CONTROLS SET POINT AND CONFIGURATION LOG (cont)
ITEM EXPANSION RANGE DEFAULT SETTING
HEAT HEATING CONFIGURATION
→HT.CF Heating Control Type 0 - 4 0
→HT.SP Heating Supply Air Setpt 80 - 120 dF 85
→OC.EN Occupied Heating Enabled Yes/No No
→LAT.M MBB Sensor Heat Relocate Yes/No No
→SG.CF STAGED GAS CONFIGS
→SG.CF→HT.ST Staged Gas Heat Type 0 - 4 0
→SG.CF→CAP.M Max Cap Change per Cycle 5 - 45 45
→SG.CF→M.R.DB S.Gas DB min.dF/PID Rate 0 - 5 0.5
→SG.CF→S.G.DB St.Gas Temp. Dead Band 0 - 5 ^F 2
→SG.CF→RISE Heat Rise dF/sec Clamp 0.05 - 0.2 0.06
→SG.CF→LAT.L LAT Limit Config 0 - 20 ^F 10
→SG.CF→LIM.M Limit Switch Monitoring? Yes/No Yes
→SG.CF→SW.H.T Limit Switch High Temp 110 - 180 dF 170
→SG.CF→SW.L.T Limit Switch Low Temp 100 - 170 dF 160
→SG.CF→HT.P Heat Control Prop. Gain 0 - 1.5 1
→SG.CF→HT.D Heat Control Derv. Gain 0 - 1.5 1
→SG.CF→HT.TM Heat PID Rate Config 60 - 300 sec 90
→HH.CF HYDRONIC HEAT CONFIGS
→HH.CF→HW.P Hydronic Ctl.Prop. Gain 0 - 1.5 1
→HH.CF→HW.I Hydronic Ctl.Integ. Gain 0 - 1.5 1
→HH.CF→HW.D Hydronic Ctl.Derv. Gain 0 - 1.5 1
→HH.CF→HW.TM Hydronic PID Rate Config 15 - 300 sec 90
→HH.CF→ACT.C HYDR.HEAT ACTUATOR CFGS.
→HH.CF→ACTC→SN.1 Hydronic Ht.Serial Num.1 0 - 255 0
→HH.CF→ACTC→SN.2 Hydronic Ht.Serial Num.2 0 - 255 0
→HH.CF→ACTC→SN.3 Hydronic Ht.Serial Num.3 0 - 255 0
→HH.CF→ACTC→SN.4 Hydronic Ht.Serial Num.4 0 - 255 0
→HH.CF→ACTC→SN.5 Hydronic Ht.Serial Num.5 0 - 255 0
→HH.CF→ACTC→C.A.LM Hydr.Ht.Ctl.Ang.Lo Limit 0-90 85
SP SUPPLY STATIC PRESS.CFG.
→SP.CF Static Pressure Config 0-2 (multi-text strings) 0
→SP.S Static Pressure Sensor Enable/Disable Disable
→SP.LO Static Press. Low Range -10 - 0 0
→SP.HI Static Press. High Range 0 - 10 5
→SP.SP Static Pressure Setpoint 0 - 5 1.5
→SP.MN VFD-IGV Minimum Speed 0 - 100 20
→SP.MX VFD-IGV Maximum Speed 0 - 100 100
→SP.FS VFD-IGV Fire Speed Over. 0 - 100 100
→SP.RS Stat. Pres. Reset Config 0 - 4 (multi-text strings) 0
→SP.RT SP Reset Ratio 0.00 - 2.00 0.20
→SP.LM SP Reset Limit 0.00 - 2.00 0.75
→SP.EC SP Reset Econo Position 0 - 100% 5
→S.PID STAT.PRESS.PID CONFIGS
→S.PID→SP.TM Stat.Pres.PID Run Rate 5 - 120 15
→S.PID→SP.P Static Press. Prop. Gain 0 - 5 0.5
→S.PID→SP.I Static Pressure Intg. Gain 0 - 2 0.5
→S.PID→SP.D Static Pressure Derv. Gain 0 - 5 0.3
→ACT.C IGV ACTUATOR CONFIGS
→ACTC→SN.1 IGV Serial Number 1 0 - 255 0
→ACTC→SN.2 IGV Serial Number 2 0 - 255 0
→ACTC→SN.3 IGV Serial Number 3 0 - 255 0
→ACTC→SN.4 IGV Serial Number 4 0 - 255 0
→ACTC→SN.5 IGV Serial Number 5 0 - 255 0
→ACTC→C.A.LM IGV Cntrl Angle Lo Limit 0-90 25