93
Table 79 — Economizer Run Status Display Table
Table 80 — Cooling Information Display Table
Table 81 — Mode Trip Helper Display Table
CCN/LINKAGE DISPLAY TABLE — The CCN/Linkage
display table provides information on unit linkage. See Table 82.
COMPRESSOR RUN HOURS DISPLAY TABLE — The
Compressor Run Hours Display Table displays the number of
run time hours for each compressor. See Table 83.
COMPRESSOR STARTS DISPLAY TABLE — The Com-
pressor Starts Display Table displays the number of starts for
each compressor. See Table 84.
SOFTWARE VERSION NUMBERS DISPLAY TABLE —
The Software Version Numbers Display Table displays the
software version numbers of the unit boards and devices. See
Table 85.
ITEM EXPANSION RANGE UNITS POINT WRITE STATUS
ECON ECONOMIZER RUN STATUS
→ECN.P Economizer Act.Curr.Pos. 0-100 % ECONOPOS
→EC2.P Economzr2 Act.Curr.Pos. 0-100 % ECON2POS
→ECN.C Economizer Act.Cmd.Pos. 0-100 % ECONOCMD forcible
→ACTV Economizer Active ? YES/NO ECACTIVE
→DISA ECON DISABLING CONDITIONS
→DISA→UNV.1 Econ Act. Unavailable? YES/NO ECONUNAV
→DISA→UNV.2 Econ2 Act. Unavailable? YES/NO ECN2UNAV
→DISA→ENTH Enth. Switch Read High ? YES/NO ENTH
→DISA→DBC DBC - OAT Lockout? YES/NO DBC_STAT
→DISA→DEW DEW - OA Dewpt.Lockout? YES/NO DEW_STAT
→DISA→DDBC DDBD- OAT > RAT Lockout? YES/NO DDBCSTAT
→DISA→OAEC OAEC- OA Enth Lockout? YES/NO OAECSTAT
→DISA→DEC DEC - Diff.Enth.Lockout? YES/NO DEC_STAT
→DISA→EDT EDT Sensor Bad? YES/NO EDT_STAT
→DISA→OAT OAT Sensor Bad ? YES/NO OAT_STAT
→DISA→FORC Economizer Forced ? YES/NO ECONFORC
→DISA→SFON Supply Fan Not On 30s ? YES/NO SFONSTAT
→DISA→CLOF Cool Mode Not In Effect? YES/NO COOL_OFF
→DISA→OAQL OAQ Lockout in Effect ? YES/NO OAQLOCKD
→DISA→HELD Econ Recovery Hold Off? YES/NO ECONHELD
→DISA→DH.DS Dehumid. Disabled Econ.? YES/NO DHDISABL
→O.AIR OUTSIDE AIR INFORMATION
→O.AIR→OAT Outside Air Temperature dF OAT forcible
→O.AIR→OA.RH Outside Air Rel. Humidity % OARH forcible
→O.AIR→OA.E Outside Air Enthalpy OAE
→O.AIR→OA.D.T OutsideAir Dewpoint Temp dF OADEWTMP
ITEM EXPANSION RANGE UNITS POINT WRITE STATUS
COOL COOLING INFORMATION
→C.CAP Current Running Capacity % CAPTOTAL
→CUR.S Current Cool Stage COOL_STG
→REQ.S Requested Cool Stage CL_STAGE
→MAX.S Maximum Cool Stages CLMAXSTG
→DEM.L Active Demand Limit % DEM_LIM forcible
→SUMZ COOL CAP. STAGE CONTROL
→SUMZ→SMZ Capacity Load Factor -100 → +100 SMZ
→SUMZ→ADD.R Next Stage EDT Decrease ^F ADDRISE
→SUMZ→SUB.R Next Stage EDT Increase ^F SUBRISE
→SUMZ→R.PCT Rise Per Percent Capacity RISE_PCT
→SUMZ→Y.MIN Cap Deadband Subtracting Y_MINUS
→SUMZ→Y.PLU Cap Deadband Adding Y_PLUS
→SUMZ→Z.MIN Cap Threshold Subtracting Z_MINUS
→SUMZ→Z.PLU Cap Threshold Adding Z_PLUS
→SUMZ→H.TMP High Temp Cap Override HI_TEMP
→SUMZ→L.TMP Low Temp Cap Override LOW_TEMP
→SUMZ→PULL Pull Down Cap Override PULLDOWN
→SUMZ→SLOW Slow Change Cap Override SLO_CHNG
ITEM EXPANSION RANGE UNITS POINT WRITE STATUS
TRIP MODE TRIP HELPER
→UN.C.S Unoccup. Cool Mode Start UCCLSTRT
→UN.C.E Unoccup. Cool Mode End UCCL_END
→OC.C.S Occupied Cool Mode Start OCCLSTRT
→OC.C.E Occupied Cool Mode End OCCL_END
→TEMP Ctl.Temp RAT,SPT or Zone CTRLTEMP
→OC.H.E Occupied Heat Mode End OCHT_END
→OC.H.S Occupied Heat Mode Start OCHTSTRT
→UN.H.E Unoccup. Heat Mode End UCHT_END
→UN.H.S Unoccup. Heat Mode Start UCHTSTRT
→HVAC ascii string spelling out the hvac modes string