138
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.
EDT.R EVAP.DISCHRGE TEMP RESET
RS.CF EDT Reset Configuration 0 - 3 (multi-text strings) EDRSTCFG 2 46,47
RTIO Reset Ratio 0 - 10 RTIO 3 46,47
LIMT Reset Limit 0 - 20 deltaF LIMT 10 46,47
RES.S EDT 4-20 ma Reset Input Enable/Disable EDTRSENS Disable 46,47
HEAT HEATING CONFIGURATION
HT.CF Heating Control Type 0 - 4 HEATTYPE 0 54,55
HT.SP Heating Supply Air Setpt 80 - 120 dF SASPHEAT 85 54,55
OC.EN Occupied Heating Enabled Yes/No HTOCCENA No 54,55
LAT.M MBB Sensor Heat Relocate Yes/No HTLATMON No 54,55
SG.CF STAGED GAS CONFIGS
SG.CFHT.ST Staged Gas Heat Type 0 - 4 HTSTGTYP 0 54,57,58
SG.CFCAP.M Max Cap Change per Cycle 5 - 45 HTCAPMAX 45 54,57,58
SG.CFM.R.DB S.Gas DB min.dF/PID Rate 0 - 5 HT_MR_DB 0.5 54,57,58
SG.CFS.G.DB St.Gas Temp. Dead Band 0 - 5 ^F HT_SG_DB 2 54,57,58
SG.CFRISE Heat Rise dF/sec Clamp 0.05 - 0.2 HTSGRISE 0.06 54,57,58
SG.CFLAT.L LAT Limit Config 0 - 20 ^F HTLATLIM 10 54,57,58
SG.CFLIM.M Limit Switch Monitoring? Yes/No HTLIMMON Yes 54,57,58
SG.CFSW.H.T Limit Switch High Temp 110 - 180 dF HT_LIMHI 170 54,57,58
SG.CFSW.L.T Limit Switch Low Temp 100 - 170 dF HT_LIMLO 160 54,57,58
SG.CFHT.P Heat Control Prop. Gain 0 - 1.5 HT_PGAIN 1 54,57,58
SG.CFHT.D Heat Control Derv. Gain 0 - 1.5 HT_DGAIN 1 54,58
SG.CFHT.TM Heat PID Rate Config 60 - 300 sec HTSGPIDR 90 54,58
HH.CF HYDRONIC HEAT CONFIGS
HH.CFHW.P Hydronic Ctl.Prop. Gain 0 - 1.5 HW_PGAIN 1 54,57
HH.CFHW.I Hydronic Ctl.Integ. Gain 0 - 1.5 HW_IGAIN 1 54,57
HH.CFHW.D Hydronic Ctl.Derv. Gain 0 - 1.5 HW_DGAIN 1 54,57
HH.CFHW.TM Hydronic PID Rate Config 15 - 300 sec HOTWPIDR 90 54,57
HH.CFACT.C HYDR.HEAT ACTUATOR CFGS.
HH.CFACTCSN.1 Hydronic Ht.Serial Num.1 0 - 255 HTCL_SN1 0 54,57
HH.CFACTCSN.2 Hydronic Ht.Serial Num.2 0 - 255 HTCL_SN2 0 54,57
HH.CFACTCSN.3 Hydronic Ht.Serial Num.3 0 - 255 HTCL_SN3 0 54,57
HH.CFACTCSN.4 Hydronic Ht.Serial Num.4 0 - 255 HTCL_SN4 0 54,57
HH.CFACTCSN.5 Hydronic Ht.Serial Num.5 0 - 255 HTCL_SN5 0 54,57
HH.CFACTCC.A.LM Hydr.Ht.Ctl.Ang.Lo Limit 0-90 HTCLCALM 85 54,57
SP SUPPLY STATIC PRESS.CFG.
SP.CF Static Pressure Config 0-2 (multi-text strings) STATICFG 0 62
SP.S Static Pressure Sensor Enable/Disable SPSENS Disable 62
SP.LO Static Press. Low Range -10 - 0 SP_LOW 0 62
SP.HI Static Press. High Range 0 - 10 SP_HIGH 5 62
SP.SP Static Pressure Setpoint 0 - 5 SPSP 1.5 62
SP.MN VFD-IGV Minimum Speed 0 - 100 STATPMIN 20 62
SP.MX VFD-IGV Maximum Speed 0 - 100 STATPMAX 100 62
SP.FS VFD-IGV Fire Speed Over. 0 - 100 STATPFSO 100 62
SP.RS Stat. Pres. Reset Config 0 - 4 (multi-text strings) SPRSTCFG 0 62
SP.RT SP Reset Ratio 0.00 - 2.00 SPRRATIO 0.20 62
SP.LM SP Reset Limit 0.00 - 2.00 SPRLIMIT 0.75 62
SP.EC SP Reset Econo. Position 0 - 100 % ECONOSPR 5 62,63
S.PID STAT.PRESS.PID CONFIGS
S.PIDSP.TM Stat.Pres.PID Run Rate 5 - 120 SPIDRATE 15 62,63
S.PIDSP.P Static Press. Prop. Gain 0 - 5 STATP_PG 0.5 62,63
S.PIDSP.I Static Pressure Intg. Gain 0 - 2 STATP_IG 0.5 62,63
S.PIDSP.D Static Pressure Derv. Gain 0 - 5 STATP_DG 0.3 62,63
ACT.C IGV ACTUATOR CONFIGS
ACTCSN.1 IGV Serial Number 1 0 - 255 IGV_SN1 0 62,63
ACTCSN.2 IGV Serial Number 2 0 - 255 IGV_SN2 0 62,63
ACTCSN.3 IGV Serial Number 3 0 - 255 IGV_SN3 0 62,63
ACTCSN.4 IGV Serial Number 4 0 - 255 IGV_SN4 0 62,63
ACTCSN.5 IGV Serial Number 5 0 - 255 IGV_SN5 0 62,63
ACTCC.A.LM IGV Cntrl Angle Lo Limit 0-90 IGV_CALM 25 62,63
ECON ECONOMIZER CONFIGURATION
EC.EN Economizer Installed? Yes/No ECON_ENA Yes 65,66
EC2.E Econ.Act.2 Installed? Yes/No ECON_TWO No 65,66
EC.MN Economizer Min.Position 0 - 100 % ECONOMIN 5 65,66
EC.MX Economizer Max.Position 0 - 100 % ECONOMAX 98 65,66
E.TRM Economzr Trim For SumZ ? Yes/No ECONTRIM Yes 65,66
E.SEL Econ ChangeOver Select 0 - 3 (multi-text strings) ECON_SEL 0 66
OA.E.C OA Enthalpy ChgOvr Selct 1 - 5 (multi-text strings) OAEC_SEL 4 66
OA.EN Outdr.Enth Compare Value 18 - 28 OAEN_CFG 24 66
OAT.L High OAT Lockout Temp -40 - 120 dF OAT_LOCK 60 66
O.DEW OA Dewpoint Temp Limit 50 - 62 dF OADEWCFG 55 66,67
ORH.S Outside Air RH Sensor Enable/Disable OARHSENS Disable 66
CFM.C OUTDOOR AIR CFM CONTROL
CFM.COCF.S Outdoor Air CFM Sensor Enable/Disable OCFMSENS Disable 66,68
CFM.CO.C.MX Economizer Min.Flow 0 - 20000 CFM OACFMMAX 2000 66,68
CFM.CO.C.MN IAQ Demand Vent Min.Flow 0 - 20000 CFM OACFMMIN 0 66,68
CFM.CO.C.DB Econ.Min.Flow Deadband 200 - 1000 CFM OACFM_DB 400 66,68
E.CFG ECON.OPERATION CONFIGS
E.CFGE.P.GN Economizer Prop.Gain 0.7 - 3.0 EC_PGAIN 1 66
E.CFGE.RNG Economizer Range Adjust 0.5 - 5 ^F EC_RANGE 2.5 66
E.CFGE.SPD Economizer Speed Adjust 0.1 - 10 EC_SPEED 0.75 66
E.CFGE.DBD Economizer Deadband 0.1 - 2 ^F EC_DBAND 0.5 66
UEFC UNOCC.ECON.FREE COOLING
UEFCFC.CF Unoc Econ Free Cool Cfg 0-2 (multi-text strings) UEFC_CFG 0 66,68
UEFCFC.TM Unoc Econ Free Cool Time 0 - 720 min UEFCTIME 120 66,68
UEFCFC.L.O Un.Ec.Free Cool OAT Lock 40 - 70 dF UEFCNTLO 50 66,68
ACT.C ECON.ACTUATOR CONFIGS
ACTCSN.1.1 Econ Serial Number 1 0 - 255 ECON_SN1 0 66,67
ACTCSN.1.2 Econ Serial Number 2 0 - 255 ECON_SN2 0 66,67
ACTCSN.1.3 Econ Serial Number 3 0 - 255 ECON_SN3 0 66,67
ACTCSN.1.4 Econ Serial Number 4 0 - 255 ECON_SN4 0 66,67
ACTCSN.1.5 Econ Serial Number 5 0 - 255 ECON_SN5 0 66,67
ACTCC.A.L1 Econ Ctrl Angle Lo Limit 0 - 90 ECONCALM 85 66
ACTCSN.2.1 Econ 2 Serial Number 1 0 - 255 ECN2_SN1 0 66,67
ACTCSN.2.2 Econ 2 Serial Number 2 0 - 255 ECN2_SN2 0 66,67
ACTCSN.2.3 Econ 2 Serial Number 3 0 - 255 ECN2_SN3 0 66,67
ACTCSN.2.4 Econ 2 Serial Number 4 0 - 255 ECN2_SN4 0 66,67
ACTCSN.2.5 Econ 2 Serial Number 5 0 - 255 ECN2_SN5 0 66,67
ACTCC.A.L2 Ecn2 Ctrl Angle Lo Limit 0 - 90 ECN2CALM 85 66