Thermistor Troubleshooting
The electronic control uses thermistors to sense temperatures used to control operation of the unit. Resistances at various temperatures are listed in Table
Air Temperatures
Air temperatures are measured with 10
The supply air temperature (SAT), return air temperature (RAT) and outdoor air temperature (OAT) thermistors use a
C07015
Fig. 10 - SAT, RAT and OAT Thermistor Mounting
Refrigerant Temperatures
Condenser coil temperatures are measured with 5
C07016
Fig. 11 - Saturated Condensing Temperature Thermistor
Location
Thermistor/Temperature Sensor Check
A high quality digital
Connect the digital voltmeter across the appropriate thermistor terminals at the J8 terminal strip on the Main Base Board (see Major System Components section).
Using the voltage reading obtained, read the sensor temperature from Table
To check thermistor accuracy, measure temperature at probe
location with an accurate
If a more accurate check is required, unit must be shut down and thermistor removed and checked at a known temperature (freezing point or boiling point of water) using either voltage drop measured across thermistor at the J8 terminal, or by determining the resistance with unit shut down and thermistor disconnected from J8. Compare the values determined with the value read by the control in the Temperatures mode using the Scrolling Marquee display.