CL-4

-
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
ITEM EXPANSION RANGE DEFAULT SETTING
BP (cont)
FAN.T FAN TRACKING CONFIG
FAN.TFT.CF Fan Track Learn Enable Yes/No No
FAN.TFT.TM Fan Track Learn Rate 5-60 min 15
FAN.TFT.ST Fan Track Initial DCFM -20000 - 20000 CFM 2000
FAN.TFT.MX Fan Track Max Clamp 0 - 20000 CFM 4000
FAN.TFT.AD Fan Track Max Correction 0 -20000 CFM 1000
FAN.TFT.OF Fan Track Internl EEPROM -20000 - 20000 CFM 0
FAN.TFT.RM Fan Track Internal RAM -20000 - 20000 CFM 0
FAN.TFT.RS Fan Track Reset Internal Yes/No No
FAN.TSCF.C Supply Air CFM Config 1 - 2 (multi-text strings) 1
B.PID BLDG.PRESS.PID CONFIGS
B.PIDBP.TM Bldg.Pres.PID Run Rate 5 - 120 sec 10
B.PIDBP.P Bldg.Press. Prop. Gain 0 - 5 0.5
B.PIDBP.I Bldg.Press. Integ. Gain 0 - 2 0.5
B.PIDBP.D Bldg.Press. Deriv. Gain 0 - 5 0.3
ACT.C BLDG.PRES. ACTUATOR CFGS
ACT.CBP.1 BLDG.PRES. ACT.1 CONFIGS
ACT.CBP.1SN.1 BP 1 Serial Number 1 0 - 255 0
ACT.CBP.1SN.2 BP 1 Serial Number 2 0 - 255 0
ACT.CBP.1SN.3 BP 1 Serial Number 3 0 - 255 0
ACT.CBP.1SN.4 BP 1 Serial Number 4 0 - 255 0
ACT.CBP.1SN.5 BP 1 Serial Number 5 0 - 255 0
ACT.CBP.1C.A.LM BP1 Cntrl Angle Lo Limit 0-90 35
ACT.CBP.2 BLDG.PRES. ACT.2 CONFIGS
ACT.CBP.2SN.1 BP 2 Serial Number 1 0 - 255 0
ACT.CBP.2SN.2 BP 2 Serial Number 2 0 - 255 0
ACT.CBP.2SN.3 BP 2 Serial Number 3 0 - 255 0
ACT.CBP.2SN.4 BP 2 Serial Number 4 0 - 255 0
ACT.CBP.2SN.5 BP 2 Serial Number 5 0 - 255 0
ACT.CBP.2C.A.LM BP2 Cntrl Angle Lo Limit 0-90 35
D.LV.T COOL/HEAT SETPT. OFFSETS
L.H.ON Dmd Level Lo Heat On -1 - 2 ^F 1.5
H.H.ON Dmd Level(+) Hi Heat On 0.5 - 20.0 ^F 0.5
L.H.OF Dmd Level(-) Lo Heat Off 0.5 - 2.0 ^F 1.0
L.C.ON Dmd Level Lo Cool On -1 - 2 ^F 1.5
H.C.ON Dmd Level(+) Hi Cool On 0.5 - 20.0 ^F 0.5
L.C.OF Dmd Level(-) Lo Cool Off 0.5 - 2.0 ^F 1.0
C.T.LV Cool Trend Demand Level 0.1 - 5.0 ^F 0.1
H.T.LV Heat Trend Demand Level 0.1 - 5.0 ^F 0.1
C.T.TM Cool Trend Time 30 - 600 sec 120
H.T.TM Heat Trend Time 30 - 600 sec 120
DMD.L DEMAND LIMIT CONFIG.
DM.L.S Demand Limit Select 0 - 3 (multi-text strings) 0
D.L.20 Demand Limit at 20 ma 0 - 100% 100
SH.NM Loadshed Group Number 0 - 99 0
SH.DL Loadshed Demand Delta 0 - 60% 0
SH.TM Maximum Loadshed Time 0 - 120 min 60
D.L.S1 Demand Limit Sw.1 Setpt. 0 - 100% 80
D.L.S2 Demand Limit Sw.2 Setpt. 0 - 100% 50
IAQ INDOOR AIR QUALITY CFG.
DCV.C DCV ECONOMIZER SETPOINTS
DCV.CEC.MN Economizer Min.Position 0 - 100% 5
DCV.CIAQ.M IAQ Demand Vent Min.Pos. 0 - 100% 0
DCV.CO.C.MX Economizer Min.Flow 0 - 20000 CFM 2000
DCV.CO.C.MN IAQ Demand Vent Min.Flow 0 - 20000 CFM 0
DCV.CO.C.DB Econ.Min.Flow Deadband 200 - 1000 CFM 400
AQ.CF AIR QUALITY CONFIGS
AQ.CFIQ.A.C IAQ Analog Sensor Config 0 - 4 (multi-text strings) 0
AQ.CFIQ.A.F IAQ 4-20 ma Fan Config 0 - 2 (multi-text strings) 0
AQ.CFIQ.I.C IAQ Discrete Input Config 0 - 2 (multi-text strings) 0
AQ.CFIQ.I.F IAQ Disc.In. Fan Config 0 - 2 (multi-text strings) 0
AQ.CFOQ.A.C OAQ 4-20ma Sensor Config 0 - 2 (multi-text strings) 0