CONTROLS QUICK START

The following section will provide a quick user guide to set-
ting up and configuring the Z Series units with ComfortLink™
controls. See Basic Control Usage section on page 4 for infor-
mation on operating the control.

Two-Stage Constant Volume Units with

Mechanical Thermostat — To configure the unit, per-
form the following:
1. The type of control is configured under Configuration
UNIT
C.TYP. Set C.TYP to 4 (TSTAT 2 STG).
2. Remove jumpers from R-W2 and W2-W1 on TB202 in
the control box.
3. See Economizer Options section on page 34 for addition-
al economizer option configurations.
4. See Exhaust Options section on page 34 for additional
exhaust option configurations.

Two-Stage Constant Volume Units with Space

Sensor — To configure the unit, perform the following:
1. The type of control is configured under Configuration
UNIT
C.TYP. Set C.TYP to 6 (SPT 2 STG).
2. Under Configuration
SENS
SPT.S, enable the space
sensor by setting SPT.S to ENBL (enable).
3. The space temperature set points are configured under the
Setpoints menu. The heating and cooling set points must
be configured. See the Heating Control and Cooling
Control sections on pages 54 and 45 for further descrip-
tion on these configurations. Configure the following set
points:
4. The degrees of demand from the space temperature set
points are configured under the Configuration
D.LV.T
submenu. See the Heating Control and Cooling Control
sections for further description on these configurations.
Configure the following set points:
5. Install jumpers between R-W2 and W2-W1.
6. Under Configuration
UNIT
CV.FN, set CV.FN to 1
for continuous fan or 0 for automatic fan.
7. To program time schedules, set SCH.N=1 under Config-
uration
CCN
SC.OV
SCH.N to configure the con-
trol to use local schedules.
8. Under the Timeclock
SCH.L submenu, enter the
desired schedule. See Time Clock section for further
descriptions of these configurations.
9. Under the Configuration
CCN
SC.OV submenu, the
following schedules and overrides should be configured:
10. See Economizer Options section on page 34 for addition-
al economizer option configurations.
11. See Exhaust Options section on page 34 for additional
exhaust option configurations.

Variable Air Volume Units Using Return Air

Sensor or Space Temperature Sensor — To
configure the unit, perform the following:
1. The type of control is configured under Configuration
UNIT
C.TYP. Set C.TYP to 1 (VAV-RAT) for return
air sensor. Set C.TYP to 2 (VAV-SPT) for space tempera-
ture sensor.
NOTE: For VAV with a space sensor (VAV-SPT), under
Configuration
UNIT
SENS
SPT.S, enable the
space sensor by setting SPT.S to ENBL.
2. The space temperature set points and the supply air set
points are configured under the Setpoints menu. The
heating and cooling set points must be configured. See
the Heating Control and Cooling Control sections for
further description on these configurations. Configure the
following set points:
3. To program time schedules, make sure SCH.N=1 under
Configuration
CCN
SC.OV
SCH.N to configure
the control to use local schedules.
4. Under the Timeclock
SCH.L submenu, enter the de-
sired schedule. See Time Clock section for further
descriptions of these configurations.
5. Under Configuration
SP
SP.SP, the Supply Duct
Static Pressure set point should be configured.
6. If supply air temperature reset is desired, under the
Configuration
EDT.R submenu, the following set
points should be configured:
NOTE: Configure either RTIO and LIMT or RES.S. All three
are not used.
7. See the Economizer Options section on page 34 for addi-
tional economizer option configurations.
8. See the Exhaust Options section on page 34 for addition
exhaust option configurations.

Multi-Stage Constant Volume Units with

Mechanical Thermostat — To configure the unit, per-
form the following:
1. Under Configuration
UNIT
C.TYP, set C.TYP to 3
(TSTAT MULTI).
2. Remove jumpers from R-W2 and W2-W1 on TB202 in
the control box.
3. Under the Setpoints menu, set the following
configurations:
OHSP Occupied Heat Setpoint
OCSP Occupied Cool Setpoint
UHSP Unoccupied Heat Setpoint
UCSP Unoccupied Cool Setpoint
GAP Heat-Cool Setpoint Gap
L.H.ON Demand Level Lo Heat On
H.H.ON Demand Level Hi Heat On
L.H.OF Demand Level Lo Heat Off
L.C.ON Demand Level Lo Cool On
H.C.ON Demand Level Hi Cool On
L.C.OF Demand Level Lo Cool Off
O.T.L. Override time limit
SPT.O SPT override enabled?
T58.O T58 override enabled?
OHSP Occupied Heat Set point
OCSP Occupied Cool Set point
UHSP Unoccupied Heat Set point
UCSP Unoccupied Cool Set point
GAP Heat-Cool Set point Gap
SP.SP Static Pressure Set point
RS.CF EDT Reset Configuration
RTIO Reset Ratio
LIMT Reset Limit
RES.S EDT 4-20 mA Reset Input
SA.HI Supply Air Set Point Hi
SA.LO Supply Air Set Point Lo