140
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.
HUMD HUMIDITY CONFIGURATION
HM.CF Humidifier Control Cfg. 0 - 4 HUMD_CFG 0 76,77
HM.SP Humidifier Setpoint 0 - 100 % HUSP 40 76,77
H.PID HUMIDIFIER PID CONFIGS
H.PIDHM.TM Humidifier PID Run Rate 10 - 120 sec HUMDRATE 30 76,77
H.PIDHM.P Humidifier Prop. Gain 0 - 5 HUMID_PG 1 76,77
H.PIDHM.I Humidifier Integral Gain 0 - 5 HUMID_IG 0.3 76,77
H.PIDHM.D Humidifier Deriv. Gain 0 - 5 HUMID_DG 0.3 76,77
ACT.C HUMIDIFIER ACTUATOR CFGS
ACTCSN.1 Humd Serial Number 1 0 - 255 HUMD_SN1 0 77
ACTCSN.2 Humd Serial Number 2 0 - 255 HUMD_SN2 0 77
ACTCSN.3 Humd Serial Number 3 0 - 255 HUMD_SN3 0 77
ACTCSN.4 Humd Serial Number 4 0 - 255 HUMD_SN4 0 77
ACTCSN.5 Humd Serial Number 5 0 - 255 HUMD_SN5 0 77
ACTCC.A.LM Humd Ctrl Angle Lo Limit 0-90 HUMDCALM 85 77
DEHU DEHUMIDIFICATION CONFIG.
D.SEL Dehumidification Config 0-3(multi-text strings) DHSELECT 0 77,78
D.SEN Dehumidification Sensor 1-3(multi-text strings) DHSENSOR 1 78
D.EC.D Econ disable in DH mode? Yes/No DHECDISA Yes 78
D.V.CF Vent Reheat Setpt Select 0-1(multi-text strings) DHVHTCFG 0 78
D.V.RA Vent Reheat RAT offset 0-8 ^F DHVRAOFF 0 78
D.V.HT Vent Reheat Setpoint 55-95 dF DHVHT_SP 70 78
D.C.SP Dehumidify Cool Setpoint 40-55 dF DHCOOLSP 45 78
D.RH.S Dehumidify RH Setpoint 10-90 % DHRELHSP 55 78
CCN CCN CONFIGURATION
CCNA CCN Address 1 - 239 CCNADD 1 79,80
CCNB CCN Bus Number 0 - 239 CCNBUS 0 79,80
BAUD CCN Baud Rate 1 - 5 (multi-text strings) CCNBAUDD 3 79,80
BROD CCN BROADCST DEFINITIONS
BRODTM.DT CCN Time/Date Broadcast ON/OFF CCNBC On 79,80
BRODOAT.B CCN OAT Broadcast ON/OFF OATBC Off 79,80
BRODORH.B CCN OARH Broadcast ON/OFF OARHBC Off 79,80
BRODOAQ.B CCN OAQ Broadcast ON/OFF OAQBC Off 79,80
BRODG.S.B Global Schedule Broadcst ON/OFF GSBC Off 79,80
BRODB.ACK CCN Broadcast Ack'er ON/OFF CCNBCACK Off 79,80
SC.OV CCN SCHEDULES-OVERRIDES
SC.OVSCH.N Schedule Number 0 - 99 SCHEDNUM 1 79,80
SC.OVHOL.T Accept Global Holidays? YES/NO HOLIDAYT No 79,80
SC.OVO.T.L. Override Time Limit 0 - 4 HRS OTL 1 79,80
SC.OVOV.EX Timed Override Hours 0 - 4 HRS OVR_EXT 0 79,80
SC.OVSPT.O SPT Override Enabled ? YES/NO SPT_OVER Yes 79,80
SC.OVT58.O T58 Override Enabled ? YES/NO T58_OVER Yes 79,80
SC.OVGL.OV Global Sched. Override ? YES/NO GLBLOVER No 79,80
ALLM ALERT LIMIT CONFIG.
SP.L.O SPT lo alert limit/occ -10-245 dF SPLO 60 80,81
SP.H.O SPT hi alert limit/occ -10-245 dF SPHO 85 80,81
SP.L.U SPT lo alert limit/unocc -10-245 dF SPLU 45 80,81
SP.H.U SPT hi alert limit/unocc -10-245 dF SPHU 100 80,81
SA.L.O EDT lo alert limit/occ -40-245 dF SALO 40 80,81
SA.H.O EDT hi alert limit/occ -40-245 dF SAHO 100 80,81
SA.L.U EDT lo alert limit/unocc -40-245 dF SALU 40 80,81
SA.H.U EDT hi alert limit/unocc -40-245 dF SAHU 100 80,81
RA.L.O RAT lo alert limit/occ -40-245 dF RALO 60 80,81
RA.H.O RAT hi alert limit/occ -40-245 dF RAHO 90 80,81
RA.L.U RAT lo alert limit/unocc -40-245 dF RALU 40 80,81
RA.H.U RAT hi alert limit/unocc -40-245 dF RAHU 100 80,81
OAT.L OAT lo alert limit -40-245 dF OATL -40 80,81
OAT.H OAT hi alert limit -40-245 dF OATH 150 80,81
R.RH.L RARH low alert limit 0-100 % RRHL 0 80,81
R.RH.H RARH high alert limit 0-100 % RRHH 100 80,81
O.RH.L OARH low alert limit 0-100 % ORHL 0 80,81
O.RH.H OARH high alert limit 0-100 % ORHH 100 80,81
SP.L SP low alert limit 0-5 "H2O SPL 0 80,81
SP.H SP high alert limit 0-5 "H2O SPH 2 81
BP.L BP lo alert limit -0.25-0.25 "H2O BPL -0.25 81
BP.H BP high alert limit -0.25-0.25 "H2O BPH 0.25 81
IAQ.H IAQ high alert limit 0-5000 IAQH 1200 81
TRIM SENSOR TRIM CONFIG.
SAT.T Air Temp Lvg SF Trim -10 - 10 ^F SAT_TRIM 0 81,82
RAT.T RAT Trim -10 - 10 ^F RAT_TRIM 0 81,82
OAT.T OAT Trim -10 - 10 ^F OAT_TRIM 0 81,82
SPT.T SPT Trim -10 - 10 ^F SPT_TRIM 0 81,82
L.SW.T Limit Switch Trim -10 - 10 ^F LSW_TRIM 0 81,82
CCT.T Air Temp Lvg Evap Trim -10 - 10 ^F CCT_TRIM 0 81,82
SP.A.T Suct.Press.Circ.A Trim -50 - 50 PSIG SPA_TRIM 0 81,82
SP.B.T Suct.Press.Circ.B Trim -50 - 50 PSIG SPB_TRIM 0 81,82
DP.A.T Dis.Press.Circ.A Trim -50 - 50 PSIG DPA_TRIM 0 81,82
DP.B.T Dis.Press.Circ.B Trim -50 - 50 PSIG DPB_TRIM 0 81,82
SW.LG SWITCH LOGIC: NO / NC
FTS.L Filter Status Inpt-Clean Open/Close FLTSLOGC Open 82
IGC.L IGC Feedback - Off Open/Close GASFANLG Open 82
RMI.L RemSw Off-Unoc-Strt-NoOv Open/Close RMTINLOG Open 82
ENT.L Enthalpy Input - Low Open/Close ENTHLOGC Close 82
SFS.L Fan Status Sw. - Off Open/Close SFSLOGIC Open 82
DL1.L Dmd.Lmt.Sw.1 - Off Open/Close DMD_SW1L Open 82
DL2.L Dmd.Lmt.Sw.2 - Off Open/Close DMD_SW2L Open 82
IAQ.L IAQ Disc.Input - Low Open/Close IAQINLOG Open 82
FSD.L Fire Shutdown - Off Open/Close FSDLOGIC Open 82
PRS.L Pressurization Sw. - Off Open/Close PRESLOGC Open 82
EVC.L Evacuation Sw. - Off Open/Close EVACLOGC Open 82
PRG.L Smoke Purge Sw. - Off Open/Close PURGLOGC Open 82
DH.LG Dehumidify Sw. - Off Open/Close DHDISCLG Open 82
DISP DISPLAY CONFIGURATION
TEST Test Display LEDs ON/OFF TEST Off 82,83
METR Metric Display ON/OFF DISPUNIT Off 82,83
LANG Language Selection 0 - 1 (multi-text strings) LANGUAGE 0 82,83
PAS.E Password Enable ENABLE/DISABLE PASS_EBL Enable 82,83
PASS Service Password 0000 - 9999 PASSWORD 1111 82,83