx

 

 

December

 

 

 

 

DAY.x

Holiday Start Day

1 to 31

 

0

 

HOLDAYxx

LEN.x

Holiday Duration (days)

1 to 99

 

0

 

HOLLENxx

(repeat up to x=9

 

 

 

 

 

(repeat up to

Holidays)

 

 

 

 

 

xx=30

 

 

 

 

 

 

Holidays)

Table 36 — CCN ONLY TABLES

ITEM

EXPANSION

RANGE

UNITS

DEFAULT

CCN

CCN POINT

TABLE/SUB---TABLE

(ALARMDEF = CCN only)

 

 

 

 

ALARMDEF

 

 

Alarm Routing Control

00000000 to 11111111

 

11000000

 

ALRM_CNT

 

Equipment Priority

0 to 7

 

4

 

EQP_TYPE

 

Comm Failure Retry Time

1 to 240

min

10

 

RETRY_TM

 

Re---Alarm Time

1 to 255

min

180

 

RE---ALARM

 

Alarm System Name

up to 8 alphanum

 

48_50_PD

 

ALRM_NAM

(CTLRID = CCN only)

 

 

 

 

CTLR---ID

 

 

Device Name:

48_50_PD

 

 

 

 

 

Description:

text string

 

 

 

 

 

Location:

text string

 

 

 

 

 

Software Part Number:

CESR131459---XX---XX

 

 

 

 

 

Model Number:

 

 

 

 

 

 

Serial Number:

 

 

 

 

 

 

Reference Number:

 

 

 

 

 

48/50PD

77

Page 77
Image 77
Carrier 48/50PD05 manual Appendix A - Local Display And Ccn Tables Cont, Mode - Time Clock, Ccn Only Tables