CL-3
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
ITEM EXPANSION RANGE DEFAULT SETTING
ECON ECONOMIZER CONFIGURATION
→EC.EN Economizer Installed? Yes/No Yes
→EC2.E Econ.Act.2 Installed? Yes/No No
→EC.MN Economizer Min.Position 0 - 100% 5
→EC.MX Economizer Max.Position 0 - 100% 98
→E.TRM Economzr Trim For SumZ ? Yes/No Yes
→E.SEL Econ ChangeOver Select 0 - 3 (multi-text strings) 0
→OA.E.C OA Enthalpy ChgOvr Selct 1 - 5 (multi-text strings) 4
→OA.EN Outdr.Enth Compare Value 18 - 28 24
→OAT.L High OAT Lockout Temp -40 - 120 dF 60
→O.DEW OA Dewpoint Temp Limit 50 - 62 dF 55
→ORH.S Outside Air RH Sensor Enable/Disable Disable
→CFM.C OUTDOOR AIR CFM CONTROL
→CFM.C→OCF.S Outdoor Air CFM Sensor Enable/Disable Disable
→CFM.C→O.C.MX Economizer Min.Flow 0 - 20000 CFM 2000
→CFM.C→O.C.MN IAQ Demand Vent Min.Flow 0 - 20000 CFM 0
→CFM.C→O.C.DB Econ.Min.Flow Deadband 200 - 1000 CFM 400
→E.CFG ECON.OPERATION CONFIGS
→E.CFG→E.P.GN Economizer Prop.Gain 0.7 - 3.0 1
→E.CFG→E.RNG Economizer Range Adjust 0.5 - 5 ^F 2.5
→E.CFG→E.SPD Economizer Speed Adjust 0.1 - 10 0.75
→E.CFG→E.DBD Economizer Deadband 0.1 - 2 ^F 0.5
→UEFC UNOCC.ECON.FREE COOLING
→UEFC→FC.CF Unoc Econ Free Cool Cfg 0-2 (multi-text strings) 0
→UEFC→FC.TM Unoc Econ Free Cool Time 0 - 720 min 120
→UEFC→FC.L.O Un.Ec.Free Cool OAT Lock 40 - 70 dF 50
→ACT.C ECON.ACTUATOR CONFIGS
→ACTC→SN.1.1 Econ Serial Number 1 0 - 255 0
→ACTC→SN.1.2 Econ Serial Number 2 0 - 255 0
→ACTC→SN.1.3 Econ Serial Number 3 0 - 255 0
→ACTC→SN.1.4 Econ Serial Number 4 0 - 255 0
→ACTC→SN.1.5 Econ Serial Number 5 0 - 255 0
→ACTC→C.A.L1 Econ Ctrl Angle Lo Limit 0 - 90 85
→ACTC→SN.2.1 Econ 2 Serial Number 1 0 - 255 0
→ACTC→SN.2.2 Econ 2 Serial Number 2 0 - 255 0
→ACTC→SN.2.3 Econ 2 Serial Number 3 0 - 255 0
→ACTC→SN.2.4 Econ 2 Serial Number 4 0 - 255 0
→ACTC→SN.2.5 Econ 2 Serial Number 5 0 - 255 0
→ACTC→C.A.L2 Econ 2 Ctrl Angle Lo Limit 0 - 90 85
BP BUILDING PRESS. CONFIGS
→BP.CF Building Press. Config 0 - 5 (multi-text strings) 0
→BP.S Building Pressure Sensor Enable/Disable Disable
→BP.R Bldg. Press. (+/-) Range 0.10 - 0.25 "H2O 0.25
→BP.SP Building Pressure Setp. -0.25 - 0.25 "H2O 0.05
→BP.SO BP Setpoint Offset 0 - 0.5 "H2O 0.05
→BP.P1 Power Exhaust On Setp.1 0 - 100% 25
→BP.P2 Power Exhaust On Setp.2 0 - 100% 75
→B.V.A VFD/ACTUATOR CONFIG
→B.V.A→BP.FS VFD/Act. Fire Speed/Pos. 0 - 100% 100
→B.V.A→BP.MN VFD/Act. Min.Speed/Pos. 0 - 50% 0
→B.V.A→BP.MX VFD Maximum Speed 50 - 100% 100
→B.V.A→BP.1M BP 1 Actuator Max Pos. 85 - 100% 100
→B.V.A→BP.2M BP 2 Actuator Max Pos. 85 - 100% 100
→B.V.A→BP.CL BP Hi Cap VFD Clamp Val. 5 - 25% 10