CL-2

-
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
ITEM EXPANSION RANGE DEFAULT SETTING
HEAT HEATING CONFIGURATION
HT.CF Heating Control Type 0 - 4 0
HT.SP Heating Supply Air Setpt 80 - 120 dF 85
OC.EN Occupied Heating Enabled Yes/No No
LAT.M MBB Sensor Heat Relocate Yes/No No
SG.CF STAGED GAS CONFIGS
SG.CFHT.ST Staged Gas Heat Type 0 - 4 0
SG.CFCAP.M Max Cap Change per Cycle 5 - 45 45
SG.CFM.R.DB S.Gas DB min.dF/PID Rate 0 - 5 0.5
SG.CFS.G.DB St.Gas Temp. Dead Band 0 - 5 ^F 2
SG.CFRISE Heat Rise dF/sec Clamp 0.05 - 0.2 0.06
SG.CFLAT.L LAT Limit Config 0 - 20 ^F 10
SG.CFLIM.M Limit Switch Monitoring? Yes/No Yes
SG.CFSW.H.T Limit Switch High Temp 110 - 180 dF 170
SG.CFSW.L.T Limit Switch Low Temp 100 - 170 dF 160
SG.CFHT.P Heat Control Prop. Gain 0 - 1.5 1
SG.CFHT.D Heat Control Derv. Gain 0 - 1.5 1
SG.CFHT.TM Heat PID Rate Config 60 - 300 sec 90
HH.CF HYDRONIC HEAT CONFIGS
HH.CFHW.P Hydronic Ctl.Prop. Gain 0 - 1.5 1
HH.CFHW.I Hydronic Ctl.Integ. Gain 0 - 1.5 1
HH.CFHW.D Hydronic Ctl.Derv. Gain 0 - 1.5 1
HH.CFHW.TM Hydronic PID Rate Config 15 - 300 sec 90
HH.CFACT.C HYDR.HEAT ACTUATOR CFGS.
HH.CFACTCSN.1 Hydronic Ht.Serial Num.1 0 - 255 0
HH.CFACTCSN.2 Hydronic Ht.Serial Num.2 0 - 255 0
HH.CFACTCSN.3 Hydronic Ht.Serial Num.3 0 - 255 0
HH.CFACTCSN.4 Hydronic Ht.Serial Num.4 0 - 255 0
HH.CFACTCSN.5 Hydronic Ht.Serial Num.5 0 - 255 0
HH.CFACTCC.A.LM Hydr.Ht.Ctl.Ang.Lo Limit 0-90 85
SP SUPPLY STATIC PRESS.CFG.
SP.CF Static Pressure Config 0-2 (multi-text strings) 0
SP.S Static Pressure Sensor Enable/Disable Disable
SP.LO Static Press. Low Range -10 - 0 0
SP.HI Static Press. High Range 0 - 10 5
SP.SP Static Pressure Setpoint 0 - 5 1.5
SP.MN VFD-IGV Minimum Speed 0 - 100 20
SP.MX VFD-IGV Maximum Speed 0 - 100 100
SP.FS VFD-IGV Fire Speed Over. 0 - 100 100
SP.RS Stat. Pres. Reset Config 0 - 4 (multi-text strings) 0
SP.RT SP Reset Ratio 0.00 - 2.00 0.20
SP.LM SP Reset Limit 0.00 - 2.00 0.75
SP.EC SP Reset Econo Position 0 - 100% 5
S.PID STAT.PRESS.PID CONFIGS
S.PIDSP.TM Stat.Pres.PID Run Rate 5 - 120 15
S.PIDSP.P Static Press. Prop. Gain 0 - 5 0.5
S.PIDSP.I Static Pressure Intg. Gain 0 - 2 0.5
S.PIDSP.D Static Pressure Derv. Gain 0 - 5 0.3
ACT.C IGV ACTUATOR CONFIGS
ACTCSN.1 IGV Serial Number 1 0 - 255 0
ACTCSN.2 IGV Serial Number 2 0 - 255 0
ACTCSN.3 IGV Serial Number 3 0 - 255 0
ACTCSN.4 IGV Serial Number 4 0 - 255 0
ACTCSN.5 IGV Serial Number 5 0 - 255 0
ACTCC.A.LM IGV Cntrl Angle Lo Limit 0-90 25