Rack Temperature Requirements
The operating temperature inside the rack will always be higher than the room temperature, and is dependent on the configuration of equipment in your rack. The TMRA for each piece of equipment should be checked before installation. The maximum internal rack temperature for your configuration should not exceed the values in the following table:
Table
Rack Internal Temperature Maximums
| Equipment Included | Maximum InternalRack Temperature | |
50°C/122°F | |||
|
|
|
|
Compaq | 40°C/104°F | ||
|
|
|
|
Other manufacturers' options | See other manufacturers' specifications | ||
|
|
|
|
|
|
|
|
CAUTION: To reduce the risk of damage to the equipment when installing
■Ensure that the option equipment does not impede airflow to the
beyond the Compaq specified maximum rating.
■Ensure that the Manufacturer’s Maximum Recommended Ambient Operating Temperature of the option equipment is not exceeded when installed in the rack.