RC GROUP - 149_ItEn.0102
102
PARAMETRI TEMPORIZZAZIONI
TIMING PARAMETERS
Premere per 4 secondi
HOME
1
PRG
3
Press for 4 seconds
quindi inserire Password
than digit Password
ON DISPLAY TIPO DI SET
SET TYPE
DEFAULT RANGE SYMBOL
Time delay switching main fan on ritardo attivazione ventilatore principale
main fan on delay
2s 0÷600 s
Time delay switching main fan off ritardo disattivazione ventilatore principale
main fan off delay
10s 0÷600 s
Alarm delay time low pressure ritardo allarme bassa pressione
low pressure alarm delay
300s 0÷600 s
Alarm delay time air flow ritardo allarme flusso aria
air flow alarm delay
15s 0÷600 s
Alarm delay time oil diff. ritardo allarme pressione differenziale olio
differential oil pressure alarm delay
120s 0÷600 s
Hi/lo temp. alarm delay time ritardo allarme alta/bassa temperatura
low/high temperature alarm delay
300s 0÷9999 s
Hi/lo humidity alarm delay time ritardo allarme alta/bassa umidità
low/high umidity alarm delay
1800s 0÷9999 s
Minimum compressor off time tempo minimo di fermo compressore
minimum off time compressor
120s 0÷600 s
Minimum compressor on time tempo minimo di funz. compressore
minimum on time compressor
60s 0÷600 s
Delay between starts same comp. ritardo minimo tra gli avviamenti dello
minimum delay between starts
stesso compressore
of the same compressor
180s 0÷600 s
Delay between starts diff. comp. ritardo minimo tra lavviamento di un
minimum delay between start of one
compressore ed il successivo
compressor and the next one
. 10s 0÷600 s
Delay between starts two unload. ritardo minimo per passaggio da 100%
minimum delay to change from 100%
a 50% capacità e viceversa.
to 50% capacity and viceversa.
(parzializzazioni o doppia velocità)
(unloading or double speed)
10s 0÷600 s
INIZIALIZZAZIONE UNITA
UNIT INITIALIZATION
Premere per 4 secondi
HOME
1
PRG
3
Press for 4 seconds
quindi inserire Password
than digit Password
ON DISPLAY TIPO DI SET
SET TYPE
DEFAULT RANGE SYMBOL
Do you want insert manufacturer vuoi inserire i parametri manufacturer?
do you want insert manufacturer
parameters?
parameters?
ripristino set di base
reset to default set
N N - Y
SET PROGRAMMABILI
PROGRAM SETS
Premere
PRG
3
Press
quindi inserire Password
than digit Password
ON DISPLAY TIPO DI SET
SET TYPE
DEFAULT RANGE SYMBOL
Temperature set point limits limiti set point temperatura
temperature set point limits
Minimum minimo
minimum
10°C0÷50 °C
Maximum massimo
maximum
30°C0÷50 °C
Humiditiy set point limits limiti set point umidità
humidity set point limits
Minimum minimo
minimum
35%rH 30÷90 %rH
Maximum massimo
maximum
80%rH 30÷90 %rH
Interg. humidifier production produzione vapore umidificatore
steam humidifier production
3Kg/h 1,4÷5 Kg/h
Defrosting limit limite per sbrinamento ad aria
limit for defrost with air
5°C0÷15°C
Defrosting cycle tempo minimo tra due sbrinamenti
minimum time between defrost
15min 15÷120min
Defrosting time durata massima sbrinamento
max defrost duration
6min 3÷15min
Pressure defrost stop stop sbrinamento con inversione di ciclo
defrost stop with reversing cycle
2000kPa 1500÷2200kPa
Defrost with main fan on sbrinamento con ventilatore attivo
Defrost with main fan on
Y N - Y
Local off switch enabled abilitazione tasto ON/OFF locale
local ON/OFF switch enabled
Y N - Y
Control condensing pressure pressione controllo condensazione
control condensing pressure
Setpoint valore sengale proporzionale minimo
proportional signal min. value
1400kPa 0÷3000 kPa zPs
Differential valore sengale proporzionale massimo
proportional signal max. value
300kPa 0÷1000 kPa zP
Control condensing pressure pressione controllo condensazione
control condensing pressure
(compr. off) (compressore off)
(compressor off)
On (max V) vent. condensatore ON con compr. OFF
cond. fan ON with compr. OFF
2200kPa 0÷3000 kPa zON
Off (min V) vent. condensatore OFF con compr. OFF
cond. fan OFF with compr.OFF
2000kPa 0÷3000 kPa zOFF
Condensing output min value valore mimino uscita condensazione
condensing output min value
3V 0÷5 V zPmin
Condensing output max value valore massimo uscita condensazione
condensing output max value
10V 5÷10 V zPmax
Maximum pressure value massimo valore di pressione
max pressure value
2500kPa 0÷4000 kPa zH.Alarm
Max compensation setpoint massimo valore di compensazione
max compensation value
5°C±20 °C
Reaction time tempo di reazione compensazione
compensation reaction time
5min 2÷30 min
Offset room temp. high preal. preallame alta temperatura ambiente
high room temperature prealarm
4,5°C (offset) 2÷20 °C xH.Prealarm
Offset room temp. low alarm allarme bassa temperatura ambiente
low room temperature alarm
4,5°C (offset) 2÷20 °C xL.Alarm
Offset room temp. high alarm allarme alta temperatura ambiente
high room temperature alarm
5,5°C (offset) 2÷20 °C xH.Alarm
Offset room humidity low alarm allarme bassa umidità ambiente
low room humidity alarm
14%rH (offset) 5÷50 %rH yL.Alarm
Offset room humidity high alarm allarme alta umidità ambiente
high room humidity alarm
14%rH (offset) 5÷50 %rH yH.Alarm
Alarm lo pressure (cool pos.) allarme bassa pressione (raffreddamento)
Alarm lo pressure (cooling)
250kPa 150÷500kPa
Set point fresh air set point % aria esterna
setpoint % fresh air
30% 0÷100% Af
MP2000 AIR CONDITIONERS
Software per condizionatori d'aria a pompa di calore e Roof Top EPROM CPX....
Software for heat pump air conditioners and Roof Top