135
APPENDIX A — LOCAL DISPLAY TABLES (cont)

MODE — TEMPERATURES

MODE — PRESSURES

MODE — SETPOINTS

ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS
AIR.T AIR TEMPERATURES
CTRL CONTROL TEMPS
CTRLEDT Evaporator Discharge Tmp dF EDT
CTRLLAT Leaving Air Temperature dF LAT
CTRLMAT Mixed Air Temperature dF MAT
CTRLR.TMP Controlling Return Temp dF RETURN_T forcible
CTRLS.TMP Controlling Space Temp dF SPACE_T forcible
SAT Air Tmp Lvg Supply Fan dF SAT
OAT Outside Air Temperature -40 - 240 dF OAT forcible
RAT Return Air Temperature dF RAT forcible
SPT Space Temperature -40 - 240 dF SPT forcible
SPTO Space Temperature Offset ^F SPTO forcible
CCT Air Temp Lvg Evap Coil dF CCT
S.G.LS Staged Gas LAT Sum dF LAT_SGAS
S.G.L1 Staged Gas LAT 1 dF LAT1SGAS
S.G.L2 Staged Gas LAT 2 dF LAT2SGAS
S.G.L3 Staged Gas LAT 3 dF LAT3SGAS
S.G.LM Staged Gas Limit Sw.Temp dF LIMSWTMP
REF.T REFRIGERANT TEMPERATURES
SCT.A Cir A Sat.Condensing Tmp dF SCTA
SST.A Cir A Sat.Suction Temp. dF SSTA
SCT.B Cir B Sat.Condensing Tmp dF SCTB
SST.B Cir B Sat.Suction Temp. dF SSTB
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS
AIR.P AIR PRESSURES
SP Static Pressure "H2O SP
BP Building Pressure "H2O BP
REF.P REFRIGERANT PRESSURES
DP.A Cir A Discharge Pressure PSIG DP_A
SP.A Cir A Suction Pressure PSIG SP_A
DP.B Cir B Discharge Pressure PSIG DP_B
SP.B Cit B Suction Pressure PSIG SP_B
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT
OHSP Occupied Heat Setpoint 40-99 dF OHSP 68
OCSP Occupied Cool Setpoint 40-99 dF OCSP 75
UHSP Unoccupied Heat Setpoint 40-99 dF UHSP 55
UCSP Unoccupied Cool Setpoint 40-110 dF UCSP 90
GAP Heat-Cool Setpoint Gap 2-10 deltaF HCSP_GAP 5
V. C . O N VAV Occ. Cool On Delta 0-25 deltaF VAVOCON 3.5
V. C . O F VAV Occ. Cool Off Delta 1-25 deltaF VAVOCOFF 2
SASP Supply Air Setpoint 45-75 dF SASP 55
SA.HI Supply Air Setpoint Hi 45-75 dF SASP_HI 55
SA.LO Supply Air Setpoint Lo 45-75 dF SASP_LO 60
SA.HT Heating Supply Air Setpt 80-120 dF SASPHEAT 85
T.PRG Tempering Purge SASP -20-80 dF TEMPPURG 50
T.CL Tempering in Cool SASP 5-75 dF TEMPCOOL 5
T.V.OC Tempering Vent Occ SASP -20-80 dF TEMPVOCC 65
T.V.UN Tempering Vent Unocc. SASP -20-80 dF TEMPVUNC 50