Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480039-01 Printed in U.S.A. Form 48/50Z-5T CL-1 7-08 Replaces: 48/50Z-4T
ITEM EXPANSION RANGE DEFAULT SETTING
UNIT UNIT CONFIGURATION
C.TYP Machine Control Type 1 - 6 (multi-text strings) 4
CV.FN Fan Mode (0=Auto, 1=Cont) 0 - 1 (multi-text strings) 1
RM.CF Remote Switch Config 0 - 3 (multi-text strings) 0
CEM CEM Module Installed Yes/No No
TCS.C Temp.Cmp.Strt.Cool Factr 0 - 60 min 0
TCS.H Temp.Cmp.Strt.Heat Factr 0 - 60 min 0
SFS.S Fan Fail Shuts Down Unit Yes/No No
SFS.M Fan Stat Monitoring Type 0 - 2 (multi-text strings) 0
VAV.S VAV Unocc.Fan Retry Time 0 - 720 min 50
SIZE Unit Size (30-105) 30 - 105 30
50.HZ 50 Hertz Unit ? Yes/No No
MAT.S MAT Calc Config 0 - 2 (multi-text strings) 1
MAT.R Reset MAT Table Entries? Yes/No No
MAT.D MAT Outside Air Default 0 - 100‘% 20
ALTI Altitude……..in feet: 0 - 60000 0
DLAY Startup Delay Time 0 - 900 secs 0
AUX.R Auxiliary Relay Config 0 - 3 (multi-text strings) 0
SENS INPUT SENSOR CONFIG
SENSSPT.S Space Temp Sensor Enable/Disable Disable
SENSSP.O.S Space Temp Offset Sensor Enable/Disable Disable
SENSSP.O.R Space Temp Offset Range 1 - 10 5
SENSSRH.S Space Air RH Sensor Enable/Disable Disable
SENSRRH.S Return Air RH Sensor Enable/Disable Disable
SENSFLT.S Filter Stat.Sw.Enabled ? Enable/Disable Disable
COOL COOLING CONFIGURATION
Z.GN Capacity Threshold Adjst -10 - 10 1
MC.LO Compressor Lockout Temp -25 - 55 dF 40
L.L.EN Lead/Lag Operation ? Yes/No No
M.M. Motor Master Control ? Yes/No No
HPSP Head Pressure Setpoint 80 - 150 dF 113
A1.EN Enable Compressor A1 Enable/Disable Enable
A2.EN Enable Compressor A2 Enable/Disable Enable
B1.EN Enable Compressor B1 Enable/Disable Enable
B2.EN Enable Compressor B2 Enable/Disable Enable
CS.A1 CSB A1 Feedback Alarm Enable/Disable Enable
CS.A2 CSB A2 Feedback Alarm Enable/Disable Enable
CS.B1 CSB B1 Feedback Alarm Enable/Disable Enable
CS.B2 CSB B2 Feedback Alarm Enable/Disable Enable
HPS.A CMPA1 Hi.Pr.Sw. Trip 365 - 415 PSIG 415
HPS.B CMPB1 Hi.Pr.Sw. Trip 365 - 415 PSIG 415
H.SST Hi SST Alert Delay Time 5 - 30 min 10
EDT.R EVAP.DISCHRGE TEMP RESET
RS.CF EDT Reset Configuration 0 - 3 (multi-text strings) 2
RTIO Reset Ratio 0 - 10 3
LIMT Reset Limit 0 - 20 ^F 10
RES.S EDT 4-20 ma Reset Input Enable/Disable Disable

CONTROLS SET POINT AND CONFIGURATION LOG

MODEL NUMBER: Software Version
SERIAL NUMBER: MBB CESR131292--
DATE: RCB CESR131249--
TECHNICIAN: ECB CESR131249--
NAVI CESR131227--
SCB CESR131226--
CEM CESR131174--
MARQ CESR131171--