override. Recovery is automatic. Reason for error is either a
faulty sensor, wiring error, or damaged input on the MBB con-
trol board. This error only occurs when the unit is configured
for minimum position override and a 4-20 mA signal is not
present.
T245 (Outside Air Cfm Sensor Failure) — If the outside air cfm
sensor (Inputs
CFM
O.CFM) fails, the economizer will de-
fault to discrete positioning of the economizer (Configuration
IAQ
DCV.C
IAQ.M, Configuration
Econ
EC.MN).
Recovery is automatic. Reason for error is either a faulty sensor,
wiring error, or damaged input on the CEM control board.
T246 (Supply Air Cfm Sensor Failure)If the supply air
cfm sensor (Inputs
CFM
S.CFM) fails, fan tracking is not
possible and the system will shut down. Recovery is automatic.
Reason for error is either a faulty sensor, wiring error, or dam-
aged input on the ECB control board.
T247 (Return Air Cfm Sensor Failure) — If the return air
cfm sensor (Inputs
CFM
R.CFM) fails, fan tracking is not
possible and the system will shut down. Recovery is automatic.
Reason for error is either a faulty sensor, wiring error, or dam-
aged input on the ECB control board.
T300 (Space Temperature Below Limit) — If the space tem-
perature is below the configurable SPT Low Alert Limits (occu-
pied [Configuration
ALLM
SP.L.O] for 5 minutes or
unoccupied [Configuration
ALLM
SP.L.U] for 10 min-
utes), then an alert will be broadcast. The alert will automatically
reset.
T301 (Space Temperature Above Limit) — If the space tem-
perature is above the configurable SPT High Alert Limits
(occupied [Configuration
ALLM
SP.H.O] for 5 minutes or
unoccupied [Configuration
ALLM
SP.H.U] for 10 min-
utes), then an alert will be broadcast. The alert will automati-
cally reset.
T302 (Supply Temperature Below Limit) — If the supply-air
temperature measured by the supply temperature sensor is below
the configurable SAT LO Alert Limit/Occ (Configuration
ALLM
SA.L.O) for 5 minutes or the Low Supply air tempera-
ture alert limit unoccupied mode (Configuration
ALLM
SA.L.U) for 10 minutes, then an alert will be broadcast.
T303 (Supply Temperature Above Limit) — If the supply
temperature is above the configurable SAT HI Alert Limit Occ
(Configuration
ALLM
SAH.O) for 5 minutes or the SAT
HI Alert Limit/Unocc (Configuration
ALLM
SA.H.U) for
10 minutes, then an alert will be broadcast. The alert will auto-
matically reset.
T304 (Return Air Temperature Below Limit) — If the re-
turn air temperature measured by the RAT sensor is below the
configurable RAT LO Alert Limit/Occ (Configuration
ALLM
RA.L.O) for 5 minutes or RAT HI Alert Limit/Occ
(Configuration
ALLM
RA.L.U) for 10 minutes, then an
alert will be broadcast.
T305 (Return Air Temperature Above Limit) — If the return
air temperature is below the RAT HI Alert Limit/Occ (Configu-
ration
ALLM
RA.H.O) for 5 minutes or RAT HI Alert
Limit/Occ (Configuration
ALLM
RA.H.U) for 10 minutes,
then an alert will be broadcast. The alert will automatically reset.
T308 (Return Air Relative Humidity Below Limit) — If the
unit is configured to use a return air relative humidity sensor
through the Return Air RH Sensor (Configuration
UNIT
SENS
RRH.S) setting, and the measured level is below the
configurable RH Low Alert Limit (Configuration
ALLM
R.RH.L) for 5 minutes, then the alert will occur. The unit will
continue to run and the alert will automatically reset.
T309 (Return Air Relative Humidity Above Limit) — If the
unit is configured to use a return air relative humidity sensor
through the Return Air RH Sensor (Configuration
UNIT
SENS
RRH.S) setting, and the measured level is above the
configurable RH High Alert Limit (Configuration
ALLM
R.RH.H) for 5 minutes, then the alert will occur. Unit will con-
tinue to run and the alert will automatically reset.
T310 (Supply Duct Pressure Below Limit) — If the unit is a
VAV unit with a supply duct pressure sensor and the measured
supply duct static pressure (Pressures
AIR.P
SP) is below
the configurable SP Low Alert Limit (Configuration
ALLM
SP.L) for 5 minutes, then the alert will occur. The unit will
continue to run and the alert will automatically reset.
T311 (Supply Duct Pressure Above Limit) If the unit is a
VAV unit with a supply duct pressure sensor and the measured
supply duct static pressure (Pressures
AIR.P
SP) is above
the configurable SP Low Alert Limit (Configuration
ALLM
SP.H) for 5 minutes, then the alert will occur. The unit will
continue to run and the alert will automatically reset.
T312 (Building Static Pressure Below Limit) — If the unit
is configured to use modulating power exhaust then a
building static pressure limit can be configured using the BP
Low Alert Limit (Configuration
ALLM
BP.L). If the mea-
sured pressure (Pressures
AIR.P
BP) is below the limit for
5 minutes then the alert will occur.
T313 (Building Static Pressure Above Limit) — If the unit
is configured to use modulating power exhaust then a
building static pressure limit can be configured using the BP HI
Alert Limit (Configuration
ALLM
BP.H). If the measured
pressure (Pressures
AIR.P
BP) is above the limit for
5 minutes, then the alert will occur.
T314 (IAQ Above Limit) — If the unit is configured to use a
CO2 sensor and the level (Inputs
AIR.Q
IAQ) is above the
configurable IAQ High Alert Limit (Configuration
ALLM
IAQ.H) for 5 minutes then the alert will occur. The unit will
continue to run and the alert will automatically reset.