CL-5
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
ITEM EXPANSION RANGE DEFAULT SETTING
IAQ (cont)
→AQ.SP AIR QUALITY SETPOINTS
→AQ.SP→IQ.O.P IAQ Econo Override Pos. 0 - 100% 100
→AQ.SP→IQ.O.C IAQ Override Flow 0 - 31000 CFM 10000
→AQ.SP→DAQ.L Diff.Air Quality LoLimit 0 - 1000 100
→AQ.SP→DAQ.H Diff. Air Quality HiLimit 100 - 2000 700
→AQ.SP→D.F.OF DAQ PPM Fan Off Setpoint 0 - 2000 200
→AQ.SP→D.F.ON DAQ PPM Fan On Setpoint 0 - 2000 400
→AQ.SP→IAQ.R Diff. AQ Responsiveness -5 - 5 0
→AQ.SP→OAQ.L OAQ Lockout Value 0 - 2000 0
→AQ.SP→OAQ.U User Determined OAQ 0 - 5000 400
→AQ.S.R AIR QUALITY SENSOR RANGE
→AQ.S.R→IQ.R.L IAQ Low Reference 0 - 5000 0
→AQ.S.R→IQ.R.H IAQ High Reference 0 - 5000 2000
→AQ.S.R→OQ.R.L OAQ Low Reference 0 - 5000 0
→AQ.S.R→OQ.R.H OAQ High Reference 0 - 5000 2000
→IAQ.P IAQ PRE-OCCUPIED PURGE
→IAQ.P→IQ.PG IAQ Purge Yes/No No
→IAQ.P→IQ.P.T IAQ Purge Duration 5 - 60 min 15
→IAQ.P→IQ.P.L IAQ Purge LoTemp Min Pos 0 - 100% 10
→IAQ.P→IQ.P.H IAQ Purge HiTemp Min Pos 0 - 100% 35
→IAQ.P→IQ.L.O IAQ Purge OAT Lockout 35 - 70 dF 50
HUMD HUMIDITY CONFIGURATION
→HM.CF Humidifier Control Cfg. 0 - 4 0
→HM.SP Humidifier Setpoint 0 - 100% 40
→H.PID HUMIDIFIER PID CONFIGS
→H.PID→HM.TM Humidifier PID Run Rate 10 - 120 sec 30
→H.PID→HM.P Humidifier Prop. Gain 0 - 5 1
→H.PID→HM.I Humidifier Integral Gain 0 - 5 0.3
→H.PID→HM.D Humidifier Deriv. Gain 0 - 5 0.3
→ACT.C HUMIDIFIER ACTUATOR CFGS
→ACTC→SN.1 Humd Serial Number 1 0 - 255 0
→ACTC→SN.2 Humd Serial Number 2 0 - 255 0
→ACTC→SN.3 Humd Serial Number 3 0 - 255 0
→ACTC→SN.4 Humd Serial Number 4 0 - 255 0
→ACTC→SN.5 Humd Serial Number 5 0 - 255 0
→ACTC→C.A.LM Humd Ctrl Angle Lo Limit 0-90 85
DEHU DEHUMIDIFICATION CONFIG.
→D.SEL Dehumidification Config 0-3(multi-text strings) 0
→D.SEN Dehumidification Sensor 1-3(multi-text strings) 1
→D.EC.D Econ disable in DH mode? Yes/No Yes
→D.V.CF Vent Reheat Setpt Select 0-1(multi-text strings) 0
→D.V.RA Vent Reheat RAT offset 0-8 delta F 0
→D.V.HT Vent Reheat Setpoint 55-95 dF 70
→D.C.SP Dehumidify Cool Setpoint 40-55 dF 45
→D.RH.S Dehumidify RH Setpoint 10-90% 55
CCN CCN CONFIGURATION
→CCNA CCN Address 1 - 239 1
→CCNB CCN Bus Number 0 - 239 0
→BAUD CCN Baud Rate 1 - 5 (multi-text strings) 3
→BROD CCN BROADCST DEFINITIONS
→BROD→TM.DT CCN Time/Date Broadcast ON/OFF On
→BROD→OAT.B CCN OAT Broadcast ON/OFF Off
→BROD→ORH.B CCN OARH Broadcast ON/OFF Off
→BROD→OAQ.B CCN OAQ Broadcast ON/OFF Off
→BROD→G.S.B Global Schedule Broadcst ON/OFF Off
→BROD→B.ACK CCN Broadcast Ack'er ON/OFF Off
→SC.OV CCN SCHEDULES-OVERRIDES
→SC.OV→SCH.N Schedule Number 0 - 99 1
→SC.OV→HOL.T Accept Global Holidays? YES/NO No
→SC.OV→O.T.L. Override Time Limit 0 - 4 HRS 1
→SC.OV→OV.EX Timed Override Hours 0 - 4 HRS 0