136
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — INPUTS
*The display text changes depending on the remote switch configuration (Configuration
→
UNIT
→
RM.CF). If RM.CF is set to 0 (No Remote Switch), then the display
text will be “On” or “Off.” If RM.CF is set to 1 (Occupied/Unoccupied Switch), then the display text will be “Occupied” or “Unoccupied.” If RM.CF is set to 2 (Start/Stop),
then the display text will be “Stop” or “Start.” If RM.CF is set to 3 (Override Switch), then the display text will be “No Override” or “Override.”
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS
GEN.I GENERAL INPUTS
→FLT.S Filter Status Input DRTY/CLN FLTS forcible
→G.FAN Fan Request From IGC ON/OFF IGCFAN
→REMT Remote Input State * RMTIN forcible
→ENTH Enth. Switch Read High ? YES/NO ENTH forcible
→S.FN.S Supply Fan Status Switch ON/OFF SFS forcible
→FRZ.S Freeze Status Switch ALRM/NORM FRZ forcible
→PP.SW Plenum Press.Safety Sw. HIGH/LOW PPS forcible
→DL.S1 Demand Limit Switch 1 ON/OFF DMD_SW1 forcible
→DL.S2 Demand Limit Switch 2 ON/OFF DMD_SW2 forcible
→DH.IN Dehumidify Switch Input ON/OFF DHDISCIN forcible
FD.BK COMPRESSOR FEEDBACK
→HPS.A Circ A High Press. Switch HIGH/LOW CIRCAHPS
→HPS.B Circ B High Press. Switch HIGH/LOW CIRCBHPS
→CS.A1 Compressor A1 Feedback ON/OFF CSB_A1
→CS.A2 Compressor A2 Feedback ON/OFF CSB_A2
→CS.B1 Compressor B1 Feedback ON/OFF CSB_B1
→CS.B2 Compressor B2 Feedback ON/OFF CSB_B2
STAT THERMOSTAT INPUTS
→GThermostat G Input ON/OFF G forcible
→W1 Thermostat W1 Input ON/OFF W1 forcible
→W2 Thermostat W2 Input ON/OFF W2 forcible
→Y1 Thermostat Y1 Input ON/OFF Y1 forcible
→Y2 Thermostat Y2 Input ON/OFF Y2 forcible
FIRE FIRE-SMOKE INPUTS
→FSD Fire Shutdown Input ALRM/NORM FSD forcible
→PRES Pressurization Input ALRM/NORM PRES forcible
→EVAC Evacuation Input ALRM/NORM EVAC forcible
→PURG Smoke Purge Input ALRM/NORM PURG forcible
REL.H RELATIVE HUMIDITY
→OA.RH Outside Air Rel. Humidity % OARH forcible
→OA.EN Outdoor Air Enthalpy OAE
→OA.DP OutsideAir Dewpoint Temp dF OADEWTMP
→RA.RH Return Air Rel. Humidity % RARH forcible
→RA.EN Return Air Enthalpy RAE
→SP.RH Space Relative Humidity % SPRH forcible
→SP.EN Space Enthalpy SPE
AIR.Q AIR QUALITY SENSORS
→IAQ.I IAQ - Discrete Input HIGH/LOW IAQIN forcible
→IAQ IAQ - PPM Return CO2 IAQ forcible
→OAQ OAQ - PPM Return CO2 OAQ forcible
→DAQ Diff.Air Quality in PPM DAQ
→IQ.P.O IAQ Min.Pos. Override % IAQMINOV forcible
CFM CFM SENSORS
→O.CFM Outside Air CFM CFM OACFM
→R.CFM Return Air CFM CFM RACFM
→S.CFM Supply Air CFM CFM SACFM
→D.CFM Fan Track Control D.CFM CFM DELTACFM
RSET RESET INPUTS
→SA.S.R Supply Air Setpnt. Reset ^F SASPRSET forcible
→SP.RS Static Pressure Reset SPRESET forcible
4-20 4-20 MILLIAMP INPUTS
→IAQ.M IAQ Milliamps ma IAQ_MA
→OAQ.M OAQ Milliamps ma OAQ_MA
→SP.R.M SP Reset milliamps ma SPRST_MA
→DML.M 4-20 ma Demand Signal ma DMDLMTMA forcible
→EDR.M EDT Reset Milliamps ma EDTRESMA
→ORH.M OARH Milliamps ma OARH_MA
→SRH.M SPRH Milliamps ma SPRH_MA
→RRH.M RARH Milliamps ma RARH_MA
→SAC.M SACFM Milliamps ma SACFM_MA
→SA.M.T Supply Air CFM Trim (ma) -2.0 → 2.0 SAMATRIM
→RAC.M RACFM Milliamps ma RACFM_MA
→RA.M.T Return Air CFM Trim (ma) -2.0 → 2.0 RAMATRIM config
→OAC.M OACFM Milliamps ma OACFM_MA
→OA.M.T Outside Air CFM Trim(ma) -2.0 → 2.0 OAMATRIM config
→BP.M BP Milliamps ma BP_MA
→BP.M.T Bldg. Pressure Trim (ma) -2.0 → 2.0 BPMATRIM config
→SP.M SP Milliamps ma SP_MA
→SP.M.T Static Press. Trim (ma) -2.0 → 2.0 SPMATRIM config