139
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.
BP BUILDING PRESS. CONFIGS
BP.CF Building Press. Config 0 - 5 (multi-text strings) BLDG_CFG 0 70,71
BP.S Building Pressure Sensor Enable/Disable BPSENS Disable 70,71
BP.R Bldg. Press. (+/-) Range 0.10 - 0.25 "H2O BP_RANGE 0.25 70,71
BP.SP Building Pressure Setp. -0.25 - 0.25 "H2O BPSP 0.05 70,71
BP.SO BP Setpoint Offset 0 - 0.5 "H2O BPSO 0.05 70,71
BP.P1 Power Exhaust On Setp.1 0 - 100 % PES1 25 70,71
BP.P2 Power Exhaust On Setp.2 0 - 100 % PES2 75 70,71
B.V.A VFD/ACTUATOR CONFIG
B.V.ABP.FS VFD/Act. Fire Speed/Pos. 0 - 100 % BLDGPFSO 100 70,71
B.V.ABP.MN VFD/Act. Min.Speed/Pos. 0 - 50 % BLDGPMIN 0 70,71
B.V.ABP.MX VFD Maximum Speed 50 - 100 % BLDGPMAX 100 70,71
B.V.ABP.1M BP 1 Actuator Max Pos. 85 - 100 % BP1SETMX 100 70,71
B.V.ABP.2M BP 2 Actuator Max Pos. 85 - 100 % BP2SETMX 100 70,71
B.V.ABP.CL BP Hi Cap VFD Clamp Val. 5 - 25 % BLDGCLMP 10 70,71
FAN.T FAN TRACKING CONFIG
FAN.TFT.CF Fan Track Learn Enable Yes/No DCFM_CFG No 70,71
FAN.TFT.TM Fan Track Learn Rate 5-60 min DCFMRATE 15 70,71
FAN.TFT.ST Fan Track Initial DCFM -20000 - 20000 CFM DCFMSTRT 2000 70,71
FAN.TFT.MX Fan Track Max Clamp 0 - 20000 CFM DCFM_MAX 4000 70,71
FAN.TFT.AD Fan Track Max Correction 0 -20000 CFM DCFM_ADJ 1000 70,71
FAN.TFT.OF Fan Track Internl EEPROM -20000 - 20000 CFM DCFM_OFF 0 70,71
FAN.TFT.RM Fan Track Internal RAM -20000 - 20000 CFM DCFM_RAM 0 70,71
FAN.TFT.RS Fan Track Reset Internal Yes/No DCFMRSET No 70,71
FAN.TSCF.C Supply Air CFM Config 1 - 2 (multi-text strings) SCFM_CFG 1 70,71
B.PID BLDG.PRESS.PID CONFIGS
B.PIDBP.TM Bldg.Pres.PID Run Rate 5 - 120 sec BPIDRATE 10 70,71
B.PIDBP.P Bldg.Press. Prop. Gain 0 - 5 BLDGP_PG 0.5 70,71
B.PIDBP.I Bldg.Press. Integ. Gain 0 - 2 BLDGP_IG 0.5 70,71
B.PIDBP.D Bldg.Press. Deriv. Gain 0 - 5 BLDGP_DG 0.3 70,71
ACT.C BLDG.PRES. ACTUATOR CFGS
ACT.CBP.1 BLDG.PRES. ACT.1 CONFIGS
ACT.CBP.1SN.1 BP 1 Serial Number 1 0 - 255 BP_1_SN1 0 70-72
ACT.CBP.1SN.2 BP 1 Serial Number 2 0 - 255 BP_1_SN2 0 70-72
ACT.CBP.1SN.3 BP 1 Serial Number 3 0 - 255 BP_1_SN3 0 70-72
ACT.CBP.1SN.4 BP 1 Serial Number 4 0 - 255 BP_1_SN4 0 70-72
ACT.CBP.1SN.5 BP 1 Serial Number 5 0 - 255 BP_1_SN5 0 70-72
ACT.CBP.1C.A.LM BP1 Cntrl Angle Lo Limit 0-90 BP1_CALM 35 70-72
ACT.CBP.2 BLDG.PRES. ACT.2 CONFIGS
ACT.CBP.2SN.1 BP 2 Serial Number 1 0 - 255 BP_2_SN1 0 70-72
ACT.CBP.2SN.2 BP 2 Serial Number 2 0 - 255 BP_2_SN2 0 70-72
ACT.CBP.2SN.3 BP 2 Serial Number 3 0 - 255 BP_2_SN3 0 70-72
ACT.CBP.2SN.4 BP 2 Serial Number 4 0 - 255 BP_2_SN4 0 70-72
ACT.CBP.2SN.5 BP 2 Serial Number 5 0 - 255 BP_2_SN5 0 70-72
ACT.CBP.2C.A.LM BP2 Cntrl Angle Lo Limit 0-90 BP2_CALM 35 70-72
D.LV.T COOL/HEAT SETPT. OFFSETS
L.H.ON Dmd Level Lo Heat On -1 - 2 ^F DMDLHON 1.5 48,55,56
H.H.ON Dmd Level(+) Hi Heat On 0.5 - 20.0 ^F DMDHHON 0.5 48,55,56
L.H.OF Dmd Level(-) Lo Heat Off 0.5 - 2.0 ^F DMDLHOFF 1 48,55,56
L.C.ON Dmd Level Lo Cool On -1 - 2 ^F DMDLCON 1.5 48,49,55
H.C.ON Dmd Level(+) Hi Cool On 0.5 - 20.0 ^F DMDHCON 0.5 48,49,55
L.C.OF Dmd Level(-) Lo Cool Off 0.5 - 2.0 ^F DMDLCOFF 1 48,49,55
C.T.LV Cool Trend Demand Level 0.1 - 5.0 ^F CTRENDLV 0.1 48,49,55
H.T.LV Heat Trend Demand Level 0.1 - 5.0 ^F HTRENDLV 0.1 48,55,56
C.T.TM Cool Trend Time 30 - 600 sec CTRENDTM 120 48,49,55
H.T.TM Heat Trend Time 30 - 600 sec HTRENDTM 120 48,55,56
DMD.L DEMAND LIMIT CONFIG.
DM.L.S Demand Limit Select 0 - 3 (multi-text strings) DMD_CTRL 0 52,53
D.L.20 Demand Limit at 20 ma 0 - 100 % DMT20MA 100 53
SH.NM Loadshed Group Number 0 - 99 SHED_NUM 0 53
SH.DL Loadshed Demand Delta 0 - 60 % SHED_DEL 0 53
SH.TM Maximum Loadshed Time 0 - 120 min SHED_TIM 60 53
D.L.S1 Demand Limit Sw.1 Setpt. 0 - 100 % DLSWSP1 80 53
D.L.S2 Demand Limit Sw.2 Setpt. 0 - 100 % DLSWSP2 50 53
IAQ INDOOR AIR QUALITY CFG.
DCV.C DCV ECONOMIZER SETPOINTS
DCV.CEC.MN Economizer Min.Position 0 - 100 % ECONOMIN 5 74-76
DCV.CIAQ.M IAQ Demand Vent Min.Pos. 0 - 100 % IAQMINP 0 74,75
DCV.CO.C.MX Economizer Min.Flow 0 - 20000 CFM OACFMMAX 2000 74
DCV.CO.C.MN IAQ Demand Vent Min.Flow 0 - 20000 CFM OACFMMIN 0 74
DCV.CO.C.DB Econ.Min.Flow Deadband 200 - 1000 CFM OACFM_DB 400 74
AQ.CF AIR QUALITY CONFIGS
AQ.CFIQ.A.C IAQ Analog Sensor Config 0 - 4 (multi-text strings) IAQANCFG 0 74
AQ.CFIQ.A.F IAQ 4-20 ma Fan Config 0 - 2 (multi-text strings) IAQANFAN 0 74
AQ.CFIQ.I.C IAQ Discrete Input Config 0 - 2 (multi-text strings) IAQINCFG 0 74,75
AQ.CFIQ.I.F IAQ Disc.In. Fan Config 0 - 2 (multi-text strings) IAQINFAN 0 74,75
AQ.CFOQ.A.C OAQ 4-20ma Sensor Config 0 - 2 (multi-text strings) OAQANCFG 0 74,75
AQ.SP AIR QUALITY SETPOINTS
AQ.SPIQ.O.P IAQ Econo Override Pos. 0 - 100 % IAQOVPOS 100 74,75
AQ.SPIQ.O.C IAQ Override Flow 0 - 31000 CFM IAQOVCFM 10000 74
AQ.SPDAQ.L Diff.Air Quality LoLimit 0 - 1000 DAQ_LOW 100 74-76
AQ.SPDAQ.H Diff. Air Quality HiLimit 100 - 2000 DAQ_HIGH 700 74-76
AQ.SPD.F.OF DAQ PPM Fan Off Setpoint 0 - 2000 DAQFNOFF 200 74,75
AQ.SPD.F.ON DAQ PPM Fan On Setpoint 0 - 2000 DAQFNON 400 74,75
AQ.SPIAQ.R Diff. AQ Responsiveness -5 - 5 IAQREACT 0 74,76
AQ.SPOAQ.L OAQ Lockout Value 0 - 2000 OAQLOCK 0 74,75
AQ.SPOAQ.U User Determined OAQ 0 - 5000 OAQ_USER 400 74
AQ.S.R AIR QUALITY SENSOR RANGE
AQ.S.RIQ.R.L IAQ Low Reference 0 - 5000 IAQREFL 0 74,75
AQ.S.RIQ.R.H IAQ High Reference 0 - 5000 IAQREFH 2000 74,75
AQ.S.ROQ.R.L OAQ Low Reference 0 - 5000 OAQREFL 0 74,76
AQ.S.ROQ.R.H OAQ High Reference 0 - 5000 OAQREFH 2000 74,76
IAQ.P IAQ PRE-OCCUPIED PURGE
IAQ.PIQ.PG IAQ Purge Yes/No IAQPURGE No 74,76
IAQ.PIQ.P.T IAQ Purge Duration 5 - 60 min IAQPTIME 15 74,76
IAQ.PIQ.P.L IAQ Purge LoTemp Min Pos 0 - 100 % IAQPLTMP 10 74,76
IAQ.PIQ.P.H IAQ Purge HiTemp Min Pos 0 - 100 % IAQPHTMP 35 74,76
IAQ.PIQ.L.O IAQ Purge OAT Lockout 35 - 70 dF IAQPNTLO 50 74,76