9.6: Analog Input Modules

Analog Input Modules Specifications

 

8AI1: 8-Channel Analog Input, 0±1mA

 

 

Model Numbers

8AI2: 8-Channel Analog Input, 0±20mA

 

 

8AI3: 8-Channel Analog Input, 0±5Vdc

 

 

8AI4: 8-Channel Analog Input, 0±10Vdc

Accuracy

0.1% of Full Scale

 

 

Scaling

Programmable

 

 

Communication

RS-485, Modbus RTU

 

 

Programmable Baud Rates: 4800, 9600, 19200,57600

 

 

 

Power Requirement

15-20Vdcat 50-200mA;

Nexus 1250/1252 Unit

 

supports up to 4 Modules

 

 

Operating Temperature

(-20 to 79)°C / (-4 to +158)°F

 

 

 

Maximum Load

0-1mA: 10k Ω;

4-20mA: 500 Ω

Impedance

 

 

 

 

 

Modbus Address:

 

8AI1, 0±1mA: 136;

8AI2, 0±20mA: 140

Factory Settings

8AI3, 0±5Vdc: 144,

8AI4, 0±10Vdc: 148

 

 

 

Baud Rate: 57600

 

 

 

Transmit Delay Time: 0

 

 

 

Modbus Address: 247

Default Settings

 

 

Baud Rate: 57600

(Reset Button)

 

 

 

Transmit Delay Time: 20 csec

 

 

 

9.6.1: Overview

The Analog Input Modules (0±1mA, 0±20mA, 0±5Vdc and 0±10Vdc) are available in 8-channel format. Maximum registers per request, read or write, is 17 registers.

Nexus 1250/1252 Unit supplies power for up to 4 connected Analog Input modules. See section 9.2 for power and communication details. Refer to sections 5.12 - 5.13 to determine if you must use an additonal power source, such as the EIG PSIO.

All inputs share a single common point. This is also an isolated connection (from ground).

Electro Industries/GaugeTech Doc # E107706 V1.25

9-9

Page 121
Image 121
Electro-Voice 1252, 250 operation manual Analog Input Modules