Alarms and Alerts — There are a variety of different
alerts and alarms in the system.
T — Alert: Part of the unit is down, but the unit is still par-
tially able to provide cooling or heating.
A — Alarm: The unit is down and is unable to provide cool-
ing or heating.
All alarms are displayed with a code of AXXX or TXXX
where XXX is the alarm/alert number. All alerts start with “T”
and all alarms start with “A”. The response of the control sys-
tem to various alerts and alarms depends on the seriousness of
the particular alert or alarm. In the mildest case, an alert does
not affect the operation of the unit in any manner.
In addition, the compressors have several diagnostics
monitoring the safety of the system which may cause a
number of attempts to be re-tried before locking out the system
from operation. This feature reduces the likelihood of false
alarms causing a properly working system to be shutdown in-
correctly.
For the compressor and circuit diagnostics, some of these
alerts/alarms will not broadcast an initial failure to the CCN
network until all attempts to recover have occurred and failed.
These alerts will be accessible in the alarm history of the
control (Alarms
HIST).
All the alarms and alerts are summarized in Table 86.
ITEM EXPANSION RANGE UNITS POINT WRITE STATUS
LINK CCN - LINKAGE
MODE Linkage Active - CCN ON/OFF MODELINK
L.Z.T Linkage Zone Control Tmp dF LZT
L.C.SP Linkage Curr. Cool Setpt dF LCSP
L.H.SP Linkage Curr. Heat Setpt dF LHSP
ITEM EXPANSION RANGE UNITS POINT WRITE STATUS
HRS COMPRESSOR RUN HOURS
HR.A1 Compressor A1 Run Hours 0-999999 HRS HOURS_A1 config
HR.A2 Compressor A2 Run Hours 0-999999 HRS HOURS_A2 config
HR.B1 Compressor B1 Run Hours 0-999999 HRS HOURS_B1 config
HR.B2 Compressor B2 Run Hours 0-999999 HRS HOURS_B2 config
ITEM EXPANSION RANGE UNITS POINT WRITE STATUS
STRT COMPRESSOR STARTS
ST.A1 Compressor A1 Starts 0-999999 CY_A1 config
ST.A2 Compressor A2 Starts 0-999999 CY_A2 config
ST.B1 Compressor B1 Starts 0-999999 CY_B1 config
ST.B2 Compressor B2 Starts 0-999999 CY_B2 config
ITEM EXPANSION RANGE UNITS POINT WRITE STATUS
VERS SOFTWARE VERSION NUMBERS
MBB CESR131292-xx-xx string
RCB CESR131249-xx-xx string
ECB CESR131249-xx-xx string
SCB CESR131226-xx-xx string
CEM CESR131174-xx-xx string
ECON xx-xx-xxx-xxx-xx string
IGV xx-xx-xxx-xxx-xx string
HUMD xx-xx-xxx-xxx-xx string
HEAT xx-xx-xxx-xxx-xx string
BP1 xx-xx-xxx-xxx-xx string
BP2 xx-xx-xxx-xxx-xx string
MARQ CESR131171-xx-xx string
NAVI CESR130227-xx-xx string