APPENDIX B — CCN TABLES (cont)
SERVICE-CONFIG TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
BP__ (cont)
Bldg.Pres.PID Run Rate 5 - 120 sec BPIDRATE 10
Bldg.Press. Prop. Gain 0 - 5 BLDGP_PG 1
Bldg.Press. Integ. Gain 0 - 2 BLDGP_IG 1
Bldg.Press. Deriv. Gain 0 - 5 BLDGP_DG 0.5
BP 1 Serial Number 1 0 - 255 BP_1_SN1 0
BP 1 Serial Number 2 0 - 255 BP_1_SN2 0
BP 1 Serial Number 3 0 - 255 BP_1_SN3 0
BP 1 Serial Number 4 0 - 255 BP_1_SN4 0
BP 1 Serial Number 5 0 - 255 BP_1_SN5 0
BP1 Cntrl Angle Lo Limit 0-90 BP1_CALM 35
BP 2 Serial Number 1 0 - 255 BP_2_SN1 0
BP 2 Serial Number 2 0 - 255 BP_2_SN2 0
BP 2 Serial Number 3 0 - 255 BP_2_SN3 0
BP 2 Serial Number 4 0 - 255 BP_2_SN4 0
BP 2 Serial Number 5 0 - 255 BP_2_SN5 0
BP2 Cntrl Angle Lo Limit 0-90 BP2_CALM 35
COOL
Capacity Threshold Adjst -10 - 10 Z_GAIN 1
Compressor Lockout Temp -25 - 55 dF OATLCOMP 40
Lead/Lag Operation ? Yes/No LLENABLE No
Motor Master Control ? Yes/No MOTRMAST No
Head Pressure Setpoint 80 - 150 dF HPSP 113
Enable Compressor A1 Enable/Disable CMPA1ENA Enable
Enable Compressor A2 Enable/Disable CMPA2ENA Enable
Enable Compressor B1 Enable/Disable CMPB1ENA Enable
Enable Compressor B2 Enable/Disable CMPB2ENA Enable
CSB A1 Feedback Alarm Enable/Disable CSB_A1EN Enable
CSB A2 Feedback Alarm Enable/Disable CSB_A2EN Enable
CSB B1 Feedback Alarm Enable/Disable CSB_B1EN Enable
CSB B2 Feedback Alarm Enable/Disable CSB_B2EN Enable
CMPA1 Hi.Pr.Sw. Trip 365-415 PSIG HPSATRIP 415
CMPB1 Hi.Pr.Sw. Trip 365-415 PSIG HPSBTRIP 415
Hi SST Alert Delay Time 5 - 30 min HSSTTIME 10
DEHU
Dehumidification Config 0-3 DHSELECT 0
Dehumidification Sensor 1-3 DHSENSOR 1
Econ disable in DH mode? Yes/No DHECONEN No
Vent Reheat Setpt Select 0-1 DHVHTCFG 0
Vent Reheat RAT offset 0-8 ^F DHVRAOFF 0
Vent Reheat Setpoint 55-95 dF DHVHT_SP 70
Dehumidify Cool Setpoint 40-55 dF DHCOOLSP 45
Dehumidify RH Setpoint 10-90 % DHRELHSP 55
DISP
Metric Display Off/On DISPUNIT Off
Language Selection 0-1 LANGUAGE 0
Password Enable Enable/Disable PASS_EBL Enable
Service Password 0000-9999 PASSWORD 1111
Contrast Adjustment 0-255 CNTR_ADJ 0
Brightness Adjustment 0-255 BRTS_ADJ 0
DLVT
Dmd Level Lo Heat On -1 - 2 ^F DMDLHON 1.5
Dmd Level(+) Hi Heat On 0.5 - 20.0 ^F DMDHHON 0.5
Dmd Level(-) Lo Heat Off 0.5 - 2.0 ^F DMDLHOFF 1
Dmd Level Lo Cool On -1 - 2 ^F DMDLCON 1.5
Dmd Level(+) Hi Cool On 0.5 - 20.0 ^F DMDHCON 0.5
Dmd Level(-) Lo Cool Off 0.5 - 2.0 ^F DMDLCOFF 1
Cool Trend Demand Level 0.1 - 5.0 ^F CTRENDLV 0.1
Heat Trend Demand Level 0.1 - 5.0 ^F HTRENDLV 0.1
Cool Trend Time 30 - 600 sec CTRENDTM 120
Heat Trend Time 30 - 600 sec HTRENDTM 120
DMDL
Demand Limit Select 0 - 3 DMD_CTRL 0
Demand Limit at 20 ma 0 - 100 % DMT20MA 100
Loadshed Group Number 0 - 99 SHED_NUM 0
Loadshed Demand Delta 0 - 60 % SHED_DEL 0
Maximum Loadshed Time 0 - 120 min SHED_TIM 60
Demand Limit Sw.1 Setpt. 0 - 100 % DLSWSP1 80
Demand Limit Sw.2 Setpt. 0 - 100 % DLSWSP2 50