APPENDIX A — LOCAL DISPLAY TABLES

MODE — RUN STATUS

ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS PAGE NO.
VIEW AUTO VIEW OF RUN STATUS
HVAC ascii string spelling out the hvac modes string 90,92
OCC Occupied ? YES/NO OCCUPIED forcible 90,92
MAT Mixed Air Temperature dF MAT 90,92
EDT Evaporator Discharge Tmp dF EDT 90,92
LAT Leaving Air Temperature dF LAT 90,92
EC.C.P Economizer Control Point dF ECONCPNT 90,92
ECN.P Economizer Act.Curr.Pos. 0-100 % ECONOPOS 90,92
EC2.P Economzr Act.Curr.Pos. 0-100 % ECON2POS 90,92
CL.C.P Cooling Control Point dF COOLCPNT 90,92
C.CAP Current Running Capacity CAPTOTAL 90,92
CL.ST Requested Cool Stage CL_STAGE 90,92
HT.C.P Heating Control Point dF HEATCPNT 90,92
HT.ST Requested Heat Stage HT_STAGE 90,92
H.MAX Maximum Heat Stages HTMAXSTG 90,92
ECON ECONOMIZER RUN STATUS
ECN.P Economizer Act.Curr.Pos. 0-100 % ECONOPOS 69,93
EC2.P Economzr 2 Act.Curr.Pos. 0-100 % ECON2POS 69,93
ECN.C Economizer Act.Cmd.Pos. 0-100 % ECONOCMD forcible 69,93
ACTV Economizer Active ? YES/NO ECACTIVE 69,93
DISA ECON DISABLING CONDITIONS
DISAUNV.1 Econ Act. Unavailable? YES/NO ECONUNAV 69,93
DISAUNV.2 Econ2 Act. Unavailable? YES/NO ECN2UNAV 69,93
DISAENTH Enth. Switch Read High ? YES/NO ENTH 69,93
DISADBC DBC - OAT Lockout? YES/NO DBC_STAT 69,93
DISADEW DEW - OA Dewpt.Lockout? YES/NO DEW_STAT 69,93
DISADDBC DDBD- OAT > RAT Lockout? YES/NO DDBCSTAT 69,93
DISAOAEC OAEC- OA Enth Lockout? YES/NO OAECSTAT 69,93
DISADEC DEC - Diff.Enth.Lockout? YES/NO DEC_STAT 69,93
DISAEDT EDT Sensor Bad? YES/NO EDT_STAT 69,93
DISAOAT OAT Sensor Bad ? YES/NO OAT_STAT 69,93
DISAFORC Economizer Forced ? YES/NO ECONFORC 69,93
DISASFON Supply Fan Not On 30s ? YES/NO SFONSTAT 69,93
DISACLOF Cool Mode Not In Effect? YES/NO COOL_OFF 69,93
DISAOAQL OAQ Lockout in Effect ? YES/NO OAQLOCKD 69,93
DISAHELD Econ Recovery Hold Off? YES/NO ECONHELD 69,93
DISADH.DS Dehumid. Disabled Econ.? YES/NO DHDISABL 69,93
O.AIR OUTSIDE AIR INFORMATION 69,93
O.AIROAT Outside Air Temperature dF OAT forcible 69,93
O.AIROA.RH Outside Air Rel. Humidity % OARH forcible 69,93
O.AIROA.E Outside Air Enthalpy OAE 69,93
O.AIROA.D.T OutsideAir Dewpoint Temp dF OADEWTMP 69,93
COOL COOLING INFORMATION
C.CAP Current Running Capacity % CAPTOTAL 92,93
CUR.S Current Cool Stage COOL_STG 92,93
REQ.S Requested Cool Stage CL_STAGE 92,93
MAX.S Maximum Cool Stages CLMAXSTG 92,93
DEM.L Active Demand Limit % DEM_LIM forcible 92,93
SUMZ COOL CAP. STAGE CONTROL
SUMZSMZ Capacity Load Factor -100 +100 SMZ 92,93
SUMZADD.R Next Stage EDT Decrease ^F ADDRISE 92,93
SUMZSUB.R Next Stage EDT Increase ^F SUBRISE 92,93
SUMZR.PCT Rise Per Percent Capacity RISE_PCT 92,93
SUMZY.M I N Cap Deadband Subtracting Y_MINUS 92,93
SUMZY.P L U Cap Deadband Adding Y_PLUS 92,93
SUMZZ.MIN Cap Threshold Subtracting Z_MINUS 92,93
SUMZZ.PLU Cap Threshold Adding Z_PLUS 92,93
SUMZH.TMP High Temp Cap Override HI_TEMP 92,93
SUMZL.TMP Low Temp Cap Override LOW_TEMP 92,93
SUMZPULL Pull Down Cap Override PULLDOWN 92,93
SUMZSLOW Slow Change Cap Override SLO_CHNG 92,93
TRIP MODE TRIP HELPER
UN.C.S Unoccup. Cool Mode Start UCCLSTRT 93
UN.C.E Unoccup. Cool Mode End UCCL_END 93
OC.C.S Occupied Cool Mode Start OCCLSTRT 93
OC.C.E Occupied Cool Mode End OCCL_END 93
TEMP Ctl.Temp RAT,SPT or Zone CTRLTEMP 93
OC.H.E Occupied Heat Mode End OCHT_END 93
OC.H.S Occupied Heat Mode Start OCHTSTRT 93
UN.H.E Unoccup. Heat Mode End UCHT_END 93
UN.H.S Unoccup. Heat Mode Start UCHTSTRT 93
HVAC ascii string spelling out the hvac modes string 93
LINK CCN - LINKAGE
MODE Linkage Active - CCN ON/OFF MODELINK 94
L.Z.T Linkage Zone Control Tmp dF LZT 94
L.C.SP Linkage Curr. Cool Setpt dF LCSP 94
L.H.SP Linkage Curr. Heat Setpt dF LHSP 94
HRS COMPRESSOR RUN HOURS
HR.A1 Compressor A1 Run Hours 0-999999 HRS HOURS_A1 config 94
HR.A2 Compressor A2 Run Hours 0-999999 HRS HOURS_A2 config 94
HR.B1 Compressor B1 Run Hours 0-999999 HRS HOURS_B1 config 94
HR.B2 Compressor B2 Run Hours 0-999999 HRS HOURS_B2 config 94
STRT COMPRESSOR STARTS
ST.A1 Compressor A1 Starts 0-999999 CY_A1 config 94
ST.A2 Compressor A2 Starts 0-999999 CY_A2 config 94
ST.B1 Compressor B1 Starts 0-999999 CY_B1 config 94
ST.B2 Compressor B2 Starts 0-999999 CY_B2 config 94
VERS SOFTWARE VERSION NUMBERS
MBB CESR131292-xx-xx string 94
RCB CESR131249-xx-xx string 94
ECB CESR131249-xx-xx string 94
SCB CESR131226-xx-xx string 94
CEM CESR131174-xx-xx string 94
ECON xx-xx-xxx-xxx-xx string 94
IGV xx-xx-xxx-xxx-xx string 94
HUMD xx-xx-xxx-xxx-xx string 94
HEAT xx-xx-xxx-xxx-xx string 94
BP1 xx-xx-xxx-xxx-xx string 94
BP2 xx-xx-xxx-xxx-xx string 94
MARQ CESR131171-xx-xx string 94
NAVI CESR130227-xx-xx string 94