CONTROLS SET POINT AND CONFIGURATION LOG (cont)
ITEM EXPANSION RANGE DEFAULT SETTING
CCN (cont)
SC.OVSPT.O SPT Override Enabled ? YES/NO Yes
SC.OVT58.O T58 Override Enabled ? YES/NO Yes
SC.OVGL.OV Global Sched. Override ? YES/NO No
ALLM ALERT LIMIT CONFIG.
SP.L.O SPT lo alert limit/occ -10-245 dF 60
SP.H.O SPT hi alert limit/occ -10-245 dF 85
SP.L.U SPT lo alert limit/unocc -10-245 dF 45
SP.H.U SPT hi alert limit/unocc -10-245 dF 100
SA.L.O EDT lo alert limit/occ -40-245 dF 40
SA.H.O EDT hi alert limit/occ -40-245 dF 100
SA.L.U EDT lo alert limit/unocc -40-245 dF 40
SA.H.U EDT hi alert limit/unocc -40-245 dF 100
RA.L.O RAT lo alert limit/occ -40-245 dF 60
RA.H.O RAT hi alert limit/occ -40-245 dF 90
RA.L.U RAT lo alert limit/unocc -40-245 dF 40
RA.H.U RAT hi alert limit/unocc -40-245 dF 100
OAT.L OAT lo alert limit -40-245 dF -40
OAT.H OAT hi alert limit -40-245 dF 150
R.RH.L RARH low alert limit 0-100% 0
R.RH.H RARH high alert limit 0-100% 100
O.RH.L OARH low alert limit 0-100% 0
O.RH.H OARH high alert limit 0-100% 100
SP.L SP low alert limit 0-5 "H2O 0
SP.H SP high alert limit 0-5 "H2O 2
BP.L BP lo alert limit -0.25-0.25 "H2O -0.25
BP.H BP high alert limit -0.25-0.25 "H2O 0.25
IAQ.H IAQ high alert limit 0-5000 1200
TRIM SENSOR TRIM CONFIG.
SAT.T Air Temp Lvg SF Trim -10 - 10 ^F 0
RAT.T RAT Trim -10 - 10 ^F 0
OAT.T OAT Trim -10 - 10 ^F 0
SPT.T SPT Trim -10 - 10 ^F 0
L.SW.T Limit Switch Trim -10 - 10 ^F 0
CCT.T Air Temp Lvg Evap Trim -10 - 10 ^F 0
SP.A.T Suct.Press.Circ.A Trim -50 - 50 PSIG 0
SP.B.T Suct.Press.Circ.B Trim -50 - 50 PSIG 0
DP.A.T Dis.Press.Circ.A Trim -50 - 50 PSIG 0
DP.B.T Dis.Press.Circ.B Trim -50 - 50 PSIG 0
SW.LG SWITCH LOGIC: NO / NC
FTS.L Filter Status Inpt-Clean Open/Close Open
IGC.L IGC Feedback - Off Open/Close Open
RMI.L RemSw Off-Unoc-Strt-NoOv Open/Close Open
ENT.L Enthalpy Input - Low Open/Close Close
SFS.L Fan Status Sw. - Off Open/Close Open
DL1.L Dmd.Lmt.Sw.1 - Off Open/Close Open
DL2.L Dmd.Lmt.Sw.2 - Off Open/Close Open
IAQ.L IAQ Disc.Input - Low Open/Close Open
FSD.L Fire Shutdown - Off Open/Close Open
PRS.L Pressurization Sw. - Off Open/Close Open
EVC.L Evacuation Sw. - Off Open/Close Open
PRG.L Smoke Purge Sw. - Off Open/Close Open
DH.LG Dehumidify Sw. - Off Open/Close Open
DISP DISPLAY CONFIGURATION
TEST Test Display LEDs ON/OFF Off
METR Metric Display ON/OFF Off
LANG Language Selection 0 - 1 (multi-text strings) 0
PAS .E Password Enable ENABLE/DISABLE Enable
PAS S Service Password 0000 - 9999 1111