APPENDIX B — CCN TABLES (cont)
MAINTENANCE DISPLAY TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
COMPRESR (cont)
Enable Compressor B1 Enable/Disable CMPB1ENA config
Compressor B2 Relay On/Off CMPB2
Compressor B2 Feedback On/Off CSB_B2
Curr.Sens.Brd. B2 Status ascii CSBB2ASC
CSB B2 Feedback Alarm Enable/Disable CSB_B2EN config
Comp B2 Locked Out ? Yes/No CMPB2LOK
Compressor B2 Strikes CMPB2STR
Enable Compressor B2 Enable/Disable CMPB2ENA config
COMPTRIP
Comp. Security Password 0-10000 COMPPASS config
Low SP Circ.A Trip 48.0 LSPATRIP config
Low SP Circ.B Trip 48.0 LSPBTRIP config
MOP 1/3 Lo SP Trip 28.0 PSIG SP13L_T config
MOP 1/3 Lo DP Trip 242.7 PSIG DP13L_T config
MOP 1/3 Hi SP Trip 75.0 PSIG SP13H_T config
MOP 1/3 Hi DP Trip 430.0 PSIG DP13H_T config
MOP 1/3 Mm DP Trip 3.985 DP13Mm_T config
MOP 1/3 Mb DP Tr 131.117 DP13Mb_T config
MOP 1/2 Lo SP Trip 28.0 PSIG SP12L_T config
MOP 1/2 Lo DP Trip 242.7 PSIG DP12L_T config
MOP 1/2 Hi SP Trip 61.5 PSIG SP12H_T config
MOP 1/2 Hi DP Trip 430.0 PSIG DP12H_T config
MOP 1/2 Mm DP Trip 5.591 DP12Mm_T config
MOP 1/2 Mb DP Trp 156.55 DP12Mb_T config
MOP 2/3 Lo SP Trip 28.0 PSIG SP23L_T config
MOP 2/3 Lo DP Trip 316.2 PSIG DP23L_T config
MOP 2/3 Hi SP Trip 57.4 PSIG SP23H_T config
MOP 2/3 Hi DP Trip 430.0 PSIG DP23H_T config
MOP 2/3 Mm DP Trip 3.871 DP23Mm_T config
MOP 2/3 Mb DP Trp 207.82 DP23Mb_T config
MOP Ful Lo SP Trip 28.0 PSIG SPFLL_T config
MOP Ful Lo DP Trip 340.0 PSIG DPFLL_T config
MOP Ful Hi SP Trip 52.4 PSIG SPFLH_T config
MOP Ful Hi DP Trip 430.0 PSIG DPFLH_T config
MOP Ful Mm DP Trip 3.689 DPFLMm_T config
MOP Ful Mb DP Trp 103.28 DPFLMb_T config
DMANDLIM
Active Demand Limit 0-100 % DEM_LIM forcible
Percent Total Capacity 0-100 % CAPTOTAL
Demand Limit Select 0-3 DMD_CTRL config
Demand Limit Switch 1 On/Off DMD_SW1 forcible
Demand Limit Switch 2 On/Off DMD_SW2 forcible
Demand Limit Sw.1 Setpt. 0-100 % DLSWSP1 config
Demand Limit Sw.2 Setpt. 0-100 % DLSWSP2 config
4-20 ma Demand Signal 4-20 ma DMDLMTMA forcible
Demand Limit at 20 ma 0-100 % DMT20MA config
CCN Loadshed Signal 0-99 DL_STAT
Loadshed Group Number 0-99 SHED_NUM config
Loadshed Demand Delta 0-60 % SHED_DEL config
Maximum Loadshed Time 0-120 min SHED_TIM config
ECON_MIN
Economizer Act.Cmd.Pos. % ECONOCMD forcible
Economizer Act.Curr.Pos. % ECONOPOS
Economzr 2 Act.Curr.Pos. % ECON2POS
Econo Current Min. Pos. % ECMINPOS
Econo Current Min. CFM CFM ECMINCFM
Outside Air CFM CFM OACFM
Diff.Air Quality in PPM DAQ
IAQ Min.Pos.Override % IAQMINOV forcible
Econ Remote 10K Pot Val. ECON_POT forcible
IAQ - PPM Return CO2 IAQ forcible
OAQ - PPM Return CO2 OAQ forcible
IAQ - Discrete Input IAQIN forcible
IAQ Demand Vent Min.Pos. % IAQMINP config
Economizer Min.Position % ECONOMIN config
IAQ Demand Vent Min.Flow CFM OACFMMIN config
Economizer Min.Flow CFM OACFMMAX config
Econ OACFM MinPos Deadbd CFM OACFM_DB config
IAQ Analog Sensor Config IAQANCFG config
IAQ 4-20 ma Fan Config IAQANFAN config
IAQ Discrete Input Confg IAQINCFG config
IAQ Disc.In. Fan Config IAQINFAN config
IAQ Econo Override Pos. % IAQOVPOS config
Diff.Air Quality LoLimit DAQ_LOW config
Diff.Air Quality HiLimit DAQ_HIGH config
DAQ PPM Fan Off Setpoint DAQFNOFF config
DAQ PPM Fan On Setpoint DAQFNON config
Diff. AQ Responsiveness IAQREACT config
IAQ Low Reference IAQREFL config
IAQ High Reference IAQREFH config
OAQ Lockout Value OAQLOCK config
OAQ 4-20ma Sensor Config ma OAQANCFG config
IAQ milliamps ma IAQ_MA
OAQ milliamps OAQ_MA