APPENDIX B — CCN TABLES (cont)
MAINTENANCE DISPLAY TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
EC_DIAG
Economizer Active ? Yes/No ECACTIVE
Conditions which prevent
economizer being active:
Econ Act. Unavailable? Yes/No ECONUNAV
Econ 2 Act. Unavailable? Yes/No ECN2UNAV
Enth.Switch Read High ? Yes/No ENTH
DBC - OAT lockout? Yes/No DBC_STAT
DEW - OA Dewpt. lockout? Yes/No DEW_STAT
DDBC- OAT > RAT lockout? Yes/No DDBCSTAT
OAEC- OA Enth Lockout? Yes/No OAECSTAT
DEC - Diff.Enth.Lockout? Yes/No DEC_STAT
EDT Sensor Bad ? Yes/No EDT_STAT
OAT Sensor Bad ? Yes/No OAT_STAT
Economizer forced ? Yes/No ECONFORC
Supply Fan not on 30s ? Yes/No SFONSTAT
Cool Mode not in effect? Yes/No COOL_OFF
OAQ lockout in effect ? Yes/No OAQLOCKD
Econ recovery hold off? Yes/No ECONHELD
Dehumid. Disabled Econ.? Yes/No DHDISABL
Outside Air Temperature dF OAT forcible
OutsideAir DewPoint Temp dF OADEWTMP
Outside Air Rel.Humidity % OARH forcible
Outdoor Air Enthalpy OAE
Return Air Temperature dF RAT forcible
Return Air Rel.Humidity % RARH forcible
Return Air Enthalpy RAE
High OAT Lockout Temp dF OAT_LOCK config
Econ ChangeOver Select ECON_SEL config
OA Enthalpy ChgOvr Selct OAEC_SEL config
Outdr.Enth Compare Value OAEN_CFG config
OA Dewpoint Temp Limit dF OADEWCFG config
Supply Fan Relay SFAN
Economizer Act.Cmd.Pos. % ECONOCMD forcible
Economizer Act.Curr.Pos. % ECONOPOS
Economzr 2 Act.Curr.Pos. % ECON2POS
Evaporator Discharge Tmp dF EDT
Economizer Control Point dF ECONCPNT
EDT Trend in degF/minute ^F EDTTREND
Economizer Prop.Gain EC_PGAIN config
Economizer Range Adjust ^F EC_RANGE config
Economizer Speed Adjust EC_SPEED config
Economizer Deadband ^F EC_DBAND config
Economizer Timer sec ERATETMR config
ENTHALPY
Outdoor Air Enthalpy OAE
Outside Air Temperature dF OAT forcible
Outside Air Rel.Humidity % OARH forcible
Outside Air RH Sensor OARHSENS config
OA Dewpoint Temp Limit dF OADEWCFG forcible
OutsideAir DewPoint Temp dF OADEWTMP
OutsideAir Humidty Ratio OA_HUMR
OA H2O Vapor Sat.Pressur "Hg OA_PWS
OA H2O Partial.Press.Vap "Hg OA_PWS
Space Enthalpy SPE
Space Temperature dF SPT forcible
Controlling Space Temp dF SPACE_T forcible
Space Relative Humidity % SPRH forcible
Space Temp Sensor SPTSENS config
Space Air RH Sensor SPRHSENS config
Return Air Enthalpy RAE
Return Air Temperature dF RAT forcible
Controlling Return Temp dF RETURN_T forcible
Return Air Rel.Humidity % RARH forcible
Return Air RH Sensor RARHSENS config
Altitude……..in feet: ALTITUDE config
Atmospheric Pressure "Hg ATMOPRES config
HUMIDITY
Space Relative Humidity % SPRH forcible
Return Air Rel.Humidity % RARH forcible
Humidifier Relay HUMIDRLY
Humidifier Act.Curr.Pos. % HUMDRPOS
Humidifier Command Pos. % HUMDCPOS
Humidifier Setpoint % HUSP config
Humidifier Control Config HUMD_CFG config
Humidifier Prop. Gain HUMID_PG config
Humidifier Integral Gain HUMID_IG config
Humidifier Deriv. Gain HUMID_DG config
Humidifier PID Run Rate sec HUMDRATE config
Space Air RH Sensor Enable/Disable SPRHSENS config
Return RH Sensor Enable/Disable RARHSENS config