9.7: Digital Dry Contact Relay Output (Form C) Module

Digital Dry Contact Relay Output (Form C) Module Specifications

Model Number

4RO1: 4 Latching Relay Outputs

 

 

 

Accuracy

0.1% of Full Scale

 

 

 

 

Scaling

Programmable

 

 

 

 

Communication

RS-485, Modbus RTU

 

 

 

 

Programmable Baud Rates: 4800, 9600, 19200, 57600

 

 

 

Power Requirement

15–20Vdcat 50–200 mA;

Nexus 1250/1252 Unit

 

 

supports up to 4 Modules

 

 

 

Operating Temperature

(-20 to 79)°C /

(-4 to +158)°F

 

 

 

 

Maximum Load Impedance

0-1mA: 10k Ω;

4-20mA:

500 Ω

 

 

 

 

Modbus Address: 156

 

Factory Settings

 

 

Baud Rate: 57600

 

 

 

 

 

Transmit Delay Time:

0

 

 

 

Default Settings

Modbus Address: 247

 

 

 

 

Baud Rate: 57600

 

(Reset Button)

 

 

 

 

 

Transmit Delay Time: 20 csec

 

 

 

 

9.7.1: Overview

The Relay Output Module consists of four Latching Relay Outputs. In Normal Mode, the device accepts commands to control the relays. Relay output modules are triggered by limits programmed with the Communicator EXT software. See the Communicator EXT User Manual for details on programming limits.

Nexus 1250/1252 Unit supplies power for up to 4 connected Relay Output modules. See section 9.2 for power and communication details. Refer to sections 5.12 - 5.13 to determine if you must use an additonal power source, such as the EIG PSIO.

The Modbus Map for the Analog Output Module (and operating details) can be found in the Modbus Communicating I/O Modules Manual.

Each latching relay will hold its state in the event of a power loss.