144
APPENDIX B — CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
TEMPS
Air Temp Lvg Supply Fan dF SAT
Return Air Temperature dF RAT forcible
Outside Air Temperature dF OAT forcible
Space Temperature dF SPT forcible
Space Temperature Offset ^F SPTO forcible
Staged Gas LAT Sum dF LAT_SGAS
Staged Gas LAT 1 dF LAT1SGAS
Staged Gas LAT 2 dF LAT2SGAS
Staged Gas LAT 3 dF LAT23SGAS
Staged Gas Limit Sw.Temp dF LIMSWTMP
Air Temp Lvg Evap Coil dF CCT
Cir A Sat.Condensing Tmp dF SCTA
Cir B Sat.Condensing Tmp dF SCTB
Cir A Sat.Suction Temp. dF SSTA
Cir B Sat.Suction Temp. dF SSTB
TSTAT
Control Mode………..: ascii text strings
Thermostat Y1 Input On/Off Y1 forcible
Thermostat Y2 Input On/Off Y2 forcible
Thermostat W1 Input On/Off W1 forcible
Thermostat W2 Input On/Off W2 forcible
Thermostat G Input On/Off G forcible
UINPUTS
Filter Status Input Dirty/Clean FLTS forcible
Fan request from IGC On/Off IGCFAN
Fire Shutdown Input Alarm/Normal FSD forcible
Thermostat G Input On/Off G forcible
Thermostat W2 Input On/Off W2 forcible
Thermostat W1 Input On/Off W1 forcible
Thermostat Y2 Input On/Off Y2 forcible
Thermostat Y1 Input On/Off Y1 forcible
Remote Input State On/Off RMTIN forcible
Enth. Switch Read High ? Yes/No ENTH forcible
Supply Fan Status Switch On/Off SFS forcible
Circ A High Press.Switch On/Off CIRCAHPS
Circ B High Press.Switch On/Off CIRCBHPS
Freeze Status Switch Alarm/Normal FRZ forcible
Plenum Press.Safety Sw. High/Low PPS forcible
Demand Limit Switch 1 On/Off DMD_SW1 forcible
Demand Limit Switch 2 On/Off DMD_SW2 forcible
Pressurization Input Alarm/Normal PRES forcible
Evacuation Input Alarm/Normal EVAC forcible
Smoke Purge Input Alarm/Normal PURG forcible
IAQ - Discrete Input High/Low IAQIN forcible
Dehumidify Switch Input On/Off DHDISCIN forcible
UOUTPUTS
FANS
Supply Fan Relay On/Off SFAN
Supply Fan VFD Speed 0-100 % SFAN_VFD
Supply Fan Request Yes/No SFANFORC forcible
Exhaust Fan VFD Speed 0-100 % EFAN_VFD
Power Exhaust Relay 1 On/Off PE1
Power Exhaust Relay 2 On/Off PE2
Condenser Fan Circuit A On/Off CONDFANA
Condenser Fan Circuit B On/Off CONDFANB
MotorMaster Condensr Fan On/Off PULSCFAB
COOLING
Compressor A1 Relay On/Off CMPA1
Unloader 1 - Comp A1 On/Off UNL_1_A1
Unloader 2 - Comp A1 On/Off UNL_2_A1
Compressor A2 Relay On/Off CMPA2
Compressor B1 Relay On/Off CMPB1
Unloader 1 - Comp B1 On/Off UNL_1_B1
Unloader 2 - Comp B1 On/Off UNL_2_B1
Compressor B2 Relay On/Off CMPB2
HEATING
Heat Relay 1 On/Off HS1
Heat Relay 2 On/Off HS2
Relay 3 W1 Gas Valve 2 On/Off HS3
Relay 4 W2 Gas Valve 2 On/Off HS4
Relay 5 W1 Gas Valve 3 On/Off HS5
Relay 6 W2 Gas Valve 3 On/Off HS6
Heat Interlock Relay On/Off HIR forcible
ACTUATORS
Economizer Act.Curr.Pos. 0-100 % ECONOPOS
Economzr 2 Act.Curr.Pos. 0-100 % ECON2POS
Economizer Act.Cmd.Pos. 0-100 % ECONOCMD forcible
IGV Actuator Current Pos 0-100 % IGV_RPOS
IGV Actuator Command Pos 0-100 % IGV_CPOS
Humidifer Act.Curr.Pos. 0-100 % HUMDRPOS
Humidifier Command Pos. 0-100 % HUMDCPOS
Ht.Coil Act.Current Pos. 0-100 % HTCLRPOS
Ht.Coil Command Position 0-100 % HTCLCPOS
BP 1 Actuator Curr.Pos. 0-100 % BP1_RPOS
BP 1 Command Position 0-100 % BP1_CPOS
BP 2 Actuator Curr.Pos. 0-100 % BP2_RPOS
BP 2 Command Position 0-100 % BP2_CPOS
GENERAL OUTPUTS
Humidifier Relay On/Off HUMIDRLY
Remote Alarm / Aux Relay On/Off ALRM forcible