146
APPENDIX B — CCN TABLES (cont)

CONFIG TABLES (cont)

SERVICE-CONFIG TABLES

TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
SCHEDOVR
Schedule Number 0-99 SCHEDNUM 0
Accept Global Holidays? Yes/No HOLIDAYT No
Override Time Limit 0-4 hours OTL 1
Timed Override Hours 0-4 hours OVR_EXT 0
Accepting an Override:
SPT Override Enabled ? Yes/No SPT_OVER Yes
T58 Override Enabled ? Yes/No T58_OVER Yes
Allowed to Broadcast a
Global Sched. Override ? Yes/No GLBLOVER No
SET_PNT
Occupied Heat Setpoint 55-80 dF OHSP 68
Occupied Cool Setpoint 55-80 dF OCSP 75
Unoccupied Heat Setpoint 40-80 dF UHSP 55
Unoccupied Cool Setpoint 75-95 dF UCSP 90
Heat-Cool Setpoint Gap 2-10 deltaF HCSP_GAP 5
VAV Occ. Cool On Delta 0-25 deltaF VAVOCON 3.5
VAV Occ. Cool Off Delta 1-25 deltaF VAVOCOFF 2
Supply Air Setpoint 45-75 dF SASP 55
Supply Air Setpoint Hi 45-75 dF SASP_HI 55
Supply Air Setpoint Lo 45-75 dF SASP_LO 60
Heating Supply Air Setpt 90-145 dF SASPHEAT 85
Tempering Purge SASP -20-80 dF TEMPPURG 50
Tempering in Cool SASP 5-75 dF TEMPCOOL 5
Tempering in Vent Occ SASP -20-80 dF TEMPVOCC 65
Tempering Vent Unocc. SASP -20-80 dF TEMPVUNC 50
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
ALLM
SPT lo alert limit/occ -10-245 dF SPLO 60
SPT hi alert limit/occ -10-245 dF SPHO 85
SPT lo alert limit/unocc -10-245 dF SPLU 45
SPT hi alert limit/unocc -10-245 dF SPHU 100
EDT lo alert limit/occ -40-245 dF SALO 40
EDT hi alert limit/occ -40-245 dF SAHO 100
EDT lo alert limit/unocc -40-245 dF SALU 40
EDT hi alert limit/unocc -40-245 dF SAHU 100
RAT lo alert limit/occ -40-245 dF RALO 60
RAT hi alert limit/occ -40-245 dF RAHO 90
RAT lo alert limit/unocc -40-245 dF RALU 40
RAT hi alert limit/unocc -40-245 dF RAHU 100
OAT lo alert limit -40-245 dF OATL -40
OAT hi alert limit -40-245 dF OATH 150
RARH low alert limit 0-100 % RRHL 0
RARH high alert limit 0-100 % RRHH 100
OARH low alert limit 0-100 % ORHL 0
OARH high alert limit 0-100 % ORHH 100
SP low alert limit 0-5 "H2O SPL 0
SP high alert limit 0-5 "H2O SPH 2
BP lo alert limit -0.25-0.25 "H2O BPL -0.25
BP high alert limit -0.25-0.25 "H2O BPH 0.25
IAQ high alert limit 0-5000 IAQH 1200
BP__
Building Press. Config 0-5 BLDG_CFG 0
Building Pressure Sensor Enable/Disable BPSENS Disable
Bldg. Press. (+/-) Range 0.10 - 0.25 "H2O BP_RANGE 0.25
Building Pressure Setp. -0.25 - 0.25 "H2O BPSP 0.05
BP Setpoint Offset 0 - 0.5 ^"H2O BPSO 0.05
Power Exhaust On Setp.1 0 - 100 % PES1 25
Power Exhaust On Setp.2 0 - 100 % PES2 75
Bldg.Pressure Fire Speed 0 - 100 % BLDGPFSO 100
Bldg.Pressure Min. Speed 0 - 100 % BLDGPMIN 10
Bldg.Pressure Max. Speed 0 - 100 % BLDGPMAX 100
BP 1 Actuator Max Pos. 85 - 100 % BP1SETMX 100
BP 2 Actuator Max Pos. 85 - 100 % BP2SETMX 100
BP Hi Cap VFD Clamp Val. 5 - 25 % BLDGCLMP 10
BP Hi Cap VFD Clamp Time 30 - 255 sec BLDGWAIT 60
Fan Track Learn Enable Yes/No DCFM_CFG NO
Fan Track Learn Rate 5-60 min DCFMRATE 15
Fan Track Initial DCFM -20000 - 20000 CFM DCFMSTRT 2000
Fan Track Max Clamp 0 - 20000 CFM DCFM_MAX 4000
Fan Track Max Correction 0 -20000 CFM DCFM_ADJ 1000
Fan Track Internl EEPROM -20000 - 20000 CFM DCFM_OFF 0
Fan Track Internal RAM -20000 - 20000 CFM DCFM_RAM 0
Fan Track Reset Internal Yes/No DCFMRSET No
Supply Air CFM Config 1 - 2 (multi-text strings) SCFM_CFG 1