Carrier Access 770-0125-AB RTRV-EQPTNSP-x.PWR-11234, ED-EQPTNSP1234ENA, ED-EQPTNSP1234DIS

Models: 770-0125-AB

1 96
Download 96 pages 9.24 Kb
Page 70
Image 70

Configuration

Setting System Node Parameters

To view the power input redundancy status of the system, use the RTRV-EQPTTL1 command:

RTRV-EQPT::NSP-x.PWR-1:1234;

To enable or disable power input redundancy, use the ED-EQPTTL1 command:

ED-EQPT::NSP:1234::<setting>;

<setting>ENA,ENABLE, ENABLED, DIS, DISABLE, or DISABLED.

Examples:

Enable power supply input redundancy (assuming NSP-1 is the active NSP):

ED-EQPT::NSP:1234::ENA;

Disable power supply input redundancy (assuming NSP-1 is the active NSP):

ED-EQPT::NSP:1234::DIS;

If you have installed two separate power sources to the BROADway chassis (both FEED A and FEED B on the back of the chassis), you should enable power input supply redundancy. (For information about connecting these power feeds, see Cabling Power and Ground on page 2-6.) If you do not have two separate power sources connected to the chassis, you should disable power supply redundancy; otherwise, the NSP PWR alarm LED will lamp red (as described in the online help).

3-22

BROADway - Release 4.00

Page 70
Image 70
Carrier Access 770-0125-AB installation manual RTRV-EQPTNSP-x.PWR-11234, ED-EQPTNSP1234ENA, ED-EQPTNSP1234DIS