154
APPENDIX B — CCN TABLES (cont)
MAINTENANCE DISPLAY TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
PRESBLDG
Building Pressure "H2O BP
Return Air CFM CFM RACFM
Supply Air CFM CFM SACFM
Power Exhaust Relay 1 On/Off PE1
Power Exhaust Relay 2 On/Off PE2
BP 1 Actuator Curr.Pos. % BP1_RPOS
BP 1 Command Position % BP1_CPOS
BP 2 Actuator Curr.Pos. % BP2_RPOS
BP 2 Command Position % BP2_CPOS
Exhaust Fan VFD Speed % EFAN_VFD
Building Pressure Setp. "H2O BPSP config
BP Setpoint Offset ^"H2O BPSO config
Fan Track Learn Enable Yes/No DCFM_CFG config
Fan Track Learn Rate min DCFMRATE config
Fan Track Initial DCFM CFM DCFMSTRT config
Fan Track Max Clamp CFM DCFM_MAX config
Fan Track Max Correction CFM DCFM_ADJ config
Fan Track Internl EEPROM CFM DCFM_OFF config
Fan Track Reset Internal DCFMRSET config
Fan Track Internal RAM CFM DCFM_RAM
Fan Track Control D.CFM CFM DELTACFM
PRESDUCT
Static Pressure "H2O SP
Supply Fan VFD Speed % SFAN_VFD
IGV Actuator Current Pos % IGV_RPOS
IGV Actuator Command Pos % IGV_CPOS
Static Pressure Setpoint "H2O SPSP config
Static Pressure Reset SPRESET forcible
STAGEGAS
Heating Mode………..: ascii text strings
Requested Heat Stage HT_STAGE
Heating Control Point HEATCPNT
Staged Gas LAT Sum dF LAT_SGAS
Staged Gas LAT 1 dF LAT1SGAS
Staged Gas LAT 2 dF LAT2SGAS
Staged Gas LAT 3 dF LAT3SGAS
Staged Gas Limit Sw.Temp dF LIMSWTMP
Heat PID Timer sec HTSGTIMR
Staged Gas Capacity Calc % HTSGCALC
Current Running Capacity % HTSG_CAP
Proportional Cap. Change HTSG_P
Derivative Cap. Change HTSG_D
Maximum Heat Stages HTMAXSTG
Hi Limit Switch Tmp Mode LIMTMODE
LAT Cutoff Mode LATCMODE
Capacity Clamp Mode CAPMODE
STRTHOUR
Compressor A1 Run Hours hours HR_A1 config
Compressor A2 Run Hours hours HR_A2 config
Compressor B1 Run Hours hours HR_B1 config
Compressor B2 Run Hours hours HR_B2 config
Compressor A1 Starts CY_A1 config
Compressor A2 Starts CY_A2 config
Compressor B1 Starts CY_B1 config
Compressor B2 Starts CY_B2 config
SUMZ
Cooling Control Point dF COOLCPNT
Mixed Air Temperature dF MAT
Evaporator Discharge Tmp dF EDT
Return Air Temperature dF RAT forcible
Outside Air Temperature dF OAT forcible
Econo Damper Current Pos % ECONOPOS
Economzr 2 Act.Curr.Pos. % ECON2POS
Capacity Threshold Adjst Z_GAIN config
Capacity Load Factor SMZ
Next Stage EDT Decrease ADDRISE
Next Stage EDT Increase SUBRISE
Rise Per Percent Capacity RISE_PCT
Cap Deadband Subtracting Y_MINUS
Cap Deadband Adding Y_PLUS
Cap Threshold Subtracting Z_MINUS
Cap Threshold Adding Z_PLUS
High Temp Cap Override On/Off HI_TEMP
Low Temp Cap Override On/Off LOW_TEMP
Pull Down Cap Override On/Off PULLDOWN
Slow Change Cap Override On/Off SLO_CHNG