93
Table 79 — Economizer Run Status Display Table
Table 80 — Cooling Information Display Table
Table 81 — Mode Trip Helper Display Table
CCN/LINKAGE DISPLAY TABLE — The CCN/Linkage
display table provides information on unit linkage. See Table 82.
COMPRESSOR RUN HOURS DISPLAY TABLE — The
Compressor Run Hours Display Table displays the number of
run time hours for each compressor. See Table 83.
COMPRESSOR STARTS DISPLAY TABLE — The Com-
pressor Starts Display Table displays the number of starts for
each compressor. See Table 84.
SOFTWARE VERSION NUMBERS DISPLAY TABLE —
The Software Version Numbers Display Table displays the
software version numbers of the unit boards and devices. See
Table 85.
ITEM EXPANSION RANGE UNITS POINT WRITE STATUS
ECON ECONOMIZER RUN STATUS
ECN.P Economizer Act.Curr.Pos. 0-100 % ECONOPOS
EC2.P Economzr2 Act.Curr.Pos. 0-100 % ECON2POS
ECN.C Economizer Act.Cmd.Pos. 0-100 % ECONOCMD forcible
ACTV Economizer Active ? YES/NO ECACTIVE
DISA ECON DISABLING CONDITIONS
DISAUNV.1 Econ Act. Unavailable? YES/NO ECONUNAV
DISAUNV.2 Econ2 Act. Unavailable? YES/NO ECN2UNAV
DISAENTH Enth. Switch Read High ? YES/NO ENTH
DISADBC DBC - OAT Lockout? YES/NO DBC_STAT
DISADEW DEW - OA Dewpt.Lockout? YES/NO DEW_STAT
DISADDBC DDBD- OAT > RAT Lockout? YES/NO DDBCSTAT
DISAOAEC OAEC- OA Enth Lockout? YES/NO OAECSTAT
DISADEC DEC - Diff.Enth.Lockout? YES/NO DEC_STAT
DISAEDT EDT Sensor Bad? YES/NO EDT_STAT
DISAOAT OAT Sensor Bad ? YES/NO OAT_STAT
DISAFORC Economizer Forced ? YES/NO ECONFORC
DISASFON Supply Fan Not On 30s ? YES/NO SFONSTAT
DISACLOF Cool Mode Not In Effect? YES/NO COOL_OFF
DISAOAQL OAQ Lockout in Effect ? YES/NO OAQLOCKD
DISAHELD Econ Recovery Hold Off? YES/NO ECONHELD
DISADH.DS Dehumid. Disabled Econ.? YES/NO DHDISABL
O.AIR OUTSIDE AIR INFORMATION
O.AIROAT Outside Air Temperature dF OAT forcible
O.AIROA.RH Outside Air Rel. Humidity % OARH forcible
O.AIROA.E Outside Air Enthalpy OAE
O.AIROA.D.T OutsideAir Dewpoint Temp dF OADEWTMP
ITEM EXPANSION RANGE UNITS POINT WRITE STATUS
COOL COOLING INFORMATION
C.CAP Current Running Capacity % CAPTOTAL
CUR.S Current Cool Stage COOL_STG
REQ.S Requested Cool Stage CL_STAGE
MAX.S Maximum Cool Stages CLMAXSTG
DEM.L Active Demand Limit % DEM_LIM forcible
SUMZ COOL CAP. STAGE CONTROL
SUMZSMZ Capacity Load Factor -100 +100 SMZ
SUMZADD.R Next Stage EDT Decrease ^F ADDRISE
SUMZSUB.R Next Stage EDT Increase ^F SUBRISE
SUMZR.PCT Rise Per Percent Capacity RISE_PCT
SUMZY.MIN Cap Deadband Subtracting Y_MINUS
SUMZY.PLU Cap Deadband Adding Y_PLUS
SUMZZ.MIN Cap Threshold Subtracting Z_MINUS
SUMZZ.PLU Cap Threshold Adding Z_PLUS
SUMZH.TMP High Temp Cap Override HI_TEMP
SUMZL.TMP Low Temp Cap Override LOW_TEMP
SUMZPULL Pull Down Cap Override PULLDOWN
SUMZSLOW Slow Change Cap Override SLO_CHNG
ITEM EXPANSION RANGE UNITS POINT WRITE STATUS
TRIP MODE TRIP HELPER
UN.C.S Unoccup. Cool Mode Start UCCLSTRT
UN.C.E Unoccup. Cool Mode End UCCL_END
OC.C.S Occupied Cool Mode Start OCCLSTRT
OC.C.E Occupied Cool Mode End OCCL_END
TEMP Ctl.Temp RAT,SPT or Zone CTRLTEMP
OC.H.E Occupied Heat Mode End OCHT_END
OC.H.S Occupied Heat Mode Start OCHTSTRT
UN.H.E Unoccup. Heat Mode End UCHT_END
UN.H.S Unoccup. Heat Mode Start UCHTSTRT
HVAC ascii string spelling out the hvac modes string